Plan Review Details - Permit 04041895
Plan Review Stops For Permit 04041895
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-06-25 Cont ID  
Sent By jwitmer Date 2004-06-25 Time 09:09 Rev Time 1.50
Received By jwitmer Date 2004-06-25 Time 09:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-05-17 Cont ID  
Sent By jwitmer Date 2004-05-17 Time 08:29 Rev Time 1.22
Received By jwitmer Date 2004-05-17 Time 08:29 Sent To PC
Notes
2004-05-17 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04041895
 ADD: 222 LAKEVIEW AV
 CONT: HEDRICK BROTHERS
 TEL: (561)718-8341
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEETSA1.3 INDICATE VARIOUS SOFFITS
 BUT NO DETAIL AS TO WHAT MATERIAL THEY
 SOFFITS ARE FASTENED TO NOR THE FASTENER
  
 2) DOOR# 1 DOES NOT INDICATE WHAT THE
 FIRE RATING IS PROVIDE IF FOR EXISTING
 DOORS?
  
 3) DOOR #18 & 19 DO NOT PROVIDE WHAT THE
 FIRE RESISTANCE RATING IS?
  
 4) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 5)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 6) TYPE I/ II BUILDINGS WOOD IN PARTI-
 TIONS BLOCKING, BACKING MUST BE FIRE
 RETARDANT TREATED WOOD, 609.1.2.
  
 7) KITHEN ELEVATION, 11-4.24.4 SINK
 HEIGHT. SINKS SHALL BE MOUNTED WITH THE
 COUNTER OR RIM NO HIGHER THAN 34INCHES.
  
 8) PROVIDE FIRE SPRINKLER PLANS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-11-03 Cont ID  
Sent By dpalmer Date 2004-11-03 Time 09:49 Rev Time 0.75
Received By dpalmer Date 2004-11-03 Time 08:53 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-06-22 Cont ID  
Sent By csiegber Date 2004-10-28 Time 11:40 Rev Time 1.00
Received By dpalmer Date 2004-06-22 Time 08:56 Sent To  
Notes
2004-06-22 00:00:00*** NOTE ***
  
 PLANS ARE REQUIRED TO HAVE COMPLETE
 ADDRESS ON TITLE BLOCK. FAC 61G15-23.002
 THIS HAS BEEN HANDWRITTEN ON PLANS.
 PLEASE ADJUST FOR FUTURE PROJECTS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-28 Cont ID  
Sent By dpalmer Date 2004-04-28 Time 05:14 Rev Time 0.75
Received By dpalmer Date 2004-04-28 Time 05:07 Sent To  
Notes
2004-04-28 00:00:00********** UNSAT ***********
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANEL SCHEDULES SUBMITTED.
 PANEL 17LA IS SHOWN ON SCHEDULES BUT
 NOT ON RISER?
 PANEL 17L INDICATES 225A MCB ON RISER
 YET BLANKS FOR MLO/MCB ARE SHOWN ON
 SCHEDULE?
  
 2)NOTE" PLEASE CLARIFY REQ'D EQUIPMENT
 GROUNDING CONDUCTOR TO AND FROM TRANS-
 -FORMER.? 250.30, 250.110 ETC.
 PLEASE ALSO CLARIFY METHOD OF EQUIPMENT
 GRNDS FOR OTHER FEEDS.
  
 3)NOTE: PLEASE CLARIFY LOCATION OF ALL
 EELECTRICAL EQUIPMENT SHOWN. PANELS?
 TRANSFORMER ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-11-08 Cont ID  
Sent By nmccray Date 2004-11-08 Time 11:38 Rev Time 0.00
Received By nmccray Date 2004-11-08 Time 11:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-06-29 Cont ID  
Sent By mcarsill Date 2004-04-28 Time 10:32 Rev Time 0.00
Received By mcarsill Date 2004-04-28 Time 10:32 Sent To  
Notes
2004-04-28 00:00:001) DEMOLITION, RENOVATION AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) SEPARATE PLANS AND PERMITS
 REQUIRED FOR FIRE ALARM SYSTEM REMODEL.
  
 3) SEPARATE PLANS AND PERMIT REQUIRED
 FOR FIRE SPRINKLER REMODEL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-10-28 Cont ID  
Sent By csiegber Date 2004-10-28 Time 11:40 Rev Time 0.00
Received By csiegber Date 2004-10-28 Time 11:40 Sent To E
Notes
2004-10-28 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-28 Cont ID  
Sent By csiegber Date 2004-10-28 Time 11:39 Rev Time 0.00
Received By csiegber Date 2004-10-28 Time 11:39 Sent To M
Notes
2004-10-28 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-08-26 Cont ID  
Sent By csiegber Date 2004-08-26 Time 15:16 Rev Time 0.00
Received By csiegber Date 2004-08-26 Time 15:16 Sent To E
Notes
2004-08-26 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-18 Cont ID  
Sent By csiegber Date 2004-06-18 Time 14:48 Rev Time 0.00
Received By csiegber Date 2004-06-18 Time 14:48 Sent To  
Notes
2004-06-18 00:00:00TO COMM BD#32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-17 Cont ID  
Sent By jwitmer Date 2004-05-17 Time 09:05 Rev Time 0.00
Received By jwitmer Date 2004-04-27 Time 16:21 Sent To PC
Notes
2004-04-27 00:00:00TO COMM BD#6

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-11-22 Cont ID  
Sent By pkrauss Date 2004-11-22 Time 17:06 Rev Time 0.35
Received By pkrauss Date 2004-11-22 Time 16:58 Sent To  
Notes
2004-11-22 00:00:00REVISION SUBMITTED 10-28-04 / JOB CO
 DATED 11-12-04.REVISION APPROVED

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-07-02 Cont ID  
Sent By csiegber Date 2004-10-28 Time 11:39 Rev Time 0.40
Received By pkrauss Date 2004-07-02 Time 11:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-05-14 Cont ID  
Sent By pkrauss Date 2004-05-14 Time 16:24 Rev Time 0.45
Received By pkrauss Date 2004-05-14 Time 16:24 Sent To  
Notes
2004-05-14 00:00:00APPROVED/STAMPED 5-6-04

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-07-03 Cont ID  
Sent By kstevens Date 2004-07-03 Time 15:19 Rev Time 1.00
Received By kstevens Date 2004-07-03 Time 15:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-05-14 Cont ID  
Sent By kstevens Date 2004-05-14 Time 16:12 Rev Time 1.50
Received By kstevens Date 2004-05-14 Time 16:11 Sent To  
Notes
2004-05-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 11
  
 1) SHT A1.2 A DRINKING FOUNTAIN IS REQ-
 UIRED PER TABLE 403.1. ALSO SEE SECTION
 410.1
 2) SHT A1.2 SINKS SHALL COMPLY WITH SEC.
 11-4.24 AND ALL SUBSECTIONS. SHOW CLEAR
 FLOOR SPACE, HEIGHT, KNEE CLEARANCE, EX-
 POSED PIPES AND SURFACES ECT.
 3) SHT P-1 FLOOR DRAINS ARE NOT APPROVED
 FOR INDIRECT WASTE. SEE SECTIONS 802.3
 AND 802.3.2.
 4) SHT P-1 SUBMIT CALCULATIONS FOR POINT
 LOADING OF BOTTON CHORD OF THE BAR JOIST
 AT WATER HEATER. INDICATE WHERE THE LOAD
 IS BEING TRANSFERRED TO. SECTION 1614.2.
 1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]