Plan Review Details - Permit 04050036
Plan Review Stops For Permit 04050036
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-08-17 Cont ID  
Sent By csiegber Date 2004-08-17 Time 14:31 Rev Time 0.00
Received By csiegber Date 2004-08-17 Time 14:31 Sent To P
Notes
2004-08-17 00:00:00TO GAS/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-05-19 Cont ID  
Sent By csiegber Date 2004-05-19 Time 12:59 Rev Time 0.00
Received By csiegber Date 2004-05-19 Time 12:59 Sent To P
Notes
2004-05-19 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-03 Cont ID  
Sent By csiegber Date 2004-05-03 Time 14:18 Rev Time 0.00
Received By csiegber Date 2004-05-03 Time 14:18 Sent To P
Notes
2004-05-03 00:00:00TO GAS

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-08-21 Cont ID  
Sent By kstevens Date 2004-08-21 Time 15:24 Rev Time 0.50
Received By kstevens Date 2004-08-21 Time 15:24 Sent To  
Notes
2004-08-21 00:00:00REVISION OK - CHANGED PE PIPE TO 100'
 FROM 50' - MOST REMOTE NOT 125' PIPE
 SIZE OK
  
  
  
  
  
  
  
 PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING.
  
 IF DRYER ROOM IS A CONFINED SPACE,
 OPENINGS REQUIRED PER SECTION 304.3.1 0R
 SECTION 304.3.2 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
  
  
  
  
  
  
  
  
  
 X

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-06-03 Cont ID  
Sent By csiegber Date 2004-08-17 Time 14:31 Rev Time 0.50
Received By kstevens Date 2004-06-03 Time 11:22 Sent To  
Notes
2004-06-03 00:00:00 
  
  
  
 PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING.
  
 IF DRYER ROOM IS A CONFINED SPACE,
 OPENINGS REQUIRED PER SECTION 304.3.1 0R
 SECTION 304.3.2 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
  
  
  
  
  
  
  
  
  
  
 Z

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-05-15 Cont ID  
Sent By csiegber Date 2004-05-19 Time 12:59 Rev Time 1.25
Received By pschmitz Date   Time   Sent To  
Notes
2004-05-15 00:00:00PLAN REVIEW, DENIED FBC 2001 FUEL GAS.
 RFI DRWG SHOWS 150' TO BAR-BA-Q, LONGEST
 RUN SHOWS 75' ???
 TWO ADDITIONAL OPENINGS ON SAMWE LINE?
 WHAT ARE THESE FOR????
 END OF COMMENTS QUESTIONS 561-805-6692