Plan Review Details - Permit 04042064
Plan Review Stops For Permit 04042064
Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2005-12-21 Cont ID  
Sent By jgomez Date 2005-12-21 Time 11:31 Rev Time 1.00
Received By jgomez Date 2005-12-21 Time 11:31 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2005-04-11 Cont ID  
Sent By jgomez Date 2005-04-11 Time 14:49 Rev Time 1.00
Received By jgomez Date 2005-04-11 Time 14:49 Sent To PC
Notes
2005-04-11 00:00:00BUILDING LOCATED IN FLOOD ZONE A5. NEED
 TO PROVIDE THE ELEVATION CERTIFICATE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2005-03-14 Cont ID  
Sent By jgomez Date 2005-03-14 Time 10:55 Rev Time 1.00
Received By jgomez Date 2005-03-14 Time 10:55 Sent To Z
Notes
2005-03-14 00:00:00BUILDING REVISION CHECKLIST:
 1- BRING REVISED DRAWINGS TO PALM BEACH
 COUNTY TO UPDATE SQUARE FOOTAGE. BRING
 BACK STAMPED DRAWINGS AND PAID RECEIPT
 IF ADDITIONAL FEES ARE DUE.
  
 2- OWNER/AGENT TO SIGN AND DATE THE
 ENERGY CALCULATIONS.
  
 3- NEED SMOKE DETECTORS ON FIRST FLOOR
 CLOSE TO THE NEW STAIRS AND AT THE
 SECOND FLOOR. SEC. 905.2.2 FBC 2001.
  
 4- OWES $706.99 FOR ADDITIONAL A/C AREA
 AND RADON FEES.
  
 5- SHEET S-3. INFORMATION BY GARAGE AREA
 IS NOT LEGIBLE BECAUSE NOTES ARE
 OVERLAPPING. REVISE AS REQUIRED.
  
 6- CONTRACTOR NEEDS TO UPDATE WORKER'S
 COMPENSATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-12-28 Cont ID  
Sent By jgomez Date 2004-12-28 Time 11:17 Rev Time 0.25
Received By jgomez Date 2004-12-28 Time 11:16 Sent To  
Notes
2004-12-28 00:00:00RECEIVED PILE TEST RESULTS. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-11-04 Cont ID  
Sent By jgomez Date 2004-11-04 Time 14:59 Rev Time 0.00
Received By jgomez Date 2004-11-04 Time 14:59 Sent To PC
Notes
2004-11-04 00:00:00SUBMITTED ENGINEERING REPORTS WITH
 ORIGINAL SIGNATURES AND SEALS.AND,
 REVISED TRUSS ANCHOR SCHEDULE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-10-21 Cont ID  
Sent By csiegber Date 2004-10-25 Time 16:14 Rev Time 2.50
Received By jgomez Date 2004-10-21 Time 16:14 Sent To PC
Notes
2004-10-21 00:00:00BUILDING REVIEW PROVISO:
 1-FLOOD ZONE A5: WILL NEED TO PROVIDE
 THE ELEVATION CERTIFICATE.
 2-TRUSS ANCHOR SCHEDULE ON SHEET S3:
 REVISE THE NUMBER OF FASTENERS FOR
 HETAL CONNECTORS. SEE SIMPSON LATEST
 CATALOGUE FOR CORRECT NUMBER OF NAILS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 3-EAST COAST TESTING ENGINEERING REPORT
 TO HAVE ORIGINAL SEAL, SIGNATURE AND
 DATE AS REQ'DBY CHAPTER 471 FLORIDA
 STATUTES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-09-20 Cont ID  
Sent By kstevens Date 2004-10-20 Time 15:19 Rev Time 3.00
Received By jgomez Date 2004-09-20 Time 15:54 Sent To E
Notes
2004-09-20 00:00:00CHECKLIST:
 1-PROVIDE COMPLETE ENGINEERING DESIGN
 PACKAGE AND SPECS FOR PILE SYSTEM TO
 BE USED AS REQUIRED BY SEC. 1805 FBC
 2001 AND AS NOTED ON SOIL TEST REPORT.
 2-PROVIDE DETAIL/SPECS SHOWING HOW ARE
 STEEL COLUMNS ATTACHED TO I BEAMS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 3-PROVIDE DETAIL/SPECS SHOWING HOW ARE
 WOOD TRUSSES ATTACHED TO I BEAM. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 4-PROVIDE UL LISTING AND COMPLETE SPECS
 FOR FIREPLACE. SEC. 2806 FBC 2001.
 5-SHEET S8: A)SPECIFY HOW LONG NEED TO
 BE THE WELDED STUDS. SEE UPPER LEFT
 DETAILS.
 B)SPECIFY HOW IS MASONRY WALL ATTACHED
 TO I BEAM. HOW IS REINFORCING #5 BAR
 WELDED TO I BEAM.
 C)EXTERIOR EDGE CONDITION DETAIL IS
 MISSING INFORMATION AT BOTTOM OF NOTE.
 D)SPECIFY HOW IS MASONRY WALL ATTACHED
 TO BEAM B-4. SEE DETAIL 8/S8.SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 E)PLANK ANCHORAGE DETAIL AT STEEL BEAM
 DETAIL DOESN'T APPLY. PROVIDE ONLY
 DETAILS THAT APPLY TO THIS PROJECT.
 6-OWES $641.36 FOR RE-SUBMITTAL FEES AND
 UPDATING VALUE TO REFLECT A/C AREA
 CHANGES. AND, ADDITIONAL RE-SUBMITTAL
 FEES WILL BE REQUIRED.
 7-PROVIDE COMPLETE ELEVATOR INFORMATION
 OR APPLY FOR SEPARATE PERMIT.
 8-NOTICE OF COMMENCEMENT NEEDS TO BE
 RECORDED AND IS VOID AFTER 90 DAYS.
 9-PROVIDE FLORIDA/LOCAL PRODUCT APPROVAL
 FOR STRUCTURAL CONNECTORS (SIMPSON OR
 USP AS SPECIFIED ON PLANS).
 10-PROVIDE UPLIFT CALCULATIONS FOR HIP
 GIRDER TRUSSES. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 B)TRUSSES WERE REVISED FROM METAL TO
 WOOD. REVISE CONNECTOR FASTENERS AS
 WELL. SEE SIMPSON LATEST CATALOGUE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-07-13 Cont ID  
Sent By csiegber Date 2004-08-24 Time 08:18 Rev Time 3.00
Received By jgomez Date 2004-07-12 Time 14:17 Sent To PC
Notes
2004-07-12 00:00:00BUILDING REVIEWCOMMENTS:
 1-PROVIDE COMPLETE INFORMATION FOR THE
 ELEVATOR OR APPLY FOR SEPARATE PERMIT.
 2-UPDATE NOTE #5 ON SHEET A1. SEE FBC
 2001 CHAPTER 13.
 3-CALCULATIONS FOR GARAGE BUCK DETAIL
 NEED TO BE SIGNED, SEALED BY THE
 ENGINEER/ARCHITECT. AND PROVIDE TITLE
 BLOCK WITH ALL INFORMATION REQUIRED
 BY CHAPTER 471/481 FLORIDA STATUTES.
 4-SHEET S-3 IS MISSING NOTE REGARDING
 ROOF SHEATHING INSTALLATION.
 5-PROVIDE COMPLETE SPECIFICATIONS AND
 DETAIL/SECTION AT THE ENDS OF I BEAM
 SHOWING ATTACHMENT TO THE STRUCTURE.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 6-PROVIDE COMPLETE SPECIFICATIONS AND
 DETAIL CONNECTIONS FOR 6" AND 8" H.C.
 CONCRETE PLANK FLOOR SYSTEM. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC.
 ARCHITECT TO REVIEW AND APPROVE
 COMPLETE PAKCAGE PRIOR TO SUBMITTAL.
 7-PROVIDE DETAIL/SECTIONS AND SPECS FOR
 RECESSED AREAS AT SHOWER AREAS IN H.C.
 CONCRETE PLANKS. SECTION 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 8-PROVIDE 2 COPIES OF COMPLETE FLORIDA
 OR LOCAL PRODUCT APPROVAL FOR:
 A)FRENCH DOOR WITH TRANSOM ABOVE SINGLE
 ASSEMBLY AND PUT TOGETHER AS SHOWN ON
 PLANS. SPECIFY ALL CONNECTIONS: DOOR
 TO MULLION & FIXED WINDOW TO MULLION.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 B)STRUCTURAL CONNECTORS.
 C)STRUCTURAL MULLIONS USED.
 D)GARAGE DOOR.
 E)ROOF TILE.
  
 9-DETAIL FOR ARCHED OPENINGS DOESN'T
 MATCH 2ND FLOOR STRUCTURAL PLAN. PLANS
 CALL FOR BOND BEAMS, NOT POURED BEAMS.
 ALSO, THERE ARE NO SPECS FOR SIZE AND
 SPACING OF STIRRUPS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 10-PROVIDE COMPLETE DETAIL SHOWING HOW
 IS LINTEL L-1 REINFORCED WITH 2#5'S
 AT BOTTOM OF PRECAST LINTEL?. IS IT A
 SOLID OR "U" TYPE LINTEL?. SECTION
 104.2.1.2 CITY AMENDMENS TO FBC.
 11-NEED THE NOTICE OF COMMENCEMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-06-03 Cont ID  
Sent By pkrauss Date 2004-07-08 Time 07:02 Rev Time 5.00
Received By jgomez Date 2004-06-02 Time 10:37 Sent To PC
Notes
2004-06-02 00:00:00BUILDING REVIEW CHECKLIST:
 1-NEED TO PAY IMPACT FEES TO PALM BEACH
 COUNTY. BRING BACK DWGS WITH COUNTY
 STAMP AND PAID RECEIPT.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-DESIGN CERTIFICATION FOR BUILDING CODE
 COMPLIANCE FORM IS TOO OLD. BESIDES,
 THIS FORM IS NOT REQUIRED. SEE SECTION
 1606.1.7 FBC 2001 FOR ALL 5 ITEMS TO
 BE INCLUDED IN DRAWINGS. REVISE SHEETS
 A1, S3 AND S7 TO INCLUDE ALL 5 ITEMS.
 4-NEED TO ADD THE ATTIC LIVE LOAD TO THE
 DESIGN CRITERIA AS REQUIRED BY TABLE
 1604.1 FBC 2001.
 5-PROVIDE 2 COPIES OF SOIL TEST REPORT
 WITH CORRECT ADDRESS & WITH ENGINEER'S
 ORIGINAL SEAL AND SIGNATURE AS REQ'D
 BY CHAPTER 471 FLORIDA STATUTES WHEN
 SUBMITTING INFORMATION FOR PUBLIC
 RECORDS.
 6-REVISE HEIGHT OF PRIVACY WALL TO MEET
 ZONING STANDARDS. REMEMBER THAT SEPA-
 RATE PERMIT IS REQUIRED FOR THIS WALL.
 7-SHEET A1: A)NOTE #5. DESIGNER NEEDS TO
 SPECIFY CONNECTORS. DO NOT CITE AS PER
 CODE. SEC. 104.2.1 CITY AMENDMENTS TO
 FBC 2001.
 B)UPDATE NOTE #5: SEE CHAPTER 13 OF FBC
 2001 FOR CORRECT CODE SECTION.
 8-PROVIDE COMPLETE INFORMATION FOR
 ELEVATOR AS REQ'D BY SECTION 3001.1.1
 FBC 2001 OR PROVIDE ALL INFORMATION
 UNDER A SEPARATE PERMIT.
 9-SHEET A2: A)PROVIDE ATTIC ACCESS AT
 GARAGE AREA. SEC. 2309.6 FBC 2001.
 B)A FLIGHT OF STAIRS SHALL NOT HAVE A
 VERTICAL RISE OF MORE THAN 12FT BET.
 FLOORS OR LANDINGS. SEC. 1007.4.1 FBC.
 REVISE STAIRS AS REQUIRED.
 C)SPECIFY HOW IS THE 5/8" CEMENT BOARD
 ATTACHED TO 2X4'S. SPECIFY FASTENER &
 SPACING. SEC 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
 D)PROVIDE SMOKE DETECTOR AT FIRST FLOOR
 BY THE STAIRWAY AS REQUIRED BY SECTION
 905.2.2 FBC 2001.
 10-SHEET A4: A)2ND FLOOR ROOF PROFILE
 DON'T MATCH 2ND FLOOR ROOF FRAMING
 PLAN ON SHEET S3. REVISE/CLARIFY.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC
 11-SHEET A5:A)PROVIDE MANUFACTURER SPECS
 FOR CEMENT BOARD.
 B)ROOF SHEATHING NOTE: REVISE FASTENER
 FOR ROOF ZONE 3. SEE TABLE 2306.1 CITY
 AMENDMENTS TO FBC.
 **ALSO, SEE FIGURE 1606.2(C) ON FBC 2001
 FOR LOCATION OF ZONE 3.
 C)SPECIFY SPECIFIC TILE STYLE USED TO
 PROPERLY CHECK PRODUCT APPROVAL.
 12-SHEET A7: A)PROVIDE SHOP DRAWINGS FOR
 BALCONIES GUARDRAILS.
 B)PROVIDE CALCS FOR GARAGE STRUCTURAL
 BUCK FASTENERS USED TO RESIST CALCULA-
 TED DESIGN PRESSURES. SEE PRODUCT
 APPROVAL FOR DOOR THAT MEET DESIGN
 PRESSURES CALCULATED AND CHECK RECO-
 MMENDATIONS FOR BUCK FASTENING. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 C)REVISE STAIR & ELEVATOR SECTION TO
 MATCH FOOTING SHOWN ON FOUNDATION PLAN
 AND SHOW ALL TIE BEAMS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 D)REVISE/CLARIFY SIZE OF ROOF TO MATCH
 SIZE SPECIFIED ON STRUCTURAL PLANS.
 13-ARCHITECT TO PROVIDE ALL INFORMATION
 AS REQUIRED BY CHAPTER 481 FLORIDA
 STATUTES WHEN SUBMITTING INFORMATION
 FOR PUBLIC RECORDS. SEE COPY OF SEC.
 61G1-16004 FOR TITLE BLOCK INFORMATION
 **ENGINEER TO PROVIDE ALL INFORMATION
 AS WELL AS REQUIRED BY CHAPTER 471 FL.
 STATUTES. SEE ATTACHED COPY OF SECTION
 61G15-23002 OF ADMINISTRATIVE CODE.
 EB #8613 IS NOT REGISTERED W/ FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS.
 14-SHEET S1: A)PROVIDE SECTION/DETAIL AT
 STEEL COLUMNS. SHOW TOP AND BOTTOM
 CONNECTORS AND EMBEDMENT OF CONCRETE
 PAD IN SOIL TO RESIST UPLIFT @ FRONT
 AND REAR PORCH COLUMNS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 B)CLARIFY FOOTING SCHEDULE: TABLE SAYS
 WF30 AND MEASURES 36". BUT FOUNDATION
 PLAN CALLS FOR WF36. REVISE AS REQ'D.
 C)SECTION DETAIL NUMBER AND SHEET KEYED
 ON PLANS TO MATCH NUMBER AND SHEET
 NUMBER SUBMITTED ON THIS SET.
 D)CLARIFY HOW ARE INTERIOR MASONRY WALLS
 REINFORCED. NOTE REGARDING #5 REINFOR-
 CEMENT APPLIES ONLY TO PERIMENTER
 WALLS. SEC. 104.2.1.2 CITY AMENDMENTS.
 15-SHEET S2:A)PROVIDE UPLIFT CALCS ON
 ROOF FRAMING PLAN. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 B)REVISE SPACING FOR ROOF SHEATHING
 FASTENER SPACING. SEE TABLE 2306.1 OF
 CITY AMENDMENTS TO FBC 2001 AND SEE
 FIGURE 1606.2(C) FBC 2001 FOR ZONE 3
 LOCATIONS.
 C)BEAM SCHEDULE: *BEAM B2 (ARCH BEAM)
 DOESN'T MATCH EXTERIOR ELEVATIONS.
 CLARIFY/REVISE AS REQUIRED.
 D)PROVIDE LINTEL SCHEDULE. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 **CLARIFY WHICH LINTELS ARE PRECAST AND
 WHICH ONES ARE PRESTRESED AS SPECIFIED
 ON NOTES AT BOTTOM OF BEAM SCHEDULE.
 E)CLARIFY HOW ARE TB-1 AND B1 INSTALLED
 BY THE DINING AREA IF THEY ARE AT
 DIFFERENT HEIGHTS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 F)WHAT ARE THE BOXES FOR SHOWN BY POWDER
 ROOM AND AT FAMILY BREAKFAST AREA?
 G)PROVIDE COMPLETE SPECS FOR I BEAM BY
 LAUNDRY AREA. SPECIFY CONNECTORS. ETC.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 **PLAN CALLS FOR TB-1? REVISE AS REQ'D.
 H)SPECIFY/SHOW TIE BEAMS AT ELEVATOR
 SHAFT AREA. SEC 104.2.1.2 CITY AMENDM.
 I)CLARIFY HOW ARE H.C. PRECAST PLANKS
 SUPPORTED ON CONCRETE BLOCK WALLS IF
 INTERIOR WALLS ARE LOWER THAN BOTTOM
 OF PLANKS. SEC. 104.2.1.2 CITY AMENDM.
 J)PROVIDE COMPLETE SHOP DRAWINGS, SPECS
 FOR H.C. CONCRETE PLANK FLOOR SYSTEM.
 SHOW ALL CONNECTIONS, ETC. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 16-SHEET S3: A)PROVIDE UPLIFT CALCS AND
 TRUSS ANCHOR SCHEDULE. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 B)ADD 30PSF OR 10PSF ATTIC LIVE LOAD AS
 REQUIRED BY TABLE 1604.1 FBC 2001.
 C)NOTE #5 CALLS FOR WIND LOAD TABLES ON
 SHEET S4. THERE ARE NONE. CLARIFY.
 D)MISSING ELEVATOR SHAFT. ALSO, SPECIFY
 TIE BEAM AT ELEVATOR SHAFT. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 E)ROOF LAYOUT DOESN'T MATCH EXTERIOR
 ELEVATIONS. REVISE AS REQUIRED.
 F)REVISE FASTENER TYPE & SPACING FOR
 SHEATHING AT END ZONES. SEE TABLE
 2306.1 CITY AMENDMENTS TO FBC 2001 AND
 FIGURE 1606.2(C)FBC 2001.
 17-A)SHEET S4: A)REVISE TRUSS CONNECTOR.
 SEE 2004 SIMPSON CATALOGUE FOR REVISED
 CONNECTOR LOADS AS REQUIRED BY SECTION
 1609.4.3 FBC 2001. PROVIDE COMPLETE
 ENGINEERING CALCS AND ANALYSIS FOR
 NUMBER AND TYPE OF FASTENER USED THAT
 ARE DIFFERENT FROM THOSE PUBLISHED ON
 SIMPSON CATALOGUE.
 B)SECTION 2/S4: CLARIFY HOW ARE 2-1/2"
 TROUGH BOLTS INSTALLED ON 8"H.C. PLANK
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC
 C)CLARIFY IF BRACING OF MASONRY WALL W/
 STEEL ANGLE APPLIES TO BRACING OF ALL
 INTERIOR WALLS. SPECIFY ON PLANS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 D)SPECIFY ON SECTION THE REQUIRED EMBED-
 MENT OF FOOTING INTO THE SOIL. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001
 18-SHEET S5: A)REVISE TRUSS CONNECTOR
 FASTENER TYPE AND NUMBER TO BE USED TO
 MATCH 2004 SIMPSON CATALOGUE. SECTION
 1609.4.3 FBC 2001.
 B)SPECIFY DEPTH OF FOOTING IN RELATION
 TO THE FINISH GRADE. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 C)SECTION 4/S5:*SPECIFY SIZE OF I BEAM.
 **SPECIFY BRACING FOR GARAGE WALL.
 19-SHEET S6: A)SECTION 5/S6: *REVISE
 FOOTING TO MATCH FOOTING SHOWN ON FOUN
 DATION PLAN.
 **SHOW/SPECIFY ALL TIE BEAMS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 B)REVISE TRUSS CONNECTOR TO MATCH 2004
 SIMPSON CATALOGUE. SEC. 1606.9.4.3 FBC
 20-SHEET S7: A)PROVIDE ONLY THE DETAILS
 THAT APPLY TO THIS PROJECT AND MAKE
 SURE DETAILS PROVIDE ALL INFORMATION
 SUCH AS SIZES, ETC. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 B)REVISE TRUSS CONNECTOR. SEE COMMENTS
 ABOVE.
 21-PROVIDE COMPLETE DRAWINGS AND SPECS
 FOR CONCRETE STAIRS. SECTION 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 22-PROVIDEPRODUCT APPROVAL FOR:
 A)FRENCH DOORS WITH TRANSOM ABOVE SINGLE
 ASSEMBLY AS SHOWN ON PLANS.
 B)ALL STRUCTURAL CONNECTORS.
 C)GARAGE DOORS THAT MEET THE DESIGN
 PRESSURES CALCULATED ON PLANS. NEED
 COMPLETE EVALUATION REPORT AND LEGIBLE
 DRAWINGS.
 D)CASEMENT WINDOWS. NEED WINDOWS THAT
 MEET THE DESIGN PRESSURES CALCULATED
 ON DRAWINGS.
 E)FIXED WINDOWS: NEED DADE COUNTY NOA
 REPORT AND DRAWINGS THAT MATCH NOA
 SPECIFIED ON FLORIDA PRODUCT APPROVAL
 COVER PAGE.
 F)MULLIONS: CLEARLY INDICATE ON DWGS
 SPECIFIC COMPONENTS TO BE USED:MULLION
 SIZE AND FASTENERS. ALSO, CHECK DESIGN
 PRESSURES SHOWN ON PLANS.
 G)ROOF TILE: NEED COMPLETE SBCCI REPORT
 AND DRAWINGS AND INDICATE SPECIFIC
 TILE STYLE AND FASTENING METHOD. CHECK
 PLANS FOR SPECIFICATIONS.
 23-ENERGY CALCULATIONS: A)MISSING INFO.
 FOR ADJACENT WALL.
 B)OWNER/AGENT TO SIGN AND DATE BOTTOM OF
 FORM.
 C)REVISE ORIENTATION OF OPENINGS TO
 MATCH ACTUAL HOUSE ORIENTATION.
 D)CLARIFY WHY THERE IS NOT OVERHANG
 LENGTH AND HEIGHT SPECIFIED.
 24-PROVIDE COMPLETE STRUCTURAL DETAILS
 FOR ARCHED OPENINGS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 25-PROVIDE COMPLETE STRUCTURAL DETAILS
 AND SPECS FOR SUSPENDED CEILING AT
 1ST FLOOR. SHOW HOW IS 5/8" DRYWALL
 SUPPORTED. SEC. 104.2.1.2 CITY AMENDM.
 26-OWES $1041.41 FOR UPDATED VALUATION
 AND RADON FEES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2007-03-27 Cont ID  
Sent By btrobaug Date 2007-03-27 Time 14:51 Rev Time 0.50
Received By btrobaug Date 2007-03-27 Time 13:36 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2005-12-19 Cont ID  
Sent By btrobaug Date 2005-12-19 Time 10:34 Rev Time 0.50
Received By btrobaug Date 2005-12-19 Time 06:42 Sent To B
Notes
2005-12-19 00:00:00 
 PLEASE REVISE THE LOAD CALCULATIONS TO
 INCLUDE THE RECESSED LIGHTING PER
 220.3(B)(4).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-03-24 Cont ID  
Sent By btrobaug Date 2005-03-24 Time 13:34 Rev Time 0.50
Received By btrobaug Date 2005-03-24 Time 13:06 Sent To Z
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-02-25 Cont ID  
Sent By btrobaug Date 2005-02-25 Time 10:38 Rev Time 1.00
Received By btrobaug Date 2005-02-25 Time 08:51 Sent To P
Notes
2005-02-25 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
  
 THESE ITEMS WERE REDLINED ON PREVIOUS
 PLANS AND NOT CORRECTED ON REVISIONS.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR IS
 NOT SUFFICIENT FOR THE SIZE OF THE
 SERVICE. THE SMALLEST ALLOWABLE FOR 400
 MCM FEEDERS IS #1/0CU PER 250.66. TWO
 CONDUCTORS CAN NOT BE SUBSTITUTED FOR
 THE SINGLE CONDUCTOR REQUIREMENT AS THEY
 CREATE PARALLEL GROUNDING PATHS.SEE
 250.6.
  
 2} SEE 250.50 FOR GROUNDING REQUIREMENTS
 INCLUDING FOOTER STEEL. LIST ALL
 AVAILABLE TO BE BONDED TOGETHER ON THE
 RISER DIAGRAM.
  
 3} THE RECEPTACLES ON THE PORTICO MUST
 BE GFI PER 210.8(A)(3). INDICATE SAME ON
 PLANS.
  
 THESE CORRECTIONS ARE DUE TO THE
 REVISION.
  
 1} SMOKE DETECTORS ARE REQUIRED AT THE
 STAIRS PER 905.2.2 FBC.
  
 2} SMOKE DETECTORS ARE REQUIRED INSIDE
 AND OUTSIDE BEDROOM #4 PER 8-1.4.1.6.2
 NFPA-72.
  
 3} THE VALUE OF THE PROJECT MUST BE
 INCREASED TO REFLECT ADDED SQUARE
 FOOTAGE. PLEASE NOTE SAME TO PERMIT
 SPECIALIST AT THE TIME OF RESUBMITTAL.
  
 PLEASE NOTE ALL KITCHEN COUNTERTOP
 RECEPTACLES MUST BE GFI PROTECTED PER
 210.8(A)(6). SEE COUNTERTOPS BETWEEN THE
 REFRIGERATOR'S.
  
 ALSO NOTE THE 250MCM CONDUCTORS FEEDING
 THE 200 AMP PANELS ARE OVERSIZED.
 ALTHOUGH NOT A VIOLATION IF THEY FIT
 UNDER THE LUGS, THEY MUST BE INSTALLED
 IF LEFT ON REVIEWED PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-09-21 Cont ID  
Sent By csiegber Date 2004-09-24 Time 09:41 Rev Time 0.75
Received By btrobaug Date 2004-09-21 Time 08:15 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-06-17 Cont ID  
Sent By jgomez Date 2004-09-20 Time 16:43 Rev Time 0.50
Received By btrobaug Date 2004-06-17 Time 14:19 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-11 Cont ID  
Sent By mjacobs Date 2004-06-16 Time 15:28 Rev Time 1.00
Received By btrobaug Date 2004-05-10 Time 17:18 Sent To M
Notes
2004-05-11 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT.
 PER 110.9/215.5
  
 2} THE GROUNDING ELECTRODE CONDUCTOR IS
 UNDERSIZED PER 250.66.
  
 3} THE GROUNDING ELECTRODE SYSTEM MUST
 BE INSTALLED PER 250.50, ALL ITEMS
 AVAILABLE MUST BE USED. PLEASE NOTE
 SAME ON PLANS.
  
 4} THE SERVICE CONDUCTORS @ 250 MCM ARE
 UNDERSIZED FOR THE 400 AMP OCP MAIN.
 SEE 310.15(B)(6).(400 MCM).
  
 5} PLEASE LIST ALL THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE PER 210.11C3.
  
 6} PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 7} THE FOLLOWING APPLIANCE CIRCUITS
 MUST BE CALCULATED AS INDICATED.
 A) LAUNDRY PER 210.16(B)-1500VA.
 B) DRYER PER 210.18-5000VA.
 C) SMALL APPLIANCE 220.16(A)-1500 EA.
  
 8} PLEASE PROVIDE A PANEL SCHEDULE SO
 THAT CODE COMPLIANCE OF CIRCUITING CAN
 BE DETERMINED.
  
 9} A SMOKE DETECTOR MUST BE ADDED AT THE
 STAIRWELL ON THE FIRST FLOOR TO COMPLY
 WITH 905.2.2 F.B.C..
  
 10} THE ELEVATOR EQUIPMENT IS NOT LISTED
 IN THE LOAD CALCULATION.
  
 11} THE DISPOSAL IS NOT LISTED IN THE
 CALCULATION.
  
 12} THE GARAGE RECEPTACLES MUST COMPLY
 WITH 210.8(A)(2).
  
 13} THE RECEPTACLES ON THE PORTICO MUST
 BE GFI PER 210.8(A)(3),GFI.
  
 14} ALL OF THE OUTDOOR EQUIPMENT
 DISCONNECTS MUST COMPLY WITH 110.26
 CLEARANCE.
  
 15} THE PHONE NUMBER OF THE ARCHITECT
 MUST BE CONTAINED IN THE TITLE BLOCK
 PER 61G1-16.004(2) FAC.
  
 THE AREAS OF NON COMPLIANCE ARE NOTED ON
 ONE SET OF REVIEWED PLANS TO AID THE
 ARCHITECT IN MAKING CORRECTIONS. IF
 THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2007-03-20 Cont ID  
Sent By adarroug Date 2007-03-20 Time 08:19 Rev Time 0.00
Received By adarroug Date 2007-03-20 Time 08:19 Sent To E
Notes
2007-03-20 08:20:30TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2006-03-21 Cont ID  
Sent By dpalmer Date 2006-03-21 Time 19:15 Rev Time 0.00
Received By dpalmer Date 2006-03-21 Time 19:15 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2005-12-12 Cont ID  
Sent By adarroug Date 2005-12-12 Time 17:48 Rev Time 0.00
Received By adarroug Date 2005-12-12 Time 17:48 Sent To Z
Notes
2005-12-12 00:00:00TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-03-29 Cont ID  
Sent By adarroug Date 2005-03-29 Time 13:13 Rev Time 0.00
Received By adarroug Date 2005-03-29 Time 13:13 Sent To P
Notes
2005-03-29 00:00:00TO "KSTEVENS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-03-28 Cont ID  
Sent By adarroug Date 2005-03-28 Time 14:08 Rev Time 0.00
Received By adarroug Date 2005-03-28 Time 14:08 Sent To E
Notes
2005-03-28 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-03-18 Cont ID  
Sent By adarroug Date 2005-03-18 Time 10:37 Rev Time 0.00
Received By adarroug Date 2005-03-18 Time 10:37 Sent To E
Notes
2005-03-18 00:00:00TO "BT" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-02-15 Cont ID  
Sent By adarroug Date 2005-02-15 Time 10:48 Rev Time 0.00
Received By adarroug Date 2005-02-15 Time 10:48 Sent To E
Notes
2005-02-15 00:00:00TO BTROBAUG DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-10-25 Cont ID  
Sent By csiegber Date 2004-10-25 Time 16:14 Rev Time 0.00
Received By csiegber Date 2004-10-25 Time 16:14 Sent To B
Notes
2004-10-25 00:00:00TO JG DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-10-12 Cont ID  
Sent By csiegber Date 2004-10-12 Time 11:52 Rev Time 0.00
Received By csiegber Date 2004-10-12 Time 11:52 Sent To P
Notes
2004-10-12 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-09-24 Cont ID  
Sent By csiegber Date 2004-09-24 Time 09:41 Rev Time 0.00
Received By csiegber Date 2004-09-24 Time 09:41 Sent To E
Notes
2004-09-24 00:00:00TO BT DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-08-24 Cont ID  
Sent By mmclean Date 2004-09-23 Time 16:52 Rev Time 0.00
Received By csiegber Date 2004-08-24 Time 08:18 Sent To B
Notes
2004-08-24 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-06-22 Cont ID  
Sent By mjacobs Date 2004-06-22 Time 15:08 Rev Time 0.00
Received By mjacobs Date 2004-06-22 Time 15:08 Sent To P
Notes
2004-06-22 00:00:00SENT TO KSDESK/SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-16 Cont ID  
Sent By mjacobs Date 2004-06-16 Time 15:28 Rev Time 0.00
Received By mjacobs Date 2004-06-16 Time 15:28 Sent To E
Notes
2004-06-16 00:00:00SENT TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-03 Cont ID  
Sent By mmclean Date 2004-05-04 Time 17:03 Rev Time 0.00
Received By jgomez Date 2004-04-30 Time 16:50 Sent To PC
Notes
2004-05-05 00:00:00TO SFD RACK/E
2004-04-30 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2006-10-19 Cont ID  
Sent By hmoser Date 2006-10-19 Time 09:29 Rev Time 0.00
Received By hmoser Date 2006-10-19 Time 09:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2006-03-22 Cont ID  
Sent By tgordon Date 2006-03-22 Time 11:37 Rev Time 1.15
Received By tgordon Date 2006-03-22 Time 11:37 Sent To  
Notes
2006-03-22 00:00:00*** DENIED ***
 1) AHU'S 1&2 SUPPLY AIR DUCTS (30"X5")
 APPEARS TO SMALL FOR A 4 TON AND A 3 TON
 SYSTEM. PLEASE SUBMIT A MANUAL J FOR ALL
 UNITS SHOWING CFM'S AND DUCT SIZES, PER
 2004 FBC/R M1401.3 .
  
 2) AHU #4 SUPPLY AIR DUCT TO THE MASTER
 SUITE IS 14" AND THE RETURN AIR DUCT IS
 12" TO ACHIEVE A BALANCE RETURN TI NEEDS
 TO BE 14" PLEASE CORRECT, PER 2004 FBC/R
 M1602.4 .
  
 3) ELECTRIAL PLANS ARE SHOWING A GAS
 WATER HEATER ON THE SECOND FLOOR
 DRESSING ROOM CLOSET. PLEASE PROVIDE
 COMBUSTION AIR AND COMBUSTION AIR
 CALCULATIONS ON MECHANICAL PLANS, OR IF
 THERE IS NO WATER HEATER HAVE ELECT.
 PLANS CORRECTED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-04-04 Cont ID  
Sent By prafter Date 2005-04-04 Time 08:46 Rev Time 0.30
Received By prafter Date 2005-04-04 Time 08:46 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-10-19 Cont ID  
Sent By pkrauss Date 2004-10-19 Time 16:26 Rev Time 0.30
Received By pkrauss Date 2004-10-19 Time 15:51 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2004-07-08 Cont ID  
Sent By pkrauss Date 2004-07-08 Time 07:01 Rev Time 0.25
Received By pkrauss Date 2004-07-08 Time 06:55 Sent To B
Notes
2004-07-08 00:00:00NO MECHANICAL PLANS RE-SUBMITTED FOR
 REVIEW WITH THE BUILDING PERMIT.
 ENERGY & MANUAL J CALCULATIONS ONLY.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-05-14 Cont ID  
Sent By jleech Date 2004-07-01 Time 18:45 Rev Time 0.40
Received By pkrauss Date 2004-05-14 Time 11:42 Sent To P
Notes
2004-05-14 00:00:00DENIED:
 REFERENCE REVISED 2001 FBC(M) 601.4;
 RETURN AIR SHALL BE EQUAL TO SUPPLY AIR
 INTO ROOMS SEPARATED BY DOORS.PLEASE
 INCREASE RETURN AIR SIZE TO COMPLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 7 Status P Date 2005-04-02 Cont ID  
Sent By kstevens Date 2005-04-02 Time 07:10 Rev Time 0.75
Received By kstevens Date 2005-04-02 Time 07:10 Sent To M
Notes
2005-04-02 00:00:00REVISION OK - CHANGED LAYOUT OF BATHROOM
 BY LAUNDRY ROOM ADDING A TUB ALSO. ADDED
 BATHROOM ON SECOND FLOOR OVER GARAGE.

Review Stop P PLUMBING
Rev No 6 Status F Date 2005-03-07 Cont ID  
Sent By jleech Date 2005-03-07 Time 17:07 Rev Time 0.75
Received By jleech Date 2005-03-07 Time 16:54 Sent To B
Notes
2005-03-07 00:00:00DEN IED;
 1.SECOND FLOOR WASTE STACK MUST BE DOWN
 STREAM OF CABANA BATH DRAINAGE PIPING.
 SEC. 909.1.
 2.ALL PIPE UNDER SLAB MUST BE A MIN. OF
 2" SEE RISER DIAGRAM MARKED IN RED PAGE
 P-2.
 3.RISER DIAGRAM AND FLAT DRAWING FOR
 BEDROOM BATH 4. DRY VENT FOR TUB NOT
 NEEDED AND NOT TO CODE MARKED IN RED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 5 Status F Date 2005-03-01 Cont ID  
Sent By kstevens Date 2005-03-01 Time 18:35 Rev Time 0.50
Received By kstevens Date 2005-03-01 Time 18:35 Sent To B1
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-10-20 Cont ID  
Sent By kstevens Date 2004-10-20 Time 15:19 Rev Time 0.33
Received By kstevens Date 2004-10-20 Time 15:19 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-09-21 Cont ID  
Sent By csiegber Date 2004-10-12 Time 11:52 Rev Time 0.50
Received By kstevens Date 2004-09-21 Time 17:44 Sent To Z
Notes
2004-09-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT P2 THE SANITARY RISER DIAGRAM
 DOES NOT MEET CODE.
 A) CLEANOUTS ARE REQUIRED WHEN EVER THE
 BLDG DRAIN EXITS THE BLDG AND TIES INTO
 THE BLDG SEWER. 708.3.5
 B) WASH MACHINE REQUIRES A TRAP, STAND-
 PIPE AND CLEANOUT 4' ABOVE THE FLOOR.
 SECTIONS 1002.1, 802.4, & 708.10.
 C) INDICATE SIZE OF FLOOR DRAIN AND THE
 PIPING TO IT. SECTION 104.2.1
 D) MINIMUM SIZE TRAP FOR THE WASH MACH-
 INE IS 2" TABLE 709.1. RISER SHOWS 1-1/2
 INCH SANT. TO WASH MACHINE.
 E) LAV IN POWDER ROOM REQUIRES A VENT
 SECTION 901.2.1
 F) AIR ADMITENCE VALVES SHALL BE ABOVE
 THE TRAPS AT THE KITCHEN SINKS. SECTION
 917.4
 G) ALL TUBS, SHOWERS AND THE BIDET RE-
 QUIRE A TRAP. SECTION 1002.1
 H) CLEANOUT SHALL BE LOCATED BETWEEN
 THE FIRST AND SECOND FIXTURE BRANCHES
 OF THE BUILDING DRAIN ON THE RISER DIA-
 GRAM TO CORRELATE WITH THE FLAT DRAWING.
 SECTION 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-07-01 Cont ID  
Sent By btrobaug Date 2004-09-21 Time 08:52 Rev Time 0.50
Received By jleech Date 2004-07-01 Time 18:45 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-05-19 Cont ID  
Sent By mjacobs Date 2004-06-22 Time 15:25 Rev Time 0.25
Received By kstevens Date 2004-05-19 Time 13:50 Sent To B
Notes
2004-05-19 00:00:00NO PLUMBING PLANS SUBMITTED. - PLUMBING
 PERMIT REQUIRED.
 SEPARATE GAS PLANS/PERMIT REQUIRED

Review Stop Z ZONING
Rev No 4 Status P Date 2005-03-25 Cont ID  
Sent By mmclean Date 2005-03-25 Time 16:17 Rev Time 0.00
Received By mmclean Date 2005-03-25 Time 16:17 Sent To I
Notes
2005-03-25 00:00:00APPROVING 2ND STORY STRUCTURE ABOVE
 GARAGE.

Review Stop Z ZONING
Rev No 3 Status F Date 2005-03-15 Cont ID  
Sent By mmclean Date 2005-03-15 Time 11:40 Rev Time 0.00
Received By mmclean Date 2005-03-15 Time 11:40 Sent To  
Notes
2005-03-15 00:00:00DENIED,
 1. MUST REMOVE MICROWAVE MUST BE REMOVED
 FROM BOTH PLANS AND THE REFRIDGERATOR
 MUST INDICATE AN U/C REFRIDGERATOR.
 CALLED CORY FOR P/U MM

Review Stop Z ZONING
Rev No 2 Status P Date 2004-09-23 Cont ID  
Sent By mmclean Date 2004-09-23 Time 16:52 Rev Time 0.00
Received By mmclean Date 2004-09-23 Time 16:52 Sent To I
Notes
2004-09-23 00:00:00RESTAMP PLANS MM

Review Stop Z ZONING
Rev No 1 Status P Date 2004-05-04 Cont ID  
Sent By kstevens Date 2004-09-21 Time 17:45 Rev Time 0.00
Received By mmclean Date 2004-05-04 Time 17:03 Sent To B
Notes
2004-05-04 00:00:00NOTE: MUST PULL SEPARATE PERMIT FOR POOL
 MUST PULL SEPARATE PERMIT FOR WALL &
 PROVIDE UTILITY EASEMENT APPROVAL.CAN
 ONLY BE 4FT IN THE FIRST 25FT FRONT SET
 BACK.