Plan Review Details - Permit 04042022
Plan Review Stops For Permit 04042022
Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status P Date 2007-04-03 Cont ID  
Sent By jwitmer Date 2007-04-03 Time 11:36 Rev Time 1.11
Received By jwitmer Date 2007-04-03 Time 11:36 Sent To PC
Notes
2007-04-03 11:38:01REVISIONWINDOW AND GLASS PRODUCT APPROVALS & SHOP
 DRAWINGS YKK AP AMERICA

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status P Date 2007-03-16 Cont ID  
Sent By jwitmer Date 2007-03-16 Time 11:04 Rev Time 0.00
Received By jwitmer Date 2007-03-16 Time 11:01 Sent To  
Notes
2007-03-16 11:05:17CLARIFICATION OF 2 HR SHAFT WALL

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status F Date 2007-03-01 Cont ID  
Sent By jwitmer Date 2007-03-01 Time 16:11 Rev Time 2.20
Received By jwitmer Date 2007-03-01 Time 16:11 Sent To PC
Notes
2007-03-01 16:16:52BUILDING PLAN REVIEW
 PERMIT: 04042022
 ADD: 444 W RAILROAD AV
 CONT: PBM DEVELOPMENT
 TEL: (954)275-1947
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 PRODUCT APPROVALREVIEW
 ACTION: DENIED
  
 1) THRESHOLD BUILDING REQUIRES THREE SETS OF ALL
 SUBMITTALS NOT TWO SETS.
  
 2) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ALL OF THE YKK AP REPORTS DO HAVE FLORIDA APPROVALS
 PLEASE PROVIDE THE ASSOCIATED COVERSHEETS.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2007-03-01 Cont ID  
Sent By jwitmer Date 2007-03-01 Time 16:10 Rev Time 0.77
Received By jwitmer Date 2007-03-01 Time 16:10 Sent To PC
Notes
2007-03-01 16:11:38STAIRRAIL HANDRAILS AND CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status F Date 2007-01-05 Cont ID  
Sent By jwitmer Date 2007-01-05 Time 07:33 Rev Time 3.33
Received By jwitmer Date 2007-01-05 Time 07:33 Sent To  
Notes
2007-01-05 08:44:09BUILDING PLAN REVIEW
 PERMIT: 04042022
 ADD: 444 W RAILROAD AVE
 CONT: PBM DEVELOPMENT
 TEL: (954)868-5944
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISIONREVIEW
 ACTION: DENIED
  
 1) PBM DEVELOPMENT IS ACTING AS A ARCHITECTURAL FIRM,
 EITHER PBM DEVELOPMENT NEEDS TO AQUIRE A CERTIFICATE
 OF AUTHORIZATION OR REMOVE THEIR NAME FROM THE
 TITLEBLOCK
 AND USE THE LICENSED ARCHITECT DOMINICK SCARFO INTHE
 TITLE
 BLOCK AS AN INDIVDUAL.
  
 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 2) THE SECOND ISSUE WITH THIS SERIES OF REVISIONS IS :
 A.31.03 THE THIRD FLOOR CORRIDOR, A.31.04 FOURTH FLOOR,
 THE NEW CORRIDOR
 WALLS ANDDOORS DO NOT INDICATE ANY RATINGS. THE
 NARRATIVE AND THE ARCHITECTURAL NOTES ON SHEET A.00.00
 HAVE A PHRASE " CORRIDOR RATED" DRYWALL PARTITIONS.
 THERE IS A DIFFERENCE IN CORRIDOR RATINGS UNDER THE
 2001FBC AND 2004 FBC. THE ISSUED PERMIT SET OF PLANS
 UNDER THE 2001 FBC INDICATE WALL TAG (102)HR FIRE
 RATED CORRIDORS AND
 20 MINUTE DOORS. THE DOORSIN THE NEWLY ADDED
 CORRIDORS DO NOT HAVE ANY
 IDENTIFICATION MARKERS EITHER.
  
 PLEASE PROVIDE WALL AND DOOR MARKER INDICATING THEIR
 FIRE RATINGS.
  
 3) A.41.03 REVISION# 7 THERE IS NO CEILING HEIGHT
 INDICATORS
 ALTHOUGH NOTE# 4AS NOTED.ADDITIONAL INFORMATION
 REQUIRED. 106.1.2.
  
 4A) A.41.04 REVISION# 1 NEW CEILING DESIGN IN LOBBY, NO
  
 INFORMATION AS TO HEIGHT OR TYPE OF MATERIALS TO BE
 USED.
 ADDITIONAL INFORMATION REQUIRED. 106.1.2.
  
 4B) A.41.04 REVISION# 2THERE IS NO CEILING HEIGHT
 INDICATORS
 ALTHOUGH NOTE# 4AS NOTED.ADDITIONAL INFORMATION
 REQUIRED. 106.1.2.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2006-08-24 Cont ID  
Sent By jwitmer Date 2006-08-24 Time 08:18 Rev Time 0.55
Received By jwitmer Date 2006-08-24 Time 08:18 Sent To M
Notes
2006-08-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04042022
 ADD: 444 W. RAILROAD AVE
 CONT: PBM DEVELOPMENT
 TEL: (561)368-2544
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: REVISION
 ACTION: DENIED
  
 1) JONES STRUCTURAL ENGINEERS, PLLC
 IS MISSING THEIR CERTIFICATE OF
 AUTHORAZATION.
 471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ENGINEERING SERVICES, SHALL INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 2)MISSING THE PRINTED NAME OF THE
 ENGINEER RESPONSIBLE FOR THE DESIGN,
 61G15-23.002(2)FL. ADMIN. CODE. PLANS
 SIGNED & SEALED BY A PROFESSIONAL
 ENGINEER SHALL INCLUDE EITHER THE NAME,
 ADDRESS AND LICENSE NUMBER OF THE
 ENGINEER OR, THE NAME AND LICENSE NUMBER
 OF THE ENGINEER AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH
 WHICH THE ENGINEER IS PRACTICING
 (471.025 F.S. AND 471.023 F.S.).
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2006-04-05 Cont ID  
Sent By jwitmer Date 2006-04-05 Time 15:10 Rev Time 0.55
Received By jwitmer Date 2006-04-05 Time 15:10 Sent To PC
Notes
2006-04-05 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04042022
 ADD: 444 W RAILROAD AVE
 CONT: PBM DEVELOPMENT
 TEL: (954)444-3021
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTAL REVIEW:
 ACTION: DENIED
  
 ALL SUBMITTALS ARE TO BE REVIEWED BY THE
 DESIGN PROFESSIONAL, PROVIDE WRITTEN
 APPROVAL OR APPROVED AS NOTEDTO THE
 BUIULDING DEPARTMENT.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2006-04-05 Cont ID  
Sent By jwitmer Date 2006-04-05 Time 15:09 Rev Time 2.22
Received By jwitmer Date 2006-04-05 Time 15:09 Sent To  
Notes
2006-04-05 00:00:00REVISIONS AS STAMPED:

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2006-02-22 Cont ID  
Sent By jwitmer Date 2006-02-22 Time 16:35 Rev Time 2.22
Received By jwitmer Date 2006-02-22 Time 16:35 Sent To PC
Notes
2006-02-22 00:00:00STRUCTURAL REVISIONS 1-4

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2006-01-12 Cont ID  
Sent By jwitmer Date 2006-01-12 Time 11:04 Rev Time 5.00
Received By jwitmer Date 2006-01-12 Time 07:19 Sent To PC
Notes
2006-01-12 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04042022
 ADD: 444 W. RAILROAD AVE.
 CONT:PBM DEVELOPMENT
 TEL: (786)877-6011
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISIONS ARCH/ MEP 10-12-05
  
 PLEASE SEND A TRANSMITTAL LETTER
 IDENTYING THE REVISIONS MADE TO THE
 PLANS.
  
  
 1) A31.01 REVISION MADE NO DELTA OR
 CLOUD INDICATING CHANGE MISSING WALL AND
 DOOR IN RESTROOMA RESTROOM CAN NOT
 OPEN INTO A FOOD PREPERATION AREA.
  
 2) A31.02 THE PERMITED SET OF DRAWINGS
 REQUIRED RED LINED CORRECTIONS BY THE
 ARCHITECT TO ACHIEVE A PERMIT. THIS
 REVISION DETAILS ST-A2/ A32.01 PLEASE
 PROVIDE THIS SHEET IN THE REVISION
 PACKAGE INDICATING CHANGE.
  
 3) A31.03 NEW ELEVATOR LOBBY IS MISSING
 THE IDENTIFICATION NUMBER AND RATING
 PAIR OF DOORS TO LOBBY.104.2.1*
  
 4) A31.04 REVISION MADE NO DELTA OR
 CLOUD INDICATING CHANGE. 1020.1
 SOUTHWEST OFFICE IS MISSING A DOOR TO
 CORRIDOR, OVER 75' TRAVEL DISTANCE FOR
 SINGLE MEANS OF EGRESS. 1020.1
  
 A31.06 :
 A) DOOR # 613 PROVIDE DOOR INFORMATION ,
 DOES THIS DOOR PROVIDE EGRESS TO ROOF,
 WILL IT BE RESTRICTIVE?NO DOOR SCHEDULE
  
 B) DOOR # 614 THERE IS NO RROM
 DESIGNATION?
  
 A31.07
 A) THE HANDICAPPED SPACE ACROSS FROM THE
 TICKET BOOTH IS MISSING THE DESIGNATION
 FOR THE ACCESS AISLE.
  
 B) IT APPEARS THAT THE SAID ACCESS AISLE
 HAS A COLUMN IN THE SPACE.
  
 C)JUST LEFT OF THE TICKET SPACE THE
 FLOOR ELEVATION INDICATES A 19.8 VERSES
 18.8 IS THIS A MISTAKE?
  
 5) THERE WERE NO STRUCTURAL PLANS
 PROVIDED FOR THE ADDITIONAL FLOOR ADDED
 TO THE PARKING GARAGE? PROVIDE
 ADDITIONAL INFORMATION FOR THE
 ADDITIONAL LIVE AND DEAD LOADING?
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-07-02 Cont ID  
Sent By jwitmer Date 2005-07-02 Time 11:54 Rev Time 3.55
Received By jwitmer Date 2005-07-02 Time 08:41 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-05-27 Cont ID  
Sent By jwitmer Date 2005-05-27 Time 16:11 Rev Time 8.00
Received By jwitmer Date 2005-05-27 Time 13:12 Sent To  
Notes
2005-05-27 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04042022
 ADD: 444 W. RAILROAD AVE.
 CONT:PBM DEVELOPMENT
 TEL: (786)877-6011
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)NEW COMMENT: PLANS INDICATE THAT THE
 LOBBY AREA COMMUNICATES WITH THE SECOND
 FLOOR BALCONY AND HALLWAY. THIS
 CONSTITUTES ANATRIUM. PLEASE PROVIDE
 CODE COMPLIANCE WITH SECTION:
 414.4 SMOKE CONTROL
 414.5 ENCLOSURES OF ATRIUMS
  
 3) SOILS REPORTS, THE SOILS REPORT OF
 JUNE 23/03, AND ADENDUMS DATED, JAN.
 30/04, MARCH 10/04 & APRIL 13/05 ALL
 HAVE RAISED SEALS BUT THE SIGNATURES ARE
 ALL COPIES!!!!!!!!!!!!!!!!!!!!
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 4) THE STATE APPROVED PLANS FOR THE
 TICKET BOOTH PROVIDE DETAILS INDICATING
 THAT THE BOTH MEETS FLORIDA
 ACCESSIBILITY BUT SHEET A83.01 INDICATES
 THE USE OF RAISED CURB, PLEASE INDICATE
 VERTICAL ACCESSIBILITY, 11-4.1.2.PROVIDE
 DETAILS WHERE THE FINISHED FLOOR WILL BE
 LESS THAN 1/2" ABOVE THE GARAGE FLOOR
 DECK.
  
 5)NEWLY ADDED PAGE A55.01 DOOR SCHEDULE:
 A) DOOR 101A MISSING FIRE RATING
 B) DOOR 108 IS MISSING FIRE RATING
 C) DOOR 2AB IS NOT ON DOOR SCHEDULE
 D) WINDOW W01 DOES NOT INDICATE ANY
 RATING IN THE WINDOW SCHEDULE
 E) NOR DOES THE WINDOW SCHEDULE PROVIDE
 PRESSURES.
  
 6) NEW COMMENT: SHEET A.11.01 DETAIL OF
 STAIR A-1 FLOOR 2, THE LANDING BEFORE
 THE STAIR TOWER, IS THIS ENCLOSED ? OR
 OPEN TO THE EXTERIOR? NO DOOR SEPERATING
  
 THE CORRIDOR, NOR IS THERE A DESIGNATION
 FOR A GUARDRAIL?
  
 7)NEW COMMENT NEWLY ADDED PAGE SHEET
 A62.01 LOBBY GAURDRAIL, PROVIDE A CLEAR
 DETAIL, 1015.2 HEIGHT. GUARDRAILS SHALL
 FORM A VERTICAL PROTECTIVE BARRIER NOT
 LESS THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
  
 8) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
  
 A) WINDOWS/ DOORS, THE TRAINER GLASS
 CURTAINWALL SYSTEM SUBMITTED DOES NOT
 HAVE THE MIAMI-DADE REPORT SUBMITTED TO
 THE STATE. THIS REPORT SPECIFIES THAT IT
 IS A ONE TIME APPROVAL FOR INSTALLATION
 OF CURTAIN WALL AT AVENTURA HOSPITAL,
 AVENTURA, FL.
 B) T. M. WINDOWS & DOORS- SLIDING DOORS,
  
 THE REPORT SUBMITTED DOES NOT INCLUDE
 THE TRANSOM ABOVE AS SHOWN IN THE
 ELEVATION VIEW.
 C)PROVIDE BOTH VERTICAL AND HORIZONTAL
 MULLIONS FOR THE CORRECT SPANS AND
 PRESSURES.
 D)FL #539 JELD-WEN REPORT SUBMITTED IS
 FOR THE 2004 CODE NOT 2001. SECOND THE
 MIAMI REPORT SUBMITTED IS NOT LISTED ON
 THE FL REPORT.
 E) WALL LOVER FL REPORT# 3281 DOES NOT
 HAVE THE CORRESPONDING MIAMI-DADE
 REPORT, WAS NOT SUBMITTED.
 F) ROOFING, FOAM ENTERPRISES IS ONLY
 LISTED ON THE FL STATE WEB SITE NO
 PRODUCTS TO DATE ARE APPROVED OR APPLIED
 FOR.
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-03-18 Cont ID  
Sent By jwitmer Date 2005-03-18 Time 12:36 Rev Time 7.77
Received By jwitmer Date 2005-03-18 Time 12:36 Sent To  
Notes
2005-03-18 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04042022
 ADD: 477 3RD ST/ 444 W RAILROAD AVE
 CONT: PLAN REVIEW
 CONTACT: WEST RAILROAD LIMITED
 PROJECT SUPERVISOR: PATTI LUDLOW
 TEL: (561)368-2544 EXT. 22
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 3RD PLAN REVIEW
 ACTION: DENIED
  
 NOTE: WHEN APPLYING FOR A PERMIT, (3)
 SETS OF PLANS, AND SUPPORTING DOCUMENTS
 SHALL BE REQUIRED, SIGNED & SEALED IF
 PRODUCED BY A DESIGN PROFESIONAL.
  
 NOTE: PLEASE PROVIDE A RESPONSE SHEET
 INDICATING WHERE THE CORECTION CAN BE
 FOUND, THIS WILL GREATLY HELP THE TURN
 AROUND TIME OF YOUR PLAN REVIEW.
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 3)W.P.B. AMENDMENT 105.13.4.4 ALL
 PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CON-
 TAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 4)WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 5) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
 WHEN SUBMITTING FOR PERMIT (3) SETS OF
 SEALED SURVEYS WILL BE REQUIRED.
  
 6) PARKING GARAGE TO BE CONSIDERED A
 OPEN PARKING GARAGE, THE AMOUNT OF
 OPENINGS SHALL MEET THE REQUIREMENTS OF
 411.3.2(2) WITH THE EXCEPTION OF THE
 FOURTH FLOOR. WITH NO WINDOWS INDICATED
 ON THE NORTH WALL OF THE FOURTH FLOOR
 THE THE AMOUNT OF OPENINGS FOR THE FORTH
 FLOOR IS 19.4% NOT THE REQUIRED 20%.
  
 7) 705.7.1 JOINTS INSTALLED IN OR BE-
 TWEEN FIRE RESISTANT WALLS, FIRE RESIS-
 TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES
 AND FIRE RESISTANT ROOFS OR ROOF/ CEIL-
 ING ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE
 FOR A PERIOD NOT LESS THAN THE RE-
 QUIRED FIRE RESISTANCE RATING OF THE
 WALL, FLOOR OR FLOOR IN OR BETWEEN
 WHICH IT IS INSTALLED.
  
 8) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 9)THE TICKET BOOTH MANUFACTURED BY
 MARDAN FABRICATORS VISTA SERIES- HANDI-
 CAPPED ACCESSIBLE BOOTH WILL REQUIRE
 PLAN SUBMITTAL WITH STATE APPROVAL FROM
 DCA PREMANUFACTURED BUILDINGS.
  
 10) PLANS APPEAR TO BE MISSING SHEETS:
 A52.01
 A55.01
 A61.01
 A62.01
 PLEASE PLACE THESE PAGES IN THE ORDER
 THEY SHOULD READ, NOT AT THE BACK OF THE
 PLANS!!!!!!
  
 11) REVISIT THE DOOR RATINGS FOR:
 A) DOORS BETWEEN THE GARAGE AND OFFICE
 CORRIDOR ( 1 1/2 HR) TABLE 704.1
 B) REFUSE CHUTE ACCESS DOORS (1
 HR)705.1.2
 C) STAIRWELL SHAFT DOORS > 4 STORIES
 (1 1/2 HR) TABLE 705.1.2
  
 12)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) EXTERIOR DOORS
 C) LOUVER
 D) SKYLIGHTS
 E) TRUSS ANCHORS
 F) ROOF ASEMBLIES
 G) RAILINGS
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 13) 2ND REQUEST FOR INFORMATION, TABLE
 600 TYPE II BUILDING, FIRE PROTECTION
 RATING FOR COLUMNS, BEAMS, GIRDERS,
 FLOORS & FLOOR/CEILING ASSEMBLIES AND
 ROOFS OR ROOF/CEILING ASSEMBLIES.
 RESPONCE IS "SEE STRUCTURAL COMMENTS",
 WHERE?
  
 14)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-09-20 Cont ID  
Sent By jwitmer Date 2004-09-20 Time 15:36 Rev Time 6.66
Received By jwitmer Date 2004-09-20 Time 13:02 Sent To  
Notes
2004-09-20 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04042022
 ADD: 477 3RD ST/ 444 W RAILROAD AVE
 CONT: PLAN REVIEW
 CONTACT: WEST RAILROAD LIMITED
 PROJECT SUPERVISOR: PATTI LUDLOW
 TEL: (561)368-2544 EXT. 22
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND PLAN REVIEW
 ACTION: DENIED
  
 NOTE: WHEN APPLYING FOR A PERMIT, (3)
 SETS OF PLANS, AND SUPPORTING DOCUMENTS
 SHALL BE REQUIRED, SIGNED & SEALED IF
 PRODUCED BY A DESIGN PROFESIONAL.
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 3)W.P.B. AMENDMENT 105.13.4.4 ALL
 PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CON-
 TAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 4)WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 5) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
 WHEN SUBMITTING FOR PERMIT (3) SETS OF
 SEALED SURVEYS WILL BE REQUIRED.
  
 6) STRUCTURAL PLANS ARE NOT SEALED. WHEN
 APPLYING FOR PERMIT (3) SIGNED AND SEAL-
 ED SETS OF PLANS WILL BE REQUIRED.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 7) TABLE 600 ISSUES, NO OPENINGS ARE
 ALLOWED 0'-3' FROM THE PROPERTY LINE.
 >3'-10' ALLOWABLE OPENINGS 10%. SEE
 705.1.1.2 WHEN OPENINGS ARE WITHIN 15'
 OF THE PROPERTY LINE OPENING PROTECTIVES
 ARE REQUIRED. THIS WILL CREATE A
 ENCLOSED GARAGE, SEE 411.4. INDICATE
 COMPLANCE WITH EXTERIOR WALLS 0'-3' RE-
 QUIRING 3 HRS, & 2HR EXTERIOR WALLS FOR
 >3'-10". PROVIDE BLOCK INFO FROM BLOCK
 MANUFACTURER, IN EQUIVANT THICKNESS,
 SEE 709.3.1.
  
 8) SHEET A.73.02 INDICATES THE USE OF
 RATED WALLS BUT NO UL LISTING, PROVIDE
 FLOOR PLANS INDICATING WALL FIRE RATING,
 INDICATE BY USE OF DASHED LINES INDICAT-
 ING ONE OR TWO HR ASSEMBLIES, SEE FIRE
 REVIEW.
  
 9)705.7.1 JOINTS INSTALLED IN OR BE-
 TWEEN FIRE RESISTANT WALLS, FIRE RESIS-
 TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES
 AND FIRE RESISTANT ROOFS OR ROOF/ CEIL-
 ING ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE
 FOR A PERIOD NOT LESS THAN THE RE-
 QUIRED FIRE RESISTANCE RATING OF THE
 WALL, FLOOR OR FLOOR IN OR BETWEEN
 WHICH IT IS INSTALLED.
  
 10) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 11)AS INDICATED FROM PREVIOUS REVIEW,
 SKYBRIDGE TO BE UNDER A SEPERATE PERMIT,
 THE DELETION CREATES A DEAD END CORRIDOR
 PLEASE INDICATE COMPLIANCE? TABLE 1004,
 20', SEE FOOTNOTE (20) ALLOWING DEAD END
 CORRIDOR TO 50'.
  
 12)THE TICKET BOOTH MANUFACTURED BY
 MARDAN FABRICATORS VISTA SERIES- HANDI-
 CAPPED ACCESSIBLE BOOTH WILL REQUIRE
 PLAN SUBMITTAL WITH STATE APPROVAL FROM
 DCA PREMANUFACTURED BUILDINGS.
  
 13) SHEET A32.01 STAIR A-2 SHALL COMPLY
 WITH 1012.1.4 DURING ITS SWING, ANY DOOR
 IN A MEANS OF EGRESS SHALL LEAVE UNOB-
 STRUCTED AT LEAST ONE-HALF OF THE RE-
 QUIRED WIDTH OF THE LANDING.
  
 14) SRUCTURAL PLANS DO NOT INDICATE THAT
 THE WIND DESIGN IS FROM ASCE 7-98 CHAP-
 TER 6, BUILDINGS OVER 60'-0".
 CORRECT WIND DESIGN:
 IMPORTANCE FACTOR I/ CATEGORY II
 WIND EXPOSURE "B"
 ENCLOSED BUILDING.18
  
 15)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) EXTERIOR DOORS
 C) LOUVER
 D) SKYLIGHTS
 E) TRUSS ANCHORS
 F) ROOF ASEMBLIES
 G) RAILINGS
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 16) SHEET S3.1 DETAIL #6 INTRIOR BLOCK
 WALL, DETAIL 6/ S7.1 INDICATES SEE PLAN
 FOR ADDITIONAL SLAB REINFORING, WHERE?
  
 17) 2ND REQUEST FOR INFORMATION, TABLE
 600 TYPE II BUILDING, FIRE PROTECTION
 RATING FOR COLUMNS, BEAMS, GIRDERS,
 FLOORS & FLOOR/CEILING ASSEMBLIES AND
 ROOFS OR ROOF/CEILING ASSEMBLIES.
 RESPONCE IS "SEE STRUCTURAL COMMENTS",
 WHERE?
  
 18) PROVIDE POSITIVE AND NEGITIVE PRES-
 SURES FOR ALL WINDOWS AND DOORS, INTER-
 IOR AND END ZONES AS WELL.
  
 19)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-05-28 Cont ID  
Sent By jwitmer Date 2004-05-28 Time 15:34 Rev Time 9.75
Received By mamini Date 2004-05-28 Time 15:34 Sent To  
Notes
2004-05-28 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04042022
 ADD: 477 3RD ST.
 CONT: PLAN REVIEW
 CONTACT WEST RAILROAD LIMITED
 PROJECT SUPERVISOR: PATTI LUDLOW
 TEL: (561)368-2544 EXT.22
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PROVIDE 2 CURRENT COPIES OF SIGNED &
 SEALED SURVEYS WITH PROPOSED IMPROVEMENT
 TO BE COMPLETED.
  
 3)FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
 A THRESHOLD INSPECTOR SHALL ALSO BE
 REQUIRED TO BE SIGNED ON SEE HAROLD
 PISKURA (561)805-6711.
 (3) SETS OF ALL DOCUMENTS ARE
 REQUIRED FOR THRESHOLD BUILDINGS.
  
 4) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL I
 S NOT DEFINITEY KNOWN, OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL P
 ROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 5) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 6) FIRE SPRINKLERS 903.8.1 BUILDINGS
 3 STORIES OR MORE IN HEIGHT SHALL
 REQUIRE FIRE SPRINKLER PLANS BEFORE THE
 ISSUANCE OF A BUILDING PERMIT.THEY ARE
 TO BE PART OF THE BUILDING SET OF PLANS.
 SEPERATE PLANS WILL BE REQUIRED FOR THE
 FIRE APRINKLER PERMIT.
  
 7) PLANS DO NOT INDICATE WHAT BUILDING
 TYPE? FOR THIS REVIEW IT WILL BE CONSID-
 ERED A TYPE II BUILDING. BUILDING IS
 70' TALL.
  
 8) PLANS ARE NOT CLEAR AS TO WHERE THE
 PROPERTY LINE IS? PROVIDE A DIMENSION
 FROM THE BUILDING TO THE PROPERTY LINE.
 THERE MAY BE TABLE 600 ISSUES (OPENINGS)
 ON THE EAST AND NORTH SIDES OF THE BUILD
 ING. 0'-3' NO OPENINGS, 3'-10',10% ALLOW
 ABLE OPENINGS. ALSO NOT 705.1.1.2 OPEN-
 INGS WITHIN 15'-0" REQUIRE OPENING
 PROTECTIVES, DEPENDING ON WHERE THE
 PROPERTY LINE IS LOCATED THE DETERMINA-
 TION IF THE PARKING GARAGE CAN REMAIN A
 OPEN STRUCTURE OR IF IT WILL NEED TO BE
 A ENCLOSED PARKING STRUCTURE.
  
 9) PLANS ARE NOT THROUGH ENOUGH FOR THE
 SKY BRIDGE, IS THIS TO BE PART OF THIS
 PERMIT? HOW WILL IT TIE IN ON THE OTHER
 SIDE OF THE STREET? WHAT TYPE OF AGREE-
 MENTS HAVE BEEN MADE WITH THE COUNTY FOR
 THE SKY BRIDGE?
  
 10) SHEET A.31.01 IS THIS A MISPRINT,
 BANK FINISH FLOOR FOR THE 1ST FLOOR TO
 BE AT 20'-0" ELEVATION? THE ELEVATIONS
 ON THE EXTERIOR ARE BETWEEN 8.53/9.92'?
  
 11) RESTROOM 125 DOESN'T HAVE 12" ON THE
 PUSH SIDE OF LATCH, SEE:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 12) CAFE TOLIET, 1202.4.1 TOLIET ROOMS
 SHALL NOT OPEN DIRECTLY INTO A ROOM USED
 FOR THE PREPERATION OF FOOD FOR SERVICE
 TO THE PUBLIC.
  
 13) WINDOW 120 RATED GLASS, TABLE 704.1
 1 HR WALL.
  
 14) 3003.4.1 ELEVATOR STRETCHER REQUIRE-
 MENTS SEE ELE 1 & 2.
  
 15) SHEET A.31.07,A31.09, A.31.11 AND
 A31.13 ALL INDICATE A COLUMN THROUGH THE
 5'-0" HANDICAPPED ACCESS ISLE.
  
 16) SHEET A.31.07 HANDICAPPED PARKING @
 DOOR# 113 (SPACE# 67) DOESN'T HAVE A
 ACCESS ISLE IN FRONT OF THE VEHICLE,
 CAUSING THE PERSON TO WHEEL BEHIND THE
 VEHICLE, IN THE INCOMING TRAFFIC LANE.
  
 17) TICKET BOOTH IS THIS A FABRICATED
 BUILDING? NO DETAILS FOR CONSTRUCTION?
  
 18) 2ND- 5TH FLOOR, THE INTERIOR HALL
 COLUMNS ARE WITHIN 6" OF THE ENTRY DOORS
 TO EACH UNIT. SEE 11-4.13.6 CLEARENCE
 @ DOORS, 12" REQUIRED ON THE PUSH SIDE.
  
 19) A.31.02 OFFICE SPACE SOUTHEAST &
 SOUTHWEST WILL REQUIRE 2 EXITS,1020.1(4)
  
 20) PROVIDE INFORMATION ON THE CANOPY
 OVER THE ENTRY WAY?
  
 21) FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 22)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) EXTERIOR DOORS
 C) LOUVERS
 D) SKYLIGHTS
 E) TRUSS ANCHORS
 F) ROOFING ASSEMBLIES
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 23) STRUCTURAL PLANS MISSING THE FOUNDA-
 TION SCHEDULE, COLUMNS AND BEAMS.
  
 24) PROVIDE ADDTIONAL INFO FOR THE FIRE
 RATING OF ALL STRUCTURAL ELEMENTS FOR
 TYPE II BUILDING.
  
 25) FOUNDATION PLAN HAS THE 2ND FLOOR
 REINFORCING LEGEND ON IT? S1.1.
  
 26) S2.1 COLUMN# 35 IS MISSING ON THIS
 SHEET?
  
 27) S.3.1 THE 3RD FLOOR FRAMING PLAN
 INDICATES A HALLWAY CONNECTION, A CORRI-
 DOR ON THE EAST SIDE OF THE BUILDING,
 PLANS ARE NOT CLEAR AS TO A SECONDARY
 COLUMN LINE, DETAILS ARE MISSING. ALSO
 BETWEEN COLUMN 56 & 39 SHOULD THERE BE
 A COLUMN BETWEEN?
  
 28) SHOULD THERE ALSO BE A COLUMN LINE
 NEXT TO THE PARKING GARAGE STRUCTURE?
  
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 COMMENTS WILL GREATLY ACCELARATE YOUR
 PERMIT.
 JIM WITMER
 BUILDING PLAN REVIEW
 (561)805-6715
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 18 Status P Date 2007-05-03 Cont ID  
Sent By btrobaug Date 2007-05-03 Time 12:37 Rev Time 0.50
Received By btrobaug Date 2007-05-03 Time 12:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 17 Status P Date 2007-04-20 Cont ID  
Sent By btrobaug Date 2007-04-20 Time 16:45 Rev Time 1.00
Received By btrobaug Date 2007-04-20 Time 16:41 Sent To PC
Notes
2007-04-20 16:45:15 
 REV FOR PANEL "ACDP" THE EMS PANEL, INSTALLATIION ON
 5TH FLOOR.

Review Stop E ELECTRICAL
Rev No 16 Status F Date 2007-03-23 Cont ID  
Sent By btrobaug Date 2007-03-23 Time 08:49 Rev Time 0.50
Received By btrobaug Date 2007-03-23 Time 08:44 Sent To PC
Notes
2007-03-23 08:56:33THIS REVISION, #16 IS FOR EMS PANELS./WRT.
2007-03-23 08:49:03 
 REVISION DENIED
  
 THE "WHITE-OUT" ON THE DATE OF THE ENGINEERS SEAL IS
 NOT ACCEPTABLE FOR RECORD RETENTION OR CLARITY IN THE
 FIELD. 106.1.3 FBC AS AMENDED. PLEASE PROVIDE ORIGINAL
 SIGNATURE, DATE AND SEAL PER 471 FS.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 15 Status F Date 2007-03-22 Cont ID  
Sent By btrobaug Date 2007-03-22 Time 10:58 Rev Time 3.00
Received By btrobaug Date 2007-03-16 Time 16:04 Sent To  
Notes
2007-03-22 11:12:31 
 THIS REVIEW, #15 IS CONCERNING CORRIDOR REMOVAL./WRT.
2007-03-22 09:55:52 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} SHEETS E2.2A, E 2.3A, E2.4A AND E2.5A, THE FLOOR
 MUST HAVE EGRESS ILLUMINATION PER 7.8.AND 7.9,
 NFPA-101. PLACE FIXTURES ON PLAN TO SHOW COMPLIANCE.
  
 2} SHEET E3.1A, CIRCUIT L1A-30 TO M1-1, IS LISTED AS A
 SPARE ON THE SCHEDULE.
  
 3} CIRCUIT L1A-6 TO THE SECURITY ROOM RECEPTACLES ARE
 INCORRECTLY LISTED AS "MAIL ROOM" ON THE SCHEDULE.
  
 4} NOTE #7 REFERENCES THE ELEVATOR MACHINE ROOM DETAIL
 WHICH HAS BEEN REMOVED FROM THIS SHEET. NOTE SHOULD BE
 CORRECTED TO REFLECT THE DETAIL ON THE CORRECT SHEET,
 E4.1.
  
 5} CIRCUIT L1A-2 NOW LOCATED IN THE ELECTRIC ROOM, IS
 INCORRECTLY MARKED AS IN THE LOBBY ON THE SCHEDULE.
  
 6}SHEET E3.3A, SHOW THE DOOR ON THE ELECTRICAL ROOM TO
 INDICATE THE EQUIPMENT IS PROPERLY GUARDED PER 110.27.
  
 7} SHEET E4.1 REVISE THIRD FLOOR ELECTRICAL ROOM TO
 INCLUDE A DOOR, 110.27 NEC.
  
 8} SHEET E5.1 DOES NOT INDICATE A FEED FOR PANEL "TB"
 SHOWN ON SHEET E3.1B. IT IS UNDERSTOOD THAT IT WILL BE
 SUPPLIED WITH THE BOOTH EQUIPMENT AS NOTED ON THE PANEL
 SCHEDULE BUT NO INDICATION OF FEEDER AND OCP ORIGIN.
  
 9} SHEET E3.1A LISTS THE ELEVATOR MMACHINE ROOM AS A
 MECHANICAL ROOM, PLEASE CORRELATE.
  
 10} REGARDING SHEET E4.1, THE ELEVATOR MACHINE ROOM IS
 NOT COMPLETE, THE DISCONNECTS FOR ELEVATORS 4 & 5 ARE
 NOT SHOWN.
  
 11} E4.1, THE ELEVATOR MACHINE ROOM FOR ELEVATORS 1, 2,
 AND 3 DOES NOT INCLUDE THE DISCONNECTS FOR SAME. ALSO
 THOSE DISCONNECTS ARE NOT MARKED WITH CIRCUIT NUMBERS
 ON SHEET E3.1. PANEL EL1AIS INCORRECTLY LOCATED ON
 ONE OR THE OTHER SHEET.
  
 13} THE ELECTRICAL ROOM LAYOUT ON E4.1 DOES NOT
 CORRELATE WITH SAME ON SHEET E3.1A.
  
 NOTE: SHEETS E2.1A, E2.6A, E3.1A, E3.2A, E3.3A, E3.4A,
 E3.5A AND E5.1, HAVING BEEN REVIEWED AS COMPLIANT AND
 HAVE BEEN STAMPED AND MADE PART OF THE FILED DOCUMENTS.
 TWO SETS HAVE BEEN STAMPED FOR RETURN TO TO THE
 CONTRACTOR.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 14 Status F Date 2007-01-22 Cont ID  
Sent By btrobaug Date 2007-03-08 Time 16:31 Rev Time 0.00
Received By btrobaug Date 2007-03-08 Time 16:31 Sent To  
Notes
2007-01-22 16:58:57 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 THE ENGINEER OF RECORD MUST SEAL THE DOCUMENTS WITH A
 SEALACCEPTABLETO THE BOARD PER 61G15-23.001, AND
 ILLUSTRATED IN SAME.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 13 Status F Date 2007-03-08 Cont ID  
Sent By btrobaug Date 2007-01-23 Time 12:03 Rev Time 5.00
Received By btrobaug Date 2007-01-19 Time 08:55 Sent To PC
Notes
2007-01-23 10:57:15 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PLEASE NOTE ALL CHANGES WITH CLOUDS AND DELTAS.
 REMOVE CLOUDS AND DELTAS FROM PREVIOUS REVIEWS FOR
 CLARITY. THE POLE MOUNTING DETAIL ON SHEET EO.1 IS NOT
 SHOWN AS A REVISION. SUBMIT THOSE REVISIONS WITH
 SPECIFICATIONS AND ENGINEERING AS REVISIONS FOR THE
 POLES.
  
 2} SHEET E2.1A, CIRCUIT EL1B-6 MARKED FOR THE ELEVATOR
 SHAFT LIGHTING IS INDICATED AS A SPARE ON THE PANEL
 SCHEDULE (E6.1), CIRCUITS 5 & 7 LISTED AS PIT LIGHTS ON
 THE SCHEDULE,
  
 3}THE ELEVATOR PIT RECEPTACLE IS ALSO LISTED ON
 CIRCUIT EL1B-6 ON SHEET E3.1A, THAT CIRCUIT IS #4 ON
 THE SCHEDULE.
 NOTE: THE ELEVATOR CONTROL CIRCUIT WAS REMOVED
 FROM THE PANEL SCHEDULE(S).
  
 4} THE TRANSFORMER IN THE ELECTRICAL ROOM ON SHEET
 E2.1A IS MISMARKED AS PANEL H1A.
  
 5} SHEET E2.3A, THE CORRIDOR LIGHTING IS NOT CIRCUITED
 ( ELEVATOR LOBBY CORRIDOR).
  
 6} SHEET E2.5A, THE ROOM MUST HAVE EGRESS ILLUMINATION
 PER 7.8.1.3NFPA-101. PLACE FIXTURES ON PLAN TO SHOW
 COMPLIANCE.
  
 7} SHEET E3.1A, CIRCUIT L1A-30 TO M1-1, IS LISTED AS A
 SPARE ON THE SCHEDULE.
  
 8} CIRCUIT L1A-6 TO THE SECURITY ROOM RECEPTACLES ARE
 INCORRECTLY LISTED AS "MAIL ROOM" ON THE SCHEDULE.
  
 9} THE DOMESTIC WATER PUMPS (2 EACH) ARE SHOWN ON
 CIRCUIT H1A-31, 33, 35. THE PANEL SCHEDULE SHOWS
 CIRCUITS 37, 39, 41 AS FUTURE . PLEASE CLARIFY THE
 NUMBER OF PUMPS TO BE INSTALLED UNDER THIS PERMIT AND
 THE CIRCUITDESIGNATION OF SAME.
  
 10} NOTE #7 REFERENCES THE ELEVATOR MACHINE ROOM DETAIL
 WHICH HAS BEEN REMOVED FROM THIS SHEET. NOTE SHOULD BE
 CORRECTED TO REFLECT THE DETAIL ON THE CORRECT SHEET,
 E4.1.
  
 11} CIRCUIT L1A-2 NOW LOCATED IN THE ELECTRIC ROOM, IS
 INCORRECTLY MARKED AS IN THE LOBBY ON THE SCHEDULE.
  
 12}SHEET E3.3A, SHOW THE DOOR ON THE ELECTRICAL ROOM TO
 INDICATE THE EQUIPMENT IS PROPERLY GUARDED PER 110.27.
  
 13} REVISE AND SUBMIT SHEET E2.3A TO REFLECT THE
 CHANGES IN THE FLOOR PLAN ON E3.3A.
  
 14} SHEET E4.1 REVISE THIRD FLOOR ELECTRICAL ROOM TO
 INCLUDE A DOOR, 110.27 NEC.
  
 15} SHEET E5.1 DOES NOT INDICATE A FEED FOR PANEL "TB"
 SHOWN ON SHEET E3.1B. IT IS UNDERSTOOD THAT IT WILL BE
 SUPPLIED WITH THE BOOTH EQUIPMENT AS NOTED ON THE PANEL
 SCHEDULE BUT NO INDICATION OF FEEDER AND OCP ORIGIN.
  
 NOTE: SHEETS E2.4A, E3.1B AND E7.1 HAVING BEEN REVIEWED
 AS COMPLIANT AND HAVE BEEN STAMPED AND MADE PART OF THE
 FILED DOCUMENTS. TWO SHEETS HAVE BEEN STAMPED FOR
 RETURN TO TO THE CONTRACTOR. SHEET E3.4A MUST ALSO BE
 REVISED TO MATCH THE CHANGES ON E2.4A.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 12 Status F Date 2007-01-11 Cont ID  
Sent By btrobaug Date 2007-01-11 Time 16:51 Rev Time 1.00
Received By btrobaug Date 2007-01-10 Time 09:00 Sent To  
Notes
2007-01-11 16:51:06 
  
 REVISION DENIED/INCOMPLETE INFORMATION
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} SHEET E2.3A THE LUMINAIRES ADDED TO THE CORRIDOR ATR
 NOT CIRCUITED. PLEASE INDICATE CIRCUIT NUMBERS AND
 PANEL DESIGNATION. 106.3.5.1FBC AS AMMENDED.
  
 2} THE ROLL UP DOOR CIRCUITS ON SHEET E3.1A AND E3.2B
 HAVE NOT BEEN ADDED TO THE PANEL SCHEDULE, AND
 THEREFORE THE CALCULATIIONS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 11 Status F Date 2006-11-22 Cont ID  
Sent By btrobaug Date 2006-11-22 Time 16:34 Rev Time 0.50
Received By btrobaug Date 2006-11-22 Time 16:31 Sent To PC
Notes
2006-11-22 16:34:01 
  
 REVISION DENIED
  
 THE ENGINEER OF RECORD MUST MAKE ALL REVISIONS TO HIS
 DESIGN. CHAPTER 471 FLORIDA STATUTES.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2006-10-31 Cont ID  
Sent By btrobaug Date 2006-10-31 Time 09:34 Rev Time 0.50
Received By btrobaug Date 2006-10-31 Time 07:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2006-08-11 Cont ID  
Sent By btrobaug Date 2006-08-11 Time 10:13 Rev Time 0.50
Received By btrobaug Date 2006-08-11 Time 09:30 Sent To  
Notes
2006-08-11 00:00:00 
  
 NONCOMPLIANT
  
 THE ENGINEER OF RECORD MUST SIGN, SEAL
 AND DATE THE DOCUMENTS PER 471.025
 FLORIDA STATUTES. THERE IS NO SIGNATURE
 ON THE SEAL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2006-06-12 Cont ID  
Sent By btrobaug Date 2006-06-12 Time 13:15 Rev Time 0.50
Received By btrobaug Date 2006-06-12 Time 12:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2006-03-14 Cont ID  
Sent By btrobaug Date 2006-03-14 Time 16:42 Rev Time 0.50
Received By btrobaug Date 2006-03-14 Time 16:29 Sent To  
Notes
2006-03-14 00:00:00 
 FAILED
  
 THE SIGNATURE OF THE ENGINEER MUST BE ON
 THE SEAL PER 61G15-23.002. SEE SHEET
 E3.5B.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-01-05 Cont ID  
Sent By btrobaug Date 2006-01-05 Time 15:31 Rev Time 1.00
Received By btrobaug Date 2006-01-05 Time 12:08 Sent To  
Notes
2006-01-05 00:00:00 
 SHEET E3.5B HAS CIRCUIT L4A-15 AT THE
 STAIRWELL RECEPTACLES. PLEAE REVISE
 SHEET E6.2 L4A PANEL SCHEDULE TO REFLECT
 SAME, AND RESUBMITWITH THE NEXT REVISION
 FOR THAT SHEET.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-06-28 Cont ID  
Sent By btrobaug Date 2005-06-28 Time 18:09 Rev Time 1.00
Received By btrobaug Date 2005-06-28 Time 16:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-05-24 Cont ID  
Sent By btrobaug Date 2005-05-24 Time 13:21 Rev Time 1.50
Received By btrobaug Date 2005-05-24 Time 12:05 Sent To  
Notes
2005-05-24 00:00:00 
 SHEETS E0.1,E3.1A,E5.1 AND E6.1 NEED THE
 ENGINEERS SIGNATURE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-03-10 Cont ID  
Sent By btrobaug Date 2005-03-10 Time 14:40 Rev Time 1.00
Received By btrobaug Date 2005-03-10 Time 10:24 Sent To  
Notes
2005-03-10 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE THE FIRE PUMP MOTER DESIGN
 LETTER SO THAT LOCKEE ROTOR CURRENT CAN
 BE DETERMINED FOR THE DISCONNECTING
 MEANS. I COULD NOT FIND THE DESIGNATION
 IN THE SPECS.
  
 2} INDICATE THAT THE FIRE PUMP
 CONTROLLER HAS AN EXTERNAL MEANS OF
 DISCONNECT ON THE PLAN ALSO INDICATE
 AMPERAGE RATING OF SAME ON PLANS. AGAIN
 THESE WERE NOT CLEAR IN THE SPECS.
  
 3} CORRELATE THE HP OF THE FIRE PUMP
 RATING ON THE PLAN WITH THE ONE IN THE
 SPECS.
  
 4} THERE ARE STILL NO LOAD OR BREAKER
 SIZES IN MSBA FOR CIRCUITS 7,8&9.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-09-23 Cont ID  
Sent By btrobaug Date 2004-09-23 Time 14:28 Rev Time 2.00
Received By btrobaug Date 2004-09-23 Time 07:47 Sent To  
Notes
2004-09-23 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE INFORMATION AND
 TECHNICAL DATA/SPECIFICATIONS FOR THE
 FIRE PUMP. SUCH INFORMATION SHOULD
 INDICATE COMPLIANCE WITH ARTICLES
 230.76, 230.79, AND 695.4 NEC 2002.
  
 2} WHAT ARE THE DISCONNECTS SHOWN ON
 SHEET E3.1A,ELEVATOR MACHINE ROOM
 DETAIL, USED FOR? THEY ARE BEING FED
 FROM MSBA CIRCUITS 7,8 & 9, THESE
 CIRCUITS SHOW NO LOADS ON THE MSBA
 SCHEDULE.
  
 3} PLEASE ADDRESS COMMENTS ON FIRE
 REVIEW AND SHOW ALL LIGHTING
 CORRECTIONS ON ELECTRICAL SHEETS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-13 Cont ID  
Sent By btrobaug Date 2004-05-13 Time 09:17 Rev Time 1.00
Received By btrobaug Date 2004-05-13 Time 08:20 Sent To Z
Notes
2004-05-13 00:00:00 
 ELECTRICAL PLANS ARE INCOMPLETE AND DO
 NOT CONTAIN ENOUGH INFORMATION FOR
 REVIEW.
 SUBMIT DRAWINGS PER 2002 NEC. INCLUDE
 LOAD CALCULATIONS, CONDUCTOR AND
 RACEWAY SIZES,PANEL SCHEDULES FOR ALL
 PANELS(ONLY "L" SUBMITTED-TWICE,SEE
 E6.1 & E6.2), THE TRANSFORMER RATINGS
 FOR THE EQUIPMENT BEING USED FOR THE
 SERVICE AND SUB FEEDS,LOCATION OF
 LUMINAIRES AND RECEPTACLES. COMPLETE
 THE LIGHTING FIXTURE SCHEDULE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop ENG ENGINEERING CSD
Rev No 5 Status F Date 2007-01-18 Cont ID  
Sent By rchokshi Date 2007-01-18 Time 11:28 Rev Time 0.00
Received By rchokshi Date 2007-01-18 Time 11:20 Sent To  
Notes
2007-01-18 11:28:20NEED TO BE REVIEWED BY BRIAN MOREE (494-1040) AT 45TH
 STREET ENG FORCURB& ROW. PLEASE CONTACT BRIAN
 MOREE. AFTER HIS REVIEW, WE AT ENG. WILL APPROVE IT.
  
 RASIK CHOKSHI 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2006-06-06 Cont ID  
Sent By   Date 2006-06-06 Time   Rev Time 1.00
Received By   Date 2006-06-06 Time   Sent To  
Notes
2006-06-06 00:00:00FYI-SHEET C7 OF 10: 4" BFV SHOULD READ
 4" BFP.

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2005-02-25 Cont ID  
Sent By mamini Date 2005-02-25 Time 15:43 Rev Time 1.00
Received By mamini Date 2005-02-25 Time 15:43 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2004-08-20 Cont ID  
Sent By mamini Date 2004-08-20 Time 09:27 Rev Time 1.00
Received By mamini Date 2004-08-20 Time 09:27 Sent To  
Notes
2004-08-20 00:00:00FAILED:
 1. ALL THE REVIEW COMMENTS FROM PUBLIC
 UTILITIES & ENGINEERING AND FROM
 THE CONSTRUCTION SERVICES, DATED 5/10/04
 MUST BE ADDRESSED AND IMPLEMENTED PRIOR
 TO THE NEXT SUBMITTAL.
 2. SHEET C2 OF C8, NOTE NO. 2 UNDER TYP
 ROAD CONSTRUCTION, PLEASE VERIFY THE
 PROPOSED 14" LIMEROCK BASE.
 2. SHEET C2 OF C8, PLEASE VERIFY
 EXFILTRATION DETAIL WITH SHEET C4 OF C8
 AND NOTE THAT PIPE USED IN PUBLIC R.O.W
 MUST BE CONCRETE C76 CLASS III.
 3. PLEASE NOTE THAT ANY WORK WITHIN
 PUBLIC R.O.W WILL REQUIRES A SEPARATE
 PERMIT FROM PUBLIC UTILITIES AND
 ENGINEERING, ATT: WINDEL PALMER 949-1086
 NOTE TO G.C.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2004-05-10 Cont ID  
Sent By mamini Date 2004-05-10 Time 14:20 Rev Time 1.00
Received By mamini Date 2004-05-10 Time 14:20 Sent To  
Notes
2004-05-10 00:00:00FAILED:
 1. PROPOSED MDIFICATION OF W. RAILROAD
 MUST BE APPROVED BY THE PUBLIC UTILITIES
 & ENGINEERING.
 2. CIVIL PLANS MUST BE APPROVED FOR ALL
 THE CONNECTIONS FOR CITY SERVICES BY THE
 PUBLIC UTILITIES & ENGINEERING, 659-8040
 ATT: MANNY GONZALEZ.
 3. PLEASE SUBMIT CALCULATION FOR THE
 PROPOSED DARINAGE SYS., INCLUDE PERVIOUS
 & IMPERVIOUS FOR TOTAL SITE AREA.
 4. IT IS RECOMMENDED TO LOCATE THE DDC
 ASSEMBLIES AT ENTRANCES TO THE BUILDING,
 PLEASE VERIFY.
 5. ROOF RAIN LEADERS MUST BE SHOWN AND
 CONNECTED TO DRAINAGE SYS.
 6. SURVEYING SHEET MUST HAVE THE
 ORIGINAL RAISED SEAL AND SIGNATURE OF
 THE REGISTERED LAND SURVEYOR, A MUST FOR
 ACTUAL PERMITTING.
 7. AIR RIGHTS EASEMENTS AGREEMENT FOR
 THE PROPOSED SKY BRIDGE OVER PUBLIC
 R.O.W (3RD ST.) MAY BE REQUIRED,CONTACT
 PLANNING & ZONING 659-8031. ALSO A
 SEPARATE R.O.W PERMIT FROM PUBLIC
 UTILITIES AND ENGINEERING FOR THIS WORK
 IS REQUIRED, 949-1040 EXT. 1086.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 12 Status P Date 2007-05-03 Cont ID  
Sent By mawillia Date 2007-05-03 Time 10:52 Rev Time 0.00
Received By mawillia Date 2007-05-03 Time 10:50 Sent To  
Notes
2007-05-03 10:52:46*****REVISION #38 DATED 05/02/2007 APPROVED*****
  
  
 REVISED PLAN SHEETS E2.2A AND E.2.5A WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 11 Status P Date 2007-03-26 Cont ID  
Sent By mawillia Date 2007-03-26 Time 17:35 Rev Time 0.00
Received By mawillia Date 2007-03-26 Time 17:00 Sent To  
Notes
2007-03-26 17:35:12*****APPROVED*****
  
  
 REVISED PLAN SHEETS A.11.01, A11.02, A.11.03, FA2.1A,
 FA2.2A, FA2.3A, FA2.4A, FA2.5A, AND FA2.6 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 10 Status P Date 2007-03-21 Cont ID  
Sent By mwennerg Date 2007-03-21 Time 11:06 Rev Time 0.00
Received By mwennerg Date 2007-03-21 Time 11:06 Sent To  
Notes
2007-03-21 11:12:03***PROVISO***
  
 1) MEANS OF EGRESS SHALL BE CLEARLY MARKED IN
 ACCORDANCE WITH NFPA 101, AND EXIT SIGNS SHALL NOT BE
 PLACED AT DISTANCES EXCEEDING 100' APART.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW(561) 805-6722
 FIRE PREVENTION(561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 9 Status F Date 2007-01-16 Cont ID  
Sent By mwennerg Date 2007-01-16 Time 10:17 Rev Time 0.00
Received By mwennerg Date 2007-01-16 Time 10:17 Sent To  
Notes
2007-01-16 10:22:01***DENIED***
  
 1) FIRE EXTINGUISHERS ARE SHOWN ON SOME SHEETS, BUT
 MISSING ON OTHERS. WHEN THE LOCATIONS ARE ILLUSTRATED,
 PLACEMENT SHALL BE WITHIN 75' TRAVEL DISTANCE.
  
 2) NEW FIRE DAMPER INSTALLATIONS SHALL BE TESTED FOR
 CLOSURE PRIOR TO FINAL INSPECTION.
  
 3) IF SEPARATE SHOP DRAWINGS AND PERMIT HAS BEEN ISSUED
 FOR FIRE ALARM SYSTEM, CHANGES TO THAT SYSTEM TO BE
 SUBMITTED UNDER THAT PERMIT.
  
 4) SOME SMOKE DETECTORS APPEAR TO BE MISSING FROM
 ELEVATOR LOBBIES.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 (561) 805-6722 OR 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status N Date 2006-06-14 Cont ID  
Sent By mwennerg Date 2006-06-14 Time 15:30 Rev Time 0.00
Received By mwennerg Date 2006-06-14 Time 15:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2006-03-30 Cont ID  
Sent By mwennerg Date 2006-03-30 Time 14:18 Rev Time 0.00
Received By mwennerg Date 2006-03-30 Time 14:18 Sent To  
Notes
2006-03-30 00:00:00REVISIONS SUBMITTED WITH NO NEW FIRE
 ALARM SHEETS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2006-01-04 Cont ID  
Sent By mcarsill Date 2006-01-04 Time 10:23 Rev Time 0.00
Received By mcarsill Date 2006-01-04 Time 10:23 Sent To  
Notes
2006-01-04 00:00:001. THE PROPOSED SIXTH FLOOR ADDITION TO
 THE GARAGE SHALL COMPLY WITH NFPA 88A.
  
 2. EXIT STAIRS SHALL COMPLY WITH ALL NEW
 STAIR REQUIREMENTS.
  
 3. SIGNS ARE REQUIRED INDICATING STAIR
 IDENTITY, FLOOR LEVEL, STAIR TERMINUS
 TOP AND BOTTOM, ETC.
  
 4. EXIT SIGNS ON THE 6TH FLOOR LEVEL
 SHALL NOT EXCEED 100 FEET.
  
 5. EMERGENCY LIGHTING ON THE 6TH FLOOR
 LEVEL SHALL MEET MINIMUM CODE
 REQUIREMENTS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2005-06-30 Cont ID  
Sent By mwennerg Date 2005-06-30 Time 09:37 Rev Time 0.00
Received By mwennerg Date 2005-06-30 Time 09:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2005-05-27 Cont ID  
Sent By mwennerg Date 2005-05-27 Time 11:22 Rev Time 0.00
Received By mwennerg Date 2005-05-27 Time 11:21 Sent To  
Notes
2005-05-27 00:00:00****DENIED****
  
 1) FIRE SPRINKLER AND FIRE ALARM
 DRAWINGS HAVE BEEN SUBMITTED UNDER THIS
 PERMIT APPLICATION. PLEASE BE ADVISED
 THAT SEPARATE PERMITS ARE REQUIRED FOR
 BOTH SYSTEMS.
  
 2) PLEASE REFER TO MECHANICAL COMMENTS
 IN REGARDS TO FIRE SPRINKLER EXTENSION
 IN CHANGED AREAS.
  
 3) A COPY OF THE PREVIOUS FIRE REVIEW
 COMMENTS HAS BEEN SUBMITTED WITH NO
 RESPONSES. PLEASE ADDRESS THE COMMENTS
 AND SHOW CHANGES ON THE DRAWINGS.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2951 OR 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2005-03-29 Cont ID  
Sent By mwennerg Date 2005-03-29 Time 13:21 Rev Time 0.00
Received By mwennerg Date 2005-03-29 Time 13:21 Sent To  
Notes
2005-03-29 00:00:00DENIED
  
 1) ELECTRICAL DRAWINGS-
 1) PLEASE BE ADVISED THAT YOUR COMMENTS
 ARE NOT REFLECTED AS REVISIONS ON THESE
 PLANS. IN ADDITION TO YOUR REVIEW NOTES,
 PLEASE PROVIDE ALL CHANGES ONTO THE
 PLANS FOR FURTHER REVIEW.
  
 2) CONSTUCTION DRAWINGS-
 1) PLEASE BE ADVISED THAT YOUR COMMENTS
 ARE NOT REFLECTED AS REVISIONS ON THESE
 PLANS. IN ADDITION TO YOUR REVIEW NOTES,
 PLEASE PROVIDE ALL CHANGES ONTO THE
 PLANS FOR FURTHER REVIEW.
  
 3) FIRE ALARM DRAWINGS-
 1) PLEASE BE ADVISED THAT THE CITY OF
 WEST PALM BEACH REQUIRES THE DUCT SMOKE
 DETECTORS TO SOUND A GENERAL FIRE ALARM
 WHEN ACTIVATED.
  
 2) SEPARATE SHOP DRAWINGS AND PERMIT IS
 REQUIRED FOR FIRE ALARM SYSTEM.
  
 FIRE SPRINKLER DRAWINGS-
 1) PLANS SHOW NO SPRINKLER COVERAGE IN
 THE FIRST FLOOR ELECTRICAL ROOM. PLEASE
 EXPLAIN WHAT EXCEPTIONS ARE BEING
 FOLLOWED.
  
 2) SITE PLAN DOES NOT SHOW WHAT ACCESS
 IS PROVIDED FOR THE FIRE DEPARTMENT
 CONNECTION.
  
 3) THE FIRE DEPARTMENT CONNECTION SHALL
 BE LOCATED NO FURTHER THAN 150 FEET FROM
 THE CLOSEST FIRE HYDRANT.
  
 4) SEPARATE SHOP DRAWINGS AND PERMIT IS
 REQUIRED FOR FIRE SPRINKLER SYSTEM.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2004-09-16 Cont ID  
Sent By mcarsill Date 2004-09-16 Time 11:57 Rev Time 0.00
Received By mcarsill Date 2004-09-16 Time 11:57 Sent To  
Notes
2004-09-16 00:00:001) NO EXIT SIGN OR EMERGENCY LIGHTS IN
 CAFE OR BANK.
  
 2) AN EXIT SIGN ON THE FIRST FLOOR
 LIGHTING PLAN DIRECTS PEOPLE FROM THE
 DRIVE THRU AREA TO WHERE.
  
 3) EXIT SIGN MISSING FROM GARAGE STAIR
 ON FIRST FLOOR LIGHTING PLAN.
  
 4) PLEASE EXPLAIN EXITING ARRANGEMENT
 FOR THE NORTHWEST OFFICE AND NORTHEAST
 OFFICE, THIRD FLOOR.
  
 5) PLEASE EXPLAIN EXITING RATIONALE
 FROM THIRD FLOOR BRIDGE FROM COURTHOUSE
 COMMONS BUILDING TO THE EXISTING
 PARKING GARAGE. WHO PRESENTLY OWNS
 THE EXISTING PARKING GARAGE AND HOW
 DO YOU EXIT PEOPLE ONTO OTHER PERSONS
 PROPERTY.
  
 6) EXIT SIGN APPEARS TO BE MISSING FROM
 CENTER STAIR 4TH FLOOR LIGHTING PLAN.
  
 7) EMERGENCY LIGHTING MISSING AT EXIT
 DOORS ON FIFTH FLOOR LIGHTING PLAN (B).
  
 8) EXIT SIGNS MISSING FROM ROOF LIGHTING
 PLAN.
  
 9) FIRE ALARM NOTES # 17 AND 19 ARE
 INCORRECT. DUCT SMOKE DETECTORS WHEN
 ACTIVATED SHALL INITIATE AN ALARM NOT
 A SUPERVISORY SIGNAL. FIRE ALARM
 CIRCUITS SHALL BE CLASS A OR STYLE D
 OR BE FULLY ADDRESSABLE. FIRE ALARM
 SYSTEM SHALL BE UL LISTED FOR CENTRAL
 STATION SERVICE.
  
 10) FIRE ALARM INITIATING DEVICES
 APPEAR TO BE MISSING FROM THE ROOF
 ELEVATOR MECHANICAL ROOM.
  
 11) PLEASE PROVIDE UL NUMBERS FOR
 ALL FIRE RATED WALLS.
  
 12) ALL RATED WALLS SHOULD HAVE DASHED
 LINES INDICATING ONE HOUR OR TWO
 HOUR ASSEMBLIES.
  
 13) PLEASE VERIFY ALL EXIT DOORS
 SWINGS.
  
 14) DOORS 6A1 AND 6A2 ON ROOF SWING
 IN THE WRONG DIRECTION.
  
 15) ALL NEW RAMPS AND STAIRS SHALL
 HAVE HANDRAILS ON BOTH SIDES.
  
 16) ELEVATOR WARNING SIGNS REQUIRED.
  
 17) THE FIRE DEPARTMENT CONNECTION IS
 LOCATED ON THE WRONG SIDE OF THE
 BUILDING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-05-05 Cont ID  
Sent By mcarsill Date 2004-05-04 Time 11:09 Rev Time 0.00
Received By mcarsill Date 2004-05-04 Time 11:09 Sent To  
Notes
2004-05-04 00:00:001) SITE PLAN DOES NOT ILLUSTRATE NEW
 OR EXISTING FIRE HYDRANTS.
  
 2) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH
 NFPA 241.
  
 3) TEMPORARY STANDPIPE SYSTEMS
 REQUIRED WHEN THE BUILDING REACHES
 THREE FLOORS OR THIRTY FEET IN HEIGHT.
  
 4) STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 5) TACTILE SIGNAGE REQUIRED AT EXITS.
  
 6) ALL SHAFTS THAT ARE LARGE ENOUGH
 FOR PERSONS TO FALL INTO MUST BE
 MARKED "SHAFTWAY" WITH 6" LETTERS.
  
 7) BUILDING ADDRESSES REQUIRED. A
 MINIMUM OF AT LEAST 6" HIGH NUMBERS.
  
 8) KNOX-BOXES WILL BE REQUIRED.
  
 9) LOCKING KNOX-BOX CAPS WILL BE
 REQUIRED FOR THE FIRE DEPARTMENT
 CONNECTIONS.
  
 10) ALL NEW STAIRS AND RAMPS ARE
 REQUIRED TO HAVE HANDRAILS ON BOTH
 SIDES.
  
 11) BUILDINGS WILL BE LOCATED IN THE
 CITY FIRE LIMITS. CETRAIN RESTRICTIONS
 WILL APPLY. PLEASE SEE APPENDIX F,
 LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE.
  
 12) IT APPEARS THAT STAIR A-B-1
 TERMINATES INTO THE LOADING DOCK.
 PLEASE EXPLAIN RATIONALE.
  
 13) HOW IS ACCESS PROVIDED INTO THE
 FIRE PUMP ROOM WHEN THE SECURITY
 GRILL IS DOWN FOR THE GARAGE AREA.
  
 14) PLEASE INDICATE WHICH ELEVATOR(S)
 WILL BE STRETCHER ACCESSIBLE.
  
 15) PLEASE PROVIDE A LIFE SAFETY PLAN
 INDICATING OCCUPANT LOADS, TRAVEL
 DISTANCES, DEAD-ENDS, ETC.
  
 16) PLEASE DISPLAY ALL TENANT SEPARATION
 WALLS.
  
 17) PLEASE VERIFY DOOR SWINGS. DOOR 111
 APPEARS TO SWING IN THE WRONG DIRECTION.
  
 18) HOW IS EXIT ACCESS ACHIEVED TO
 DOOR 202. A COLUMN AND A PARKING
 SPACE IS PRESENT. PLEASE EXPLAIN.
  
 19) SAME CONDITION APPEARS TO EXIST
 FOR DOOR 301. SAME FOR DOOR 401.
  
 20) PLEASE PROVIDE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR ALL HANDRAILS
 AND GUARDRAILS.
  
 21) TWO DOORS CLOSELY SPACED AT STAIR
 A-1, LEVEL 3. HOW DO PEOPLE MOVE
 QUICKLY IS TWO DIRECTIONS IN THIS SMALL
 AREA.
  
 22) STAIR IDENTIFICATION SIGNS REQUIRED.
 THESE SIGNS SHALL IDENTIFY STAIR
 NUMBER, TERMINUS TOP AND BOTTOM, AND
 FLOOR NUMBER.
  
 23) PLEASE INDICATE INTERIOR FINISH
 FOR WALL AND CEILINGS.
  
 24) DOES THE CORRIDOR CONNECT TO THE
 EXISTING UNSPRINKLERED PARKING GARAGE.
 PLEASE ADVISE. PLEASE SEE FS 553.895 (2)
  
 25) PLEASE IDENTIFY HEIGHT OF
 CONNECTION BRIDGE. A MINIMUM OF 13 FEET
 6 INCHES WILL BE REQUIRED.
  
 26) DOOR SCHEDULES DO NOT IDENTIFY
 REQUIRED FIRE RATINGS.
  
 27) PLEASE EXPLAIN IF CAFE WILL BE
 COOKING ANY ITEMS THAT PRODUCE SMOKE
 OR GREASE LADEN VAPORS. IF SO WHERE
 WILL THE REQUIRED GREASE HOOD DUCT
 TERMINATE.
  
 28) LOADING DOCK WILL BE REQUIRED TO
 BE FIRE SPRINKLER PROTECTED.
  
 29) A TWO HOUR FIRE SEPARATION WILL
 BE REQUIRED FOR ANY PARKING AREAS AND
 ADJACENT AREAS.
  
 30) PLEASE DISPLAY ALL FIRE RATED WALLS
 AND SHAFTS AND THEIR APPROPRIATE
 HOURLY RATINGS. PLEASE PROVIDE UL
 NUMBERS.
  
 31) NO EXIT SIGNS AND EMERGENCY LIGHTS
 SHOWN ON FIRST FLOOR A, PAGE E2.1A.
  
 32) WHERE IS THE SECOND EXIT IDENTIFIED
 ON FIRST FLOOR B, PAGE E2.1B. ALSO
 EXIT SIGNS SHOWN IN WITHIN PARKING
 SPACES.
  
 33) WHERE DOES THE EXIT SIGN FROM THE
 CORRIDOR TO THE BRIDGE LEAD TO.
  
 34) EXIT SIGN MISSING INFRONT OF EXIT
 FOURTH FLOOR SECTION A, PAGE E2.4A
 SAME CONDITION EXISTS ON PAGE E2.5A.
  
 35) EMERGENCY LIGHTING REQUIRED IN
 FIRE PUMP ROOM.
  
 36) PLEASE INDICATE OCCUPANT LOADS
 FOR ALL STAIRS. AT LEAST ONE STAIR
 IS BEING SHARED WITH THE GARAGE.
  
 37) NO FIRE SPRINKLER DRAWINGS
 PROVIDED WITH PLANS.
  
 38) NEW FIRE ALARM SYSTEM SHALL BE
 UL LISTED FOR CENTRAL STATION SERVICE.
  
 39) PLEASE PROVIDE CONSTRUCTION TYPE
 FOR THE BUILDING.
  
 40) PLEASE DISPLAY STANDPIPE SYSTEM
 LOCATIONS.
  
 41) MORE DETAILS REQUIRED FOR FIRE
 PUMP.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 43 Status N Date 2007-05-02 Cont ID  
Sent By adarroug Date 2007-05-02 Time 15:37 Rev Time 0.00
Received By adarroug Date 2007-05-02 Time 15:37 Sent To E
Notes
2007-05-02 15:38:16TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 42 Status N Date 2007-04-20 Cont ID  
Sent By adarroug Date 2007-04-20 Time 16:52 Rev Time 0.00
Received By adarroug Date 2007-04-20 Time 16:52 Sent To M
Notes
2007-04-20 16:52:28TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 41 Status N Date 2007-04-06 Cont ID  
Sent By spalmer Date 2007-04-06 Time 17:11 Rev Time 0.00
Received By spalmer Date 2007-04-06 Time 17:11 Sent To B
Notes
2007-04-06 17:11:35TO JIM WITMER

Review Stop I INCOMING/PROCESSING
Rev No 40 Status N Date 2007-04-02 Cont ID  
Sent By spalmer Date 2007-04-02 Time 17:38 Rev Time 0.00
Received By spalmer Date 2007-04-02 Time 17:38 Sent To E
Notes
2007-04-02 17:39:09ELEC REV TO BILL TROBAUGH

Review Stop I INCOMING/PROCESSING
Rev No 39 Status N Date 2007-04-02 Cont ID  
Sent By spalmer Date 2007-04-02 Time 17:34 Rev Time 0.00
Received By spalmer Date 2007-04-02 Time 17:33 Sent To P
Notes
2007-04-02 17:34:13PLUMB REV TO KEN STEVENS

Review Stop I INCOMING/PROCESSING
Rev No 38 Status N Date 2007-03-24 Cont ID  
Sent By adarroug Date 2007-03-24 Time 15:25 Rev Time 0.00
Received By adarroug Date 2007-03-24 Time 15:25 Sent To B
Notes
2007-03-24 15:26:13TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 37 Status N Date 2007-03-22 Cont ID  
Sent By adarroug Date 2007-03-22 Time 16:24 Rev Time 0.00
Received By adarroug Date 2007-03-22 Time 16:24 Sent To Z
Notes
2007-03-22 16:24:59TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 36 Status N Date 2007-03-14 Cont ID  
Sent By adarroug Date 2007-03-14 Time 11:39 Rev Time 0.00
Received By adarroug Date 2007-03-14 Time 11:39 Sent To E
Notes
2007-03-14 11:40:14TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 35 Status N Date 2007-03-14 Cont ID  
Sent By adarroug Date 2007-03-14 Time 09:46 Rev Time 0.00
Received By adarroug Date 2007-03-14 Time 09:46 Sent To M
Notes
2007-03-14 09:46:41TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 34 Status N Date 2007-03-06 Cont ID  
Sent By adarroug Date 2007-03-06 Time 13:46 Rev Time 0.00
Received By adarroug Date 2007-03-06 Time 13:30 Sent To  
Notes
2007-03-08 13:10:42TO "COMM" BD#10--PLANS ON RACK 4 ROLLS
2007-03-06 13:30:59WAITING FOR "COMM "BD--REV

Review Stop I INCOMING/PROCESSING
Rev No 33 Status N Date 2007-03-03 Cont ID  
Sent By adarroug Date 2007-03-03 Time 14:34 Rev Time 0.00
Received By adarroug Date 2007-03-03 Time 14:34 Sent To M
Notes
2007-03-03 14:35:14TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 32 Status   Date 2007-02-12 Cont ID  
Sent By adarroug Date 2007-02-12 Time 11:27 Rev Time 0.00
Received By adarroug Date 2007-02-12 Time 13:15 Sent To  
Notes
2007-02-26 11:27:45TO "COMM" BD#1
2007-02-12 13:16:10WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 31 Status N Date 2007-02-12 Cont ID  
Sent By adarroug Date 2007-02-12 Time 10:03 Rev Time 0.00
Received By adarroug Date 2007-02-12 Time 10:03 Sent To P
Notes
2007-02-12 10:03:42TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 30 Status N Date 2007-02-12 Cont ID  
Sent By adarroug Date 2007-02-12 Time 09:54 Rev Time 0.00
Received By adarroug Date 2007-02-12 Time 09:54 Sent To M
Notes
2007-02-12 09:55:15TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 29 Status N Date 2007-01-20 Cont ID  
Sent By adarroug Date 2007-01-20 Time 15:34 Rev Time 0.00
Received By adarroug Date 2007-01-20 Time 15:34 Sent To M
Notes
2007-01-20 15:35:07TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 28 Status N Date 2007-01-20 Cont ID  
Sent By adarroug Date 2007-01-20 Time 15:32 Rev Time 0.00
Received By adarroug Date 2007-01-20 Time 15:32 Sent To P
Notes
2007-01-20 15:32:39TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 27 Status N Date 2007-01-08 Cont ID  
Sent By adarroug Date 2007-01-08 Time 16:11 Rev Time 0.00
Received By adarroug Date 2007-01-08 Time 16:11 Sent To M
Notes
2007-01-08 16:11:39TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 26 Status N Date 2006-12-22 Cont ID  
Sent By adarroug Date 2006-12-22 Time 09:22 Rev Time 0.00
Received By adarroug Date 2006-12-22 Time 09:21 Sent To  
Notes
2007-01-11 11:02:28TO "COMM" BD#64
2006-12-22 09:23:04WAITING FOR "COMM" BD--REV

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2006-12-18 Cont ID  
Sent By adarroug Date 2006-12-18 Time 11:35 Rev Time 0.00
Received By adarroug Date 2006-12-18 Time 11:35 Sent To B
Notes
2006-12-18 11:35:29TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2006-12-13 Cont ID  
Sent By adarroug Date 2006-12-13 Time 14:35 Rev Time 0.00
Received By adarroug Date 2006-12-13 Time 14:35 Sent To B
Notes
2006-12-13 14:36:06TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2006-12-08 Cont ID  
Sent By adarroug Date 2006-12-08 Time 13:22 Rev Time 0.00
Received By adarroug Date 2006-12-08 Time 13:22 Sent To M
Notes
2006-12-08 13:22:37TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2006-12-06 Cont ID  
Sent By adarroug Date 2006-12-06 Time 15:19 Rev Time 0.00
Received By adarroug Date 2006-12-06 Time 15:19 Sent To  
Notes
2006-12-08 13:21:4112/7/06-REV TAKEN FROM REVIEW PROCESS PER CUSTOMER
 REQUEST
2006-12-06 15:21:11WAITING FOR "COMM" BD--REV >E>M

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2006-12-04 Cont ID  
Sent By adarroug Date 2006-12-04 Time 09:35 Rev Time 0.00
Received By adarroug Date 2006-12-04 Time 09:35 Sent To  
Notes
2006-12-21 08:51:05TO "COMM" BD#16/PLANS ON RACK--3 SMALL ROLLS
2006-12-04 09:35:50WAITING FOR "COMM" BD--REV

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2006-12-01 Cont ID  
Sent By adarroug Date 2006-12-01 Time 10:39 Rev Time 0.00
Received By adarroug Date 2006-12-01 Time 10:39 Sent To M
Notes
2006-12-01 10:40:16TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2006-10-24 Cont ID  
Sent By adarroug Date 2006-10-24 Time 10:27 Rev Time 0.00
Received By adarroug Date 2006-10-24 Time 10:27 Sent To  
Notes
2006-10-26 08:44:09TO "COMM" BD#6
2006-10-24 10:28:00WAITING FOR "COMM" BD--REV

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2006-07-11 Cont ID  
Sent By adarroug Date 2006-07-11 Time 12:17 Rev Time 0.00
Received By adarroug Date 2006-07-11 Time 12:17 Sent To  
Notes
2006-07-26 00:00:00TO "COMM" BD#48
2006-07-11 00:00:00WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2006-05-08 Cont ID  
Sent By adarroug Date 2006-05-08 Time 16:24 Rev Time 0.00
Received By adarroug Date 2006-05-08 Time 16:24 Sent To  
Notes
2006-05-25 00:00:00TO "COMM" BD#28
2006-05-08 00:00:00WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2006-04-21 Cont ID  
Sent By adarroug Date 2006-04-21 Time 14:54 Rev Time 0.00
Received By adarroug Date 2006-04-21 Time 14:54 Sent To ENG
Notes
2006-04-21 00:00:00TO "ENG" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2006-04-05 Cont ID  
Sent By adarroug Date 2006-04-05 Time 09:35 Rev Time 0.00
Received By adarroug Date 2006-04-05 Time 09:35 Sent To B
Notes
2006-04-05 00:00:00TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2006-03-10 Cont ID  
Sent By adarroug Date 2006-03-10 Time 13:41 Rev Time 0.00
Received By adarroug Date 2006-03-10 Time 13:41 Sent To  
Notes
2006-03-10 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2006-02-15 Cont ID  
Sent By adarroug Date 2006-02-15 Time 17:22 Rev Time 0.00
Received By adarroug Date 2006-02-15 Time 17:22 Sent To B
Notes
2006-02-15 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2006-02-14 Cont ID  
Sent By adarroug Date 2006-02-14 Time 14:43 Rev Time 0.00
Received By adarroug Date 2006-02-14 Time 14:43 Sent To  
Notes
2006-03-03 00:00:00TO "COMM" BD#43-REV
2006-02-14 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 11 Status   Date 2005-11-17 Cont ID  
Sent By adarroug Date 2005-10-12 Time 14:18 Rev Time 0.00
Received By adarroug Date 2005-10-12 Time 14:18 Sent To  
Notes
2005-11-17 00:00:00TO "COMM" BD#63

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-10-04 Cont ID  
Sent By adarroug Date 2005-10-04 Time 16:30 Rev Time 0.00
Received By adarroug Date 2005-10-04 Time 16:30 Sent To Z
Notes
2005-10-04 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-06-24 Cont ID  
Sent By adarroug Date 2005-06-24 Time 15:07 Rev Time 0.00
Received By adarroug Date 2005-06-24 Time 15:07 Sent To  
Notes
2005-06-27 00:00:00TO "COMM" BD#60/PLANS ON RACK/9 ROLLS
2005-06-24 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-05-19 Cont ID  
Sent By adarroug Date 2005-05-19 Time 12:39 Rev Time 0.00
Received By adarroug Date 2005-05-19 Time 12:39 Sent To  
Notes
2005-05-19 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-05-13 Cont ID  
Sent By adarroug Date 2005-05-13 Time 11:06 Rev Time 0.00
Received By adarroug Date 2005-05-13 Time 11:06 Sent To  
Notes
2005-05-13 00:00:00PRODUCT APPROVALS ADDED TO PLANS ON
 BD#39

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-05-11 Cont ID  
Sent By adarroug Date 2005-05-04 Time 16:39 Rev Time 0.00
Received By adarroug Date 2005-05-04 Time 16:35 Sent To  
Notes
2005-05-11 00:00:00TO "COMM" BD#39/"COMM" RACK 8 ROLLS
2005-05-04 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-03-29 Cont ID  
Sent By adarroug Date 2005-03-29 Time 15:11 Rev Time 0.00
Received By adarroug Date 2005-03-29 Time 15:11 Sent To Z
Notes
2005-03-29 00:00:00TO "Z" BOX/TAKEN OFF BD#50

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-02-25 Cont ID  
Sent By adarroug Date 2005-02-25 Time 15:25 Rev Time 0.00
Received By adarroug Date 2005-02-25 Time 15:25 Sent To  
Notes
2005-02-25 00:00:00TO "COMM"BD#50

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-23 Cont ID  
Sent By adarroug Date 2005-02-23 Time 11:37 Rev Time 0.00
Received By adarroug Date 2005-02-23 Time 11:37 Sent To  
Notes
2005-02-23 00:00:00TO "COMM" BD#50

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-03 Cont ID  
Sent By csiegber Date 2004-08-03 Time 15:23 Rev Time 0.00
Received By csiegber Date 2004-08-03 Time 15:23 Sent To  
Notes
2004-08-03 00:00:00TO COMM BD#38

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-07 Cont ID  
Sent By csiegber Date 2004-08-03 Time 15:22 Rev Time 0.00
Received By jwitmer Date 2005-05-27 Time 13:12 Sent To  
Notes
2004-04-30 00:00:00TO COMM BD#35

Review Stop M MECHANICAL (A/C)
Rev No 15 Status P Date 2007-04-25 Cont ID  
Sent By rregueir Date 2007-04-25 Time 17:50 Rev Time 0.00
Received By rregueir Date 2007-04-25 Time 17:50 Sent To PC
Notes
2007-04-25 17:52:49MECH REVISION PAGES M2.1A AND M2.5

Review Stop M MECHANICAL (A/C)
Rev No 14 Status N Date 2007-03-22 Cont ID  
Sent By rregueir Date 2007-03-22 Time 16:03 Rev Time 0.00
Received By rregueir Date 2007-03-22 Time 15:39 Sent To  
Notes
2007-03-22 16:03:52MECHANICAL PAGES SUBMITTED WITH THIS REVISION ARE
 OUT-DATED AS THEY HAVE BEEN SUPERCEDED BY OTHER SHEETS
 SUBMITTED AS MECHANICAL-ONLY REVISIONS. THESE PAGES ARE
 BEING RETURNED WITHOUT REVIEW.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 13 Status P Date 2007-03-19 Cont ID  
Sent By rregueir Date 2007-03-19 Time 10:14 Rev Time 0.00
Received By rregueir Date 2007-03-19 Time 09:59 Sent To  
Notes
2007-03-19 10:15:09REVISED PAGE M2.2 SUBMITTED 3/13/07 OK

Review Stop M MECHANICAL (A/C)
Rev No 12 Status P Date 2007-03-06 Cont ID  
Sent By rregueir Date 2007-03-06 Time 15:42 Rev Time 0.00
Received By rregueir Date 2007-03-06 Time 13:21 Sent To PC
Notes
2007-03-06 15:54:00REVISIONS SUBMITTED FOR PAGES M2.1A, M2.2, M2.3, M2.4,
 M2.5
  
 PG M2.2 DENIED: THE FIRE DAMPER EXCEPTION AS NOTED ON
 PLAN DOES NOT APPLY TO THIS PROJECT AS IT WAS PERMITTED
 UNDER FBC 2001. THE CODE SECTION CITED DOES NOT RELATE
 TO FBC,M 2001. PLEASE CORRECT AND RESUBMIT.
  
 PG M2.5 CITES THE SAME CODE SECTION. HOWEVER, THE FIRE
 DAMPERS IN QUESTION ARE INSTALLED AND SHOWN ON PLAN.
 SINCE THE EXCEPTION IS NOT BEING CLAIMED, THIS PAGE HAS
 PASSED REVIEW.
  
 ALL OTHER MECHANICAL PLAN REVIEW COMMENTS AND PROVISOS
 HAVE BEEN SATISFIED TO THIS POINT.
  
 RONALD J REGUEIRO
 561-805-6734
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 11 Status P Date 2007-02-13 Cont ID  
Sent By rregueir Date 2007-02-13 Time 13:53 Rev Time 0.00
Received By rregueir Date 2007-02-13 Time 09:12 Sent To  
Notes
2007-02-13 13:52:37PAGE M 2.5 - ELEVATOR LOBBY 1 AND 2, DUCT SIZE AND FIRE
 DAMPER MISSING. ONE SHEET IS MARKED TO SHOW LOCATIONS
 IN QUESTION. ALL OTHER PAGES ARE OK. PLEASE PROVIDE
 MISSING INFORMATION ON THIS PAGE AND RESUBMIT. FBC,M
 106.1.1.

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2007-02-01 Cont ID  
Sent By rregueir Date 2007-02-01 Time 10:06 Rev Time 0.00
Received By rregueir Date 2007-02-01 Time 10:06 Sent To PC
Notes
2007-02-01 10:15:11----------------PROVISO---------------------
  
 1. M2.2: 20X10 R/A ABOVE CEILING IN MAIN LOBBY, IF THIS
 DUCT WAS NOT INSTALLED IT SHOULD BE REMOVED FROM
 PLANS.
  
 2. M2.3 NORTHEAST LOBBY SHOWS TWO FIRE DAMPERS WHERE
 THERE IS NOT RATED BARRIER/PARTITION. THESE SHOULD BE
 REMOVED FROM PLANS.
  
 RONALD J REGUEIRO
 561-805-6734
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2007-01-11 Cont ID  
Sent By pkrauss Date 2007-01-11 Time 07:05 Rev Time 0.00
Received By pkrauss Date 2007-01-11 Time 07:05 Sent To  
Notes
2007-01-11 09:15:24PROVISO:
  
 1.PLEASE CLARIFY THE FOLLOWING; PLAN SHEET M2.1A NOTE
 INDICATES THE CO SENSORS ARE TO MOUNTED AT 96" AFF.
 PLEASE PROVIDE MANUFACTURER'S INSTALLATION INSTRUCTIONS
 FOR THE CO SENSORS.PLEASE NOTE, GARAGE VENTILATION IS
 DEPENDANT ON CO SENSORS ACTIVIATION, PLEASE CLARIFY HOW
 THIS WILL BE CODE COMPLIANT SHOULD THE BUILDING HAVE
 LOSS OF POWER.
  
 2. PLAN SHEET M2.1,VENTILATION TO THE MECHANICAL
 ROOM, PER 2001 FMC 401.5.1, MECHANICAL INTAKE OPENINGS
 SHALL BE LOCATED A MINIMUM OF 10FTFROM ANY HAZARDOUS
 OR NOXIOUS CONTAMINANT SUCH AS PARKING LOTS.
  
 3.PLEASE NOTE, RESPONSE OR REVISIONS GENERATED BY
 COMMENT 2 BY BUILDING PLANS EXAMINER, JIM WITMER MAY
 IMPACT THE NEED FOR DAMPERS AT RATED PARTITIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2007-01-03 Cont ID  
Sent By pkrauss Date 2007-01-03 Time 11:53 Rev Time 0.00
Received By pkrauss Date 2007-01-03 Time 11:43 Sent To  
Notes
2007-01-03 11:54:52REVISION / PLAN SHEET M5.1 / DUCT SIZE REVISION

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2006-12-04 Cont ID  
Sent By hmoser Date 2006-12-04 Time 15:07 Rev Time 0.00
Received By hmoser Date 2006-12-04 Time 15:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2006-09-06 Cont ID  
Sent By pkrauss Date 2006-09-06 Time 07:14 Rev Time 0.00
Received By pkrauss Date 2006-09-06 Time 07:14 Sent To  
Notes
2006-09-06 00:00:00PROVISO:
 THE FOLLOWING SHEETS NEED TO BE REVISED,
 DELETING THE HEAT EXCHANGER AND PUMPS 3
 & 4:M0.1, M2.6, M7.1, & M8.1.
  
 PLEASE NOTE:
 VARIANCE APPROVED NOVEMBER 18, 2004 WITH
 THE FOLLOWING CONDITIONS TO BE SET
 FORTH:
 1) OFFICE OPENINGS REDUCED TO 25.5% &
 EXPAND THE SPRINKLER SYSTEM TO
 INCLUDE SPRINKLER HEADS ON BOTH
 SIDES OF THE GLASS FILLED OPENINGS.
 2) GARAGE OPENINGS REDUCED TO 20% &
 EXPAND FIRE SPRINKLER SYSTEM TO
 HAVESPRINKLER HEAD OVER ALL
 OPENINGS
 3) ELEVATIONS HAVE BEEN CHANGED TO
 AESTHETICALLY IMPROVE THE
 APPEARANCE OF THE GARAGE BUILDING.
  
 PLEASE NOTE, THIS SHOULD ALSO INCLUDE
 ALL MECHANICAL OPENINGS, LOUVERS FOR
 EXHAUST & AIR INTAKES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2005-06-30 Cont ID  
Sent By pkrauss Date 2005-06-30 Time 14:37 Rev Time 0.55
Received By pkrauss Date 2005-06-30 Time 14:37 Sent To  
Notes
2005-06-30 00:00:00PROVISO:
 VARIANCE APPROVED NOVEMBER 18, 2004 WITH
 THE FOLLOWING CONDITIONS TO BE SET
 FORTH:
 1) OFFICE OPENINGS REDUCED TO 25.5% &
 EXPAND THE SPRINKLER SYSTEM TO
 INCLUDE SPRINKLER HEADS ON BOTH
 SIDES OF THE GLASS FILLED OPENINGS.
 2) GARAGE OPENINGS REDUCED TO 20% &
 EXPAND FIRE SPRINKLER SYSTEM TO
 HAVESPRINKLER HEAD OVER ALL
 OPENINGS
 3) ELEVATIONS HAVE BEEN CHANGED TO
 AESTHETICALLY IMPROVE THE
 APPEARANCE OF THE GARAGE BUILDING.
  
 PLEASE NOTE, THIS SHOULD ALSO INCLUDE
 ALL MECHANICAL OPENINGS, LOUVERS FOR
 EXHAUST & AIR INTAKES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2005-05-26 Cont ID  
Sent By pkrauss Date 2005-05-26 Time 09:05 Rev Time 0.55
Received By pkrauss Date 2005-05-25 Time 16:15 Sent To  
Notes
2005-05-26 00:00:00DENIED:
 1.PLAN INDICATES THE FIRST FLOOR LOBBY
 AREA OPEN TO THE SECOND FLOOR LOBBY AND
 EGRESS CORRIDOR.SHOW COMPLIANCE WITH
 2001 FBC 414 & 2001 FBC/ M 403.6.6.
 PROVIDE TOTAL CUBIC FEET CALCULATION FOR
 THE AREA IN QUESTION.
  
 PROVISO:
 VARIANCE APPROVED NOVEMBER 18, 2005 WITH
 THE FOLLOWING CONDITIONS TO BE SET
 FORTH:
 1) OFFICE OPENINGS REDUCED TO 25.5% &
 EXPAND THE FIRE SPRINKLER SYSTEM TO
 INCLUDE SPRINKLER HEADS ON BOTH
 SIDES OF THE GLASS FILLED OPENINGS
 2) GARAGE OPENINGS REDUCED TO 20% &
 EXPAND FIRE SPRINKLER SYSTEM TO HAVE
 SPRINKLER HEAD OVER ALL OPENINGS
 3) ELEVATIONS HAVE BEEN CHANGED TO
 AESTHETICALLY IMPROVE THE APPEARANCE
 OF THE GARAGE BUILDING.
  
 PLEASE NOTE, THIS SHOULD ALSO INCLUDE
 ALL MECHANICAL OPENINGS, LOUVERS FOR
 EXHAUST & AIR INTAKES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2005-03-25 Cont ID  
Sent By pkrauss Date 2005-03-25 Time 10:53 Rev Time 0.55
Received By pkrauss Date 2005-03-25 Time 10:11 Sent To  
Notes
2005-03-25 00:00:00DENIED:
 RESPONSE TO COMMENT FROM REVIEW DATED
 8-28-04:CONDENSATE INDICATED ON THE
 PLUMBING PLANS.REFERENCE COMMENTS BY
 KEN STEVENS, PLUMBING PLAN REVIEW;
 CONDENSATE AND STORM ARE INDICATED INTO
 THE SANITARY.
  
 2.PROVIDE PIPING MATERIAL FOR THE
 CONDENSER WATER PIPING.PLAN SHEET M0.2
 ONLY INDICATES PIPE MATERIAL FOR THE
 REFRIGERANT AND CONDENSATE PIPING.
  
 3.SEE COMMENT #6 BY JIM WITMER
 BUILDING PLAN REVIEW; VENTILATION FOR
 THE GARAGE.
  
 4.PLEASE NOTE, PLAN SHEET M2.1A
 INDICATES ENCLOSED GARAGE, PER 2001 FBC
 411.4.2 THE MECHANICAL SYSTEM SHALL BE
 CAPABLE OF PROVIDING AT LEAST 6 AIR
 CHANGES PER HOUR FOR EACH LEVEL.PLAN
 INDICATES EF-6 FOR THE EXHAUST BUT DOES
 NOT ADDRESS HOW THE AIR MAKE UP WILL BE
 ACHIEVED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-10-06 Cont ID  
Sent By pkrauss Date 2004-08-28 Time 10:40 Rev Time 2.00
Received By pkrauss Date 2004-08-28 Time 09:16 Sent To  
Notes
2004-08-28 00:00:00DENIED:
 REFERENCE COMMENT #3, CONDENSATE, PLEASE
 PROVIDE DETAIL, LAYOUT, & LINE SIZE.
 RESPONSE:SEE PLUMBING PLANS.
 PLEASE REFERENCE PLUMBING PLAN SHEET
 THAT REFLECTS THE CONDENSATE, AFTER
 FURTHER REVIEW I STILL DID NOT LOCATE
 CONDENSATE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-06-07 Cont ID  
Sent By pkrauss Date 2004-06-07 Time 15:06 Rev Time 0.50
Received By pkrauss Date 2004-06-07 Time 15:06 Sent To  
Notes
2004-06-07 00:00:00DENIED:
 ARCHITECTURAL PLANS ARE INCOMPLETE.
 PLEASE INDICATE RATING FOR CORRIDORS.
 DOOR SCHEDULE DOES NOT GIVE FIRE
 RESISTANCE RATING.
  
 1.PLEASE CLARIFY OUTSIDE AIR INTAKE.
 DUCTS THAT PENETRATE MORE THAN 1 FLOOR
 SHALL BE PROTECTED BY A SHAFT ENCLOSURE,
 PER 2001 FBC(M) 607.4. PROVIDE DETAIL
 FOR THE SHAFT ENCLOSURE AND INDICATE
 RATING OF THE ENCLOSURE.
  
 2.PLAN SHEET M2.3, 10" DUCT TO
 VAV-3-6 FIRE DAMPER IS NOT LOCATED AT
 THE WALL.
  
 3.INDICATE CONDENSATE, LINE SIZE,
 MATERIAL, LAYOUT AND TERMINATION PER
 2001 FBC(M) 307.2.1.
  
 4.PLAN SHEET M2.2 & M2.3, INDICATE
 AHU-2, PLANS DO NOT INDICATE AHU-3 AS
 LISTED ON THE EQUIPMENT SCHEDULE.
 PLEASE CLARIFY.
  
 5.PROVIDE CWS/R LINE SIZE ON PLAN
 SHEETS M2.2, M2.3, M2.4 & THROUGH PUMPS
 AND COOLING TOWER.
  
 6.PLAN SHEETS M2.3 & M2.4 M2,M4,M5
 DUCT PENETRATING SHAFT, MISSING FIRE
 DAMPERS.
  
 7.PLANS ARE NOT SIGNED, SEALED OR
 DATED AS REQUIRED PER FS 471.025 & FAC
 61G15-23.002.
  
 8.ENERGY CALCULATIONS ARE REQUIRED PER
 2001 FBC CHAPTER 13 SUB-CHAPTER 4
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 13 Status P Date 2007-05-03 Cont ID  
Sent By kstevens Date 2007-05-03 Time 09:22 Rev Time 0.00
Received By kstevens Date 2007-05-03 Time 09:22 Sent To  
Notes
2007-05-03 09:56:15AS BUILTS SHEETS P2.1A, P2.1B, P2.2A, P2.3A, P2.5A,
 P3.1A, P3.2A, P3.3A, P3.3B P3.5A, P5.1 & P6.1.--
 REVISIONS OK SHEETS P2.4A, P3.4A & P3.4B.

Review Stop P PLUMBING
Rev No 12 Status P Date 2007-03-21 Cont ID  
Sent By kstevens Date 2007-03-21 Time 18:30 Rev Time 0.00
Received By kstevens Date 2007-03-21 Time 18:30 Sent To  
Notes
2007-03-21 18:30:48REVISIONS OK - SHTS P2.1A, P2.1B, P5.1 & P6.1

Review Stop P PLUMBING
Rev No 11 Status P Date 2007-03-12 Cont ID  
Sent By kstevens Date 2007-03-12 Time 18:17 Rev Time 0.00
Received By kstevens Date 2007-03-12 Time 18:17 Sent To  
Notes
2007-03-12 18:18:43REVISIONS OK - SHTS P2.1B, P3.1B, P6.1 & P7.1

Review Stop P PLUMBING
Rev No 10 Status P Date 2007-03-05 Cont ID  
Sent By kstevens Date 2007-03-05 Time 11:56 Rev Time 0.00
Received By kstevens Date 2007-03-05 Time 11:56 Sent To  
Notes
2007-03-05 11:58:07REVISION OK - SHTS P2.2B, P2.3B, P2.4B & P7.1-
 REVISIONS REQUIRED FOR SHTS P2.5B & P2.6B TO REFLECT
 THE CHANGES ON THE RISER DIAGRAM.

Review Stop P PLUMBING
Rev No 9 Status P Date 2007-01-17 Cont ID  
Sent By kstevens Date 2007-01-17 Time 10:44 Rev Time 0.00
Received By kstevens Date 2007-01-17 Time 10:44 Sent To  
Notes
2007-01-17 10:51:01REVISIONS OK - SHTS P0.1, P2.2A, P2.3A, P2.5A, P3.1A,
 P3.2A, P3.3A & P3.5A.

Review Stop P PLUMBING
Rev No 8 Status F Date 2007-01-17 Cont ID  
Sent By kstevens Date 2007-01-17 Time 10:28 Rev Time 0.00
Received By kstevens Date 2007-01-17 Time 10:28 Sent To  
Notes
2007-01-17 10:44:37REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1. SHT P2.1A. THERE ARE MANY CHANGES NOT INDICATED AS
 REVISIONS. NO CLOUDS ARE INDICATED ON THE SHEET FOR
 THESE REVISIONS. REVISIONS 13, 19, & 20 ARE NOT SHOWN
 ON THE PLANS BUT ARE SHOWN ON THE REVISION LIST. PLEASE
 CLARIFY, AS THE LATEST APPROVED REVISION PRIOR TO THIS
 SUBMITTAL IS REVISION #5.
  
 2. SHT P2.1B. THERE ARE REVISIONS FOUND THAT WERE NOT
 CLOUDED NOR INDICATED AS REVISIONS. REVISION #14 WAS
 NOT FOUND. THE LATEST REVISION PRIOR TO THIS SUBMITTAL
 IS REVISION #12. PLEASE CLARIFY.
  
 3. SHT P5.1. THERE ARE MANY REVISIONS NOT CLOUDED NOR
 INDICATED AS REVISIONS. REVISIONS 13, 19 & 20 ON THE
 REVISION LIST WERE NOT FOUND ON THE PLANS. THE LAST
 APPROVED REVISION PRIOR TO THIS SUBMITTAL IS #5. PLEASE
 CLARIFY.-THE MOP SINK MOVED TO THE NEW LOCATION IN
 NOT VENTED. SECTION 901.2.1.
  
 4. SHT P6.1. THERE ARE REVISIONS NOT CLOUDED NOR
 INDICATED AS REVISIONS. SOME REVISIONS HAVE NOT BEEN
 FOUND ON THE PLANS. PLEASE CLARIFY.-THE WATER
 HAMMER ARRESTORS FOR THE MOP SINK IN THE NEW LOCATION
 AND FOR THE LAV NEAR THE CAFE SHALL BE LOCATED NEAR THE
 FIXTURE IN AN "EFFECTIVE RANGE", NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 7 Status P Date 2006-01-20 Cont ID  
Sent By pschmitz Date 2006-01-20 Time 14:13 Rev Time 0.00
Received By pschmitz Date 2006-01-20 Time 14:13 Sent To  
Notes
2006-01-20 00:00:00REVISION 01-09-06 APPROVED

Review Stop P PLUMBING
Rev No 6 Status F Date 2006-01-07 Cont ID  
Sent By pschmitz Date 2006-01-07 Time 14:59 Rev Time 0.00
Received By pschmitz Date 2006-01-07 Time 14:59 Sent To  
Notes
2006-01-07 00:00:00ADDING 6TH FLOOR, NO SUBMITTAL SHEET
 WITH PLANS.PES

Review Stop P PLUMBING
Rev No 5 Status P Date 2005-07-01 Cont ID  
Sent By kstevens Date 2005-07-01 Time 13:36 Rev Time 1.00
Received By kstevens Date 2005-07-01 Time 13:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2005-05-25 Cont ID  
Sent By kstevens Date 2005-05-25 Time 11:25 Rev Time 1.25
Received By kstevens Date 2005-05-25 Time 10:54 Sent To  
Notes
2005-05-25 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025 - THIS HAS BEEN POINTED OUT
 TO THE ENGINEER IN THE PAST AND IS STILL
 REQUIRED.
  
 2) SHTS P3.1A AND P61. THE WATER RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN
 AT COL. LINES B/X1 THRU A/X1. ALSO THE
 HOSE BIBB AT COL. LINE C/X3 IS NOT SHOWN
 ON THE RISER DIAGRAM. THIS COULD HAVE
 BEEN A PROVISO BUT SINCE THE PLANS WERE
 DENIED BY COMMENT #1 THIS CAN BE
 ADDRESSED AT THIS TIME.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2005-03-12 Cont ID  
Sent By kstevens Date 2005-03-12 Time 13:11 Rev Time 6.00
Received By kstevens Date 2005-03-12 Time 13:11 Sent To  
Notes
2005-03-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A) FROM PREVIOUS REVIEW: COMMENT NUMBERS
 SHALL STAY THE SAME TO AVOID CONFUSION.
 1) A TITLE BLOCK MUST APPEAR ON ALL
 ARCHITECTURAL DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE
 FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE
 NUMBER.
 IF THE FIRM NAME IS A CORP., PARTNERSHIP
 OR A FICITIOUS NAME A CERTIFICATE OF
 AUTHORIZATION IS REQUIRED. 61G1-16.004 &
 FS 481.219 FS 481.2055 - NO RESPONSE
 NOTED.
 3) DRINKING FOUNTAINS ARE REQUIRED PER
 TABLE 403.1. RESPONSE NOTED, BUT IF THIS
 IS A NEW BUILDING THEN HOW CAN THERE BE
 EXISTING DRINKING FOUNTAINS? NO DRINKING
 FOUNTAINS ARE SHOWN ON THE FLOOR PLAN OR
 THE SANT. RISER DIAGRAM.
 4) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE FOR GREASE INTERCEPTOR. WASTE
 ORD #2938-96. (561) 837-4074. RESPONSE
 NOTED, BUT THIS IS NOT A PERMIT ISSUE.
 THIS IS TO SEE IF A GREASE INTERCEPTOR
 WILL BE REQUIRED, AND IF ONE IS A GREASE
 LINE CAN BE BROUGHT INTO THE BUILDING
 NOW RATHER THAN TEARING UP THE FLOOR IN
 THE FUTURE.
 *********NEW COMMENTS SOME BECAUSE OF
 CHANGES IN THE PLANS OR NEW SHEETS******
 1B) SHT P2.1 LABELED AS SANITARY, BUT
 HAS STORM AND CONDENSATE ALSO. - STORM
 LINE AT COL. LINE B?X9 DOES NOT REFLECT
 THE RISER ON SHT P7.1. RISER DIAGRAM
 SHOWS 2 STORM RISERS, BUT FLOOR PLAN
 SHOWS ONLY ONE. PLEASE CORRELATE FLOOR
 PLAN AND RISER DIAGRAM.
 2B) SHTS P2.1A & P5.1 FLOOR DRAIN IN
 PUMP NOT VENTED. SECTION 901.2.1.
 3B) SHTS P2.1A & P5.1 PIPING UPSTREAM OF
 THE PUMP ROOM FLOOR DRAINS, THE FLOOR
 PLAN AND RISER DIAGRAM DO NOT REFLECT
 EACH OTHER. FLOOR PLAN SHOWS 6" PIPING
 AND THE RISER DIAGRAM SHOWS 8" PLEASE
 CORRELATE. SECTION 104.2.1.
 4B) SHTS P2.1A & P5.1 SANT. RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 THE COFFEE SHOP IN NOT ON THE RISER
 DIAGRAM. PLEASE CORRELATE. SECTION
 104.2.1.
 5B) SHTS P2.1B & P5.1 SANT. RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 SANT. RISER DIAGRAM SHOWS 4" TO THE
 TICKED BOOTH AND THE FLOOR PLAN SHOWS
 6". PLEASE CLARIFY. SECTION 104.2.1.
 6B) SHTS P2.2B, P2.3B SHOW STORM DRAINS
 AS FLOOR DRAINS ON THE FLOOR PLAN, BUT
 ARE SHOWN AS DECK DRAINS ON THE STORM
 RISER SHT P7.1. PLEASE CORRELATE/CLARIFY
 SECTION 104.2.1.
 7B) SHTS P2.2B, P2.3B, P2.4B & P2.5B ARE
 LABELED AS SANITARY FLOOR PLANS, BUT THE
 INFORMATION IS FOR STORM DRAINAGE.
 PLEASE CLARIFY. SECTION 104.2.1.
 8B) SHTS P2.5B & P7.1 DO NOT REFLECT
 EACH OTHER. STORM RISER DIAGRAM DOES NOT
 SHOW 2" PLANTER DRAIN LINE. PLEASE
 CORRELATE SHEETS. SECTION 104.2.1.
 9B) SHT P5.1 STACKS FOR LAVS NOT SIZED
 CORRECTLY. MAXIMUM 10 DFU'S ON 2" STACK
 WITH 3 BRANCH INTERVALS OR LESS. 18 DFU
 SHOWN. TABLE 710.1(2).
 10B) SHTS P3.19 & P6.1 FULL OPEN VALVES
 REQUIRED ON THE WATER DISTRIBUTION
 SUPPLY PIPE AT THE ENTRANCE INTO THE
 STRUCTURE, SECTION 606.1(2), AND ON THE
 TOP OF EVERY WATER DOWN-FEED PIPE,
 SECTION 606.1(4).
 11B) SHT P6.1 WATER LINE TO TICKET BOOTH
 NOT SHOWN ON THE WATER RISER DIAGRAM. -
 WATER LINE BY COL. X7 NOT SHOWN ON THE
 WATER RISER DIAGRAM. -DOES NOT REFLECT
 THE WATER PIPING SHOWN ON SHT P3.1A BY
 COL. LINES B/X1!!! THRU A"/X1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-08-26 Cont ID  
Sent By kstevens Date 2004-08-26 Time 16:50 Rev Time 7.00
Received By kstevens Date 2004-08-26 Time 16:50 Sent To  
Notes
2004-08-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) FAC 61G1-16.004(2) FIRM LICENSE NUM-
 BER REQUIRED. FS 481.025
 2) DPBR STAMPS AND WORKSHEETS FOR CAFE
 TO BE SUBMITTED AT TIME OF PERMIT APPLI-
 CATION. RESPONSE NOTED.
 3) DRINKING FOUNTAIN REQUIRED PER TABLE
 403.1
 4) FROM PREVIOUS REVIEW: CONTACT RODNEY
 COMPO, ENVIRONMENTAL COMPLIANCE FOR SIZ-
 ING OF GREASE INTERCEPTOR. WASTE ORDIN.
 2938-96. (561) 837-4074. NO RESPONSE NO-
 TED.
 5) FROM PREVIOUS REVIEW: SHTS P2.1A AND
 P2.1B NOT SANITARY PIPING SHOWN FOR THE
 TOILET ROOM IN THE CAFE OR THE TICKET
 BOOTH. INDICATE HOW THESE WILL BE PIPED.
 SHOW PIPE SIZE AND VENTING.
 6) SHTS P2.1A & P7.1 INDICATE EXISTING
 PIPING. PLEASE CLARIFY.
 7) FROM PREVIOUS REVIEW: SHT P2.6 HOW
 UPPER ROOFS SHALL BE DRAINED. SHOW CALC-
 ULATIONS FOR ROOF AREAS BETWEEN COLS. X5
 AND X8. SHOW 1/2 AREA OF ALL VERTICAL
 WALLS AND AREA OF ROOF ABOVE DRAINING ON
 TO ROOF AREAS ADDED TO CALCULATIONS.
 SECTIONS 1106 & 1107 AND ALL SUBSECTIONS
 RESPONSE NOTED, BUT NO CALCULATIONS WERE
 FOUND.
 8) FROM PREVIOUS REVIEW: SHTS P3.1A,
 P3.4A, & P3.5A NO WATER SHOWN TO TOILET
 ROOMS IN CAFE OR THE TICKET BOOTH. SECT-
 ION 104.2.1
 9) STORM FOR THE PARKING GARAGE SHOWS
 ONLY ONE ROOF DRAIN. INDICATE HOW THE
 RAIN WATER WILL BE DRAINED BY ONE ROOF
 DRAIN. SUBMIT CALCULATIONS FOR THE PARK-
 ING GARAGE SHOWING SQUARE FOOTAGE AND
 1/2 AREA OF ALL VERTICAL WALLS ADDED TO
 THE SF AREA OF THE ROOF. INDICATE HOW
 THE RAIN WATER FROM THE RAMP FROM THE
 5TH FLOOR TO THE 4TH FLOOR WILL BE
 DRAINED. - WHAT WILL THE CATCH BASIN AT
 THE NORTH END OF THE PARKING GARAGE
 DRAIN? SECTION 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-04 Cont ID  
Sent By kstevens Date 2004-06-04 Time 13:58 Rev Time 6.50
Received By kstevens Date 2004-06-03 Time 18:24 Sent To  
Notes
2004-06-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
  
  
 1) SECTION 104.2.2 OFFICIAL SEAL SHALL
 BE AFFIXED TO PLANS WITH SIGNATURE, DATE
 AND TITLE BLOCK.
 2) SHT A.00.03 SITE CALCULATIONS FOR
 MINIMUM FIXTURES PER TABLES 1003.1 AND
 403.1. SHOW GROSS AREA FOR BANK AND CAFE
 ON THE FIRST FLOOR, AND FOR OFFICE SPACE
 ON 2ND THRU 5TH FLOORS.
 3) PLANS SHALL BE ROUTED TO DBPR HOTEL &
 RESTURANT DIVISION FOR REVIEW. PLANS
 SHALL BE STAMPED AND WORKSHEETS ATTACHED
 TO EACH SET OF PLANS PRIOR TO RESUBMITT-
 ING FOR REVIEW WITH WPB. 101.4.7
 4) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE FOR SIZING OF GREASE INTER-
 CEPTOR. WASTE ORD. 2938-96. PHONE NUMBER
 (561) 837-4074.
 5) SHT A.71.02 MENS/WOMENS 2ND THRU 5TH
 FLOOR PLAN FOR TOILET ROOMS. SHOW 5'
 TURNING AREA IN TOILET ROOM, NOT IN THE
 STALL.
 6) SHT A.71.02 SHOW TURNING AREA FOR
 TOILET AREA FOR TOILET ROOM WITH ELEVAT-
 ION INDICATORS 7 & 8.
 7) SHT A.71.02 SHOW MEASURMENT FROM CEN-
 TER OF WATER CLOSET TO WALL FOR EACH
 ACCESSIBLE W/C PER FIGURES 30 & 30E. -
 SHOW MEASUREMENT FROM CENTER OF ACCESSI-
 BLE LAVS TO WALL. MIN. 15".104.2.1
 8) SHT P2.1A NO SANT. SHOWN FOR CAFE OR
 TOILET ROOMS FOR BACK. PLEASE CLARIFY
 SECTION 104.2.1
 9) SHT 2.1B NO SANT. SHOWN FOR TOILET
 ROOM IN TICKET BOOTH. PLEASE CLARIFY.
 SECTION 104.2.1
 10) SHT P2.2A SANT; PIPING SHOW BETWEEN
 COLS. X5 & X6 OUTSIDE BLDG FOOTPRINT.
 PLEASE CLARIFY. SECTION 104.2.1
 11) SHT P2.6 ROOF PLAN, INDICATE HOW UP-
 PER ROOFS SHALL BE DRAINED. SHOW CLACUL-
 ATIONS FOR ROOF AREAS BETWEEN COLS. X5
 AND X8. SHOW 1/2 AREA OF ALL VERTICAL
 WALLS AND AREA OF ROOF ABOVE DRAINING ON
 TO ROOF AREAS ADDED TO CALCULATIONS.
 SECTIONS 1106 & 1107 AND ALL SUBSECTIONS
 12) SHOW LOCATION OF SECONDARY ROOF
 DRAINS. SHOW PIPING OF SECONDARY ROOF
 DRAINS WITH ALL PIPE SIZES SHOWN. SECT-
 ION 1107.
 13) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE BLDG. SECTION 608.
 13.2
 14) SHTS P3.1A, P3.4A, & P3.5A NO WATER
 SHOWN TO TOILET ROOMS. PLEASE CLARIFY
 SECTION 104.2.1
 15) NO STORM PIPING SHOWN TO THE PARKING
 GARAGE. PLEASE CLARIFY.
 16) SHT P5.1 SANITARY ISOMETRIC DIAGRAM
 INDICATE DFU'S AT THE BASE OF EACH STACK
 AND SHOW DFU'S AS THEY ACCUMULATE IN THE
 SYSTEM. TABLE 710.1
 17) SHT P5.1 SECTION 903.4 THE VENT
 STACK SHALL CONNECT AT OR BELOW THE LOW-
 EST HORIZONTAL BRANCH.
 18) SHT P5.1 SANT RISER DOES NOT REFLECT
 THE FLOOR PLAN ON SHTS P2.2A, P2.3A,
 P2.4A, & P2.5A. EXTRA FLOOR DRAINS ARE
 ON RISER PAST LAVS IN MENS TOILET ROOM.
 - FLOOR PLAN SHOWS 1 RISER TO LAVS AT
 THE SIDE WALL OF THE LAVS AND PIPES THRU
 THE WALL IN 2" PIPE FOR ALL THREE LAVS.
 ON THE RISER IT SHOWS 2 RISERS, ONE
 PICKS UP 2 LAVS AND THE OTHER RISER
 PICKS UP 1 LAV. PLEASE CLARIFY, CORREL-
 ATE PLANS. SECTION 104.2.1
 19) SHT P6.1 WATER HAMMER ARRESTORS ON
 THE ISOMETRIC DIAGRAM SHALL BE LOCATED
 NEAR THE FIXTURES, NOT IN THE CEILING.
 PDI-WH 201 & MANUF. INSTALL. INSTRUCTION
 20) SUBMIT INFORMATION & RISER DIAGRAM
 FOR BUILDING STORM DRAIN AND RISERS.
 SHOW PIPE SIZE AND SQUARE FOOTAGE AS IT
 ACCUMULATES IN SYSTEM. SHOW TERMINATION
 OF SYSTEM. SECTION 104.2.1
 21) PLANS DO NOT SEEM TO BE COMPLETE.
 MORE COMMENTS MAY FOLLOW ON NEXT REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 10 Status P Date 2007-05-07 Cont ID  
Sent By mflis Date 2007-05-07 Time 11:02 Rev Time 0.00
Received By mflis Date 2007-05-07 Time 11:02 Sent To  
Notes
2007-05-07 11:02:49ZONING REVIEW: PASSED
  
 - REVISION 17 - REVIEWED MODIFICATIONS TO PLANTER
 LOCATIONS
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 9 Status P Date 2007-01-17 Cont ID  
Sent By aaponte Date 2007-01-17 Time 16:27 Rev Time 0.00
Received By aaponte Date 2007-01-17 Time 16:27 Sent To  
Notes
2007-01-17 16:26:58APPROVAL FOR THE CHANGES ON THE CURB TYPE INSTALL IN
 FRONT OF THE PEDESTRIAN ACCESS ALONG RAILROAD AVE.
 DRAWINGS WERE REVIEWED AND OK. BY DEAN LAUDERMILK.

Review Stop Z ZONING
Rev No 8 Status N Date 2006-08-09 Cont ID  
Sent By aaponte Date 2006-08-09 Time 16:38 Rev Time 0.00
Received By aaponte Date 2006-08-09 Time 16:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 7 Status P Date 2006-01-03 Cont ID  
Sent By mflis Date 2006-01-03 Time 13:44 Rev Time 0.00
Received By mflis Date 2006-01-03 Time 13:44 Sent To  
Notes
2006-01-03 00:00:00REVIEW 6TH FLOOR ADD. PARKING LEVEL. TO
 COMPLY WITH PREVIOUS REVIEW (3) PROVISO
 ITEMS. -MJF

Review Stop Z ZONING
Rev No 6 Status P Date 2005-12-12 Cont ID  
Sent By mflis Date 2005-12-12 Time 14:48 Rev Time 0.00
Received By mflis Date 2005-12-12 Time 14:48 Sent To  
Notes
2005-12-12 00:00:00REVIEW OF (3) PROVISO ITEMS PER PREVIOUS
 URBAN DESIGN REVIEW - MJF

Review Stop Z ZONING
Rev No 5 Status P Date 2005-09-01 Cont ID  
Sent By aaponte Date 2005-09-01 Time 15:43 Rev Time 0.00
Received By aaponte Date 2005-09-01 Time 15:43 Sent To  
Notes
2005-09-01 00:00:00PROVISO:
 1. LOADING DOCK SHALL BE RELOCATED
 INSIDE THE PARKING GARAGE.
 2. RAMPS AND HAND RAIL SHALL BE REMOVED
 FROM THE RAILROAD AVENUE SIDEWALK.
 3. SHADE TREES SHALL BE PLANTED ALONG
 RAILROAD AVENUE.

Review Stop Z ZONING
Rev No 4 Status F Date 2005-07-06 Cont ID  
Sent By aaponte Date 2005-07-05 Time 16:47 Rev Time 0.00
Received By aaponte Date 2005-07-05 Time 16:47 Sent To  
Notes
2005-07-06 00:00:001. HAND RAIL ON RAILROAD AVENUE IS NOT
 PERMITTED.
 2. SIDEWALK SHALL BE A MINIMUM OF 8'
 WIDE AND CLEAR, ACCESS RAMPS ARE NOT
 ALLOWED ON THE SIDEWALK.
 3. PLEASE PROVIDE TWO ADDITIONAL SHADE
 TREES ALONG 3RD STREET. SUGGESTED
 SPECIE:DAHOON HOLY.
 4. PLEASE PROVIDE SHADE TREET ALONG WEST
 RAILROAD AVENUE. SHADE TREES SHALL BE
 PLANTED WITH A REGULAR SPACING NO
 GREATER THAN 40 FEET.RECOMMENDED SPECIE:
 DAHOON HOLY. PALMS CAN BE PLANTED
 BETWEEN TREES. PLANTING AREA MUST BE AT
 LEAST 4 FEET WIDE.
 5. LOADING DOCK MUST PROVIDE ITS OWN
 MANEUVER AREA. TRUCKS ARE NOT ALLOWED TO
 BACK UP ON THE ROW.
 6. PARKING ENTRANCE MUST PROVIDE SPACE
 TO STACK AT LEAST THREE CARS BEFORE
 GATES.
 7. SOUTH ELEVATION ARCHITECTURAL STYLE
 IS NOT CONSISTENT WITH THE EAST AND WEST
 ELEVATIONS.
 8.DRAWING SCALE ON SHEET A.62.01 IS
 WRONG.

Review Stop Z ZONING
Rev No 3 Status F Date 2005-06-06 Cont ID  
Sent By aaponte Date 2005-06-06 Time 11:17 Rev Time 0.00
Received By aaponte Date 2005-06-06 Time 11:17 Sent To  
Notes
2005-06-06 00:00:001. HAND RAIL ON RAILROAD AVENUE IS NOT
 PERMITTED.
 2. SIDEWALK SHALL BE A MINIMUM OF 8'
 WIDE AND CLEAR. ACCESS RAMPS ARE NOT
 ALLOWED ON THE SIDEWALK.
 3. PLEASE SUBMITT LANDSCAPE DRAWINGS TO
 CONFIRM COMPLIANCE WITH THE REGULATION.
 4. STREET TREES SHALL BE INSTALLED IN
 THE SIDEWALK ADJACENT TO THE CURB ALONG
 THE FRONTAGE LINE.
 5. SOUTH ELEVATION ARCHITECTURAL STYLE
 IS NOT CONSISTENT WITH THE EAST AND WEST
 ELEVATIONS.

Review Stop Z ZONING
Rev No 2 Status F Date 2004-08-18 Cont ID  
Sent By agiannio Date 2004-08-18 Time 09:42 Rev Time 2.00
Received By agiannio Date 2004-08-18 Time 09:42 Sent To  
Notes
2004-08-18 00:00:001.PROPOSED BUILDING DOES NOT MEET THE
 SPIRIT AND INTENT OF THE DMP.
 2.PEDESTRIAN BRIDGE REQUIRES CITY COM.
 APPROVAL OF AN AIR RIGHTS EASEMENT.
 3. 94-107(D)(4) ACCESS FROM ELEVATORS
 DOES NOT ALLOW ENTRY TO THE PARKING
 FROM THE STREET
 4. 94-107(E)(1) CONFIRM TINTING LEVELS
 AND COLOR OF GLASS
 5. 94-107(E)(4) PLEASE INDICATE THE
 OPENINGS ON THE PARKING GARAGE ELEVATION
 MORE CLEARLY.PROVIDE CALCULATIONS TO
 DEMONSTRATE COMPLIANCES WITH THE 45% MAX
 OPENINGS ON ELEVATIONS.
 6.LANDSCAPE INFORMATION NOT INCLUDED.
 SECTION 94-107(G) REQUIRES STREET TREES
 AND LANDSCAPE UNITS.PLEASE PROVIDE
 PLANTING & IRRIGATION DETAILS INCLUDING
 GRADING & TREE VAULT DETAILS.PLEASE
 PROVIDE DETAILS FOR PROPOSED WIDOW BOXES
 ON PARKING GARAGE.

Review Stop Z ZONING
Rev No 1 Status F Date 2004-08-18 Cont ID  
Sent By btrobaug Date 2004-05-13 Time 09:33 Rev Time 0.00
Received By agiannio Date 2004-05-25 Time 15:48 Sent To  
Notes
2004-05-25 00:00:00PROPOSED BUILDING DOES NOT MEET THE
 SPIRIT AND INTENT OF THE DOWNTOWN MASTER
 PLAN - GOAL TO PROVIDE CONNECTIVITY FROM
 NW NEIGHBORHOOD TO REST OF CITY.ALSO:
 1) PEDESTRIAN BRIDGE REQUIRES CITY COM.
 APPROVAL BY RESOLUTION.PLANNING WILL
 NOT SUPPORT.
 2)CANTILEVERED CANOPY & OTHER ELEMENTS
 THAT OVERHAND THE ROW REQUIRE CITY COM.
 APPROVAL BY RESOLUTION.PLANNING WILL
 NOT SUPPORT.
 3) 94-107(B)(6) CAFE DOOR MUST BE ON
 FRONTAGE LINE
 4) 94-107(B)(7) CONFIRM THAT 8FT. MIN.
 FOR SIDEWALK IS PROVIDED AND THAT ON-
 STREET PARKING IS FEASIBLE.
 5) 94-107(D)(4) ACCESS FROM ELEVATORS
 DOES NOT ALLW ENTRY TO THE PARKING
 GARAGE FROM THE FRONTAGE LINE
 6) 94-107(E)(1) CONFIRM TINTING LEVELS A
 ND COLOR OF GLASS
 7) 94-107(E)(4) ELEVATIONS OF PARKING
 GARAGE ARE ILLEGIBLE - PLEASE INDICATE
 MORE CLEARLY THE OPENINGS ON THE FACADES
 AND PROVIDE CALCULATIONS TO DEMONSTRATE
 COMPLIANCE WITH 45% MAX.