Plan Review Stops For Permit 04041895 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2004-06-25 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2004-06-25 |
Time |
09:09 |
Rev Time |
1.50 |
Received By |
jwitmer |
Date |
2004-06-25 |
Time |
09:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2004-05-17 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2004-05-17 |
Time |
08:29 |
Rev Time |
1.22 |
Received By |
jwitmer |
Date |
2004-05-17 |
Time |
08:29 |
Sent To |
PC |
|
Notes |
2004-05-17 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 04041895 | | ADD: 222 LAKEVIEW AV | | CONT: HEDRICK BROTHERS | | TEL: (561)718-8341 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | 1ST REVIEW | | ACTION: DENIED | | | | 1) SHEETSA1.3 INDICATE VARIOUS SOFFITS | | BUT NO DETAIL AS TO WHAT MATERIAL THEY | | SOFFITS ARE FASTENED TO NOR THE FASTENER | | | | 2) DOOR# 1 DOES NOT INDICATE WHAT THE | | FIRE RATING IS PROVIDE IF FOR EXISTING | | DOORS? | | | | 3) DOOR #18 & 19 DO NOT PROVIDE WHAT THE | | FIRE RESISTANCE RATING IS? | | | | 4) TABLE 803.3 MINIMUM INTERIOR FINISH | | CLASSIFICATION; PROVIDE INFORMATION | | BASED ON INTERIOR FINISH REQUIREMENTS | | BASED ON OCCUPANCY | | | | 5)704.2.1.4 CORRIDOR PARTITIONS, SMOKE | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | ITIONS, EXIT ENCLOSURES, AND FIRE | | RATED WALLS REQUIRED TO HAVE PROTECTED | | OPENINGS SHALL BE EFFECTIVELY AND | | PERMANETLY IDENTIFIED WITH SIGNS OR | | STENCILING IN A MANNER ACCEPTABLE TO THE | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | CEILING CEILING AND IN CONCEALED SPACES. | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | PROTECT ALL OPENINGS". | | | | 6) TYPE I/ II BUILDINGS WOOD IN PARTI- | | TIONS BLOCKING, BACKING MUST BE FIRE | | RETARDANT TREATED WOOD, 609.1.2. | | | | 7) KITHEN ELEVATION, 11-4.24.4 SINK | | HEIGHT. SINKS SHALL BE MOUNTED WITH THE | | COUNTER OR RIM NO HIGHER THAN 34INCHES. | | | | 8) PROVIDE FIRE SPRINKLER PLANS. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2004-11-03 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-11-03 |
Time |
09:49 |
Rev Time |
0.75 |
Received By |
dpalmer |
Date |
2004-11-03 |
Time |
08:53 |
Sent To |
FIRE |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2004-06-22 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-10-28 |
Time |
11:40 |
Rev Time |
1.00 |
Received By |
dpalmer |
Date |
2004-06-22 |
Time |
08:56 |
Sent To |
|
|
Notes |
2004-06-22 00:00:00 | *** NOTE *** | | | | PLANS ARE REQUIRED TO HAVE COMPLETE | | ADDRESS ON TITLE BLOCK. FAC 61G15-23.002 | | THIS HAS BEEN HANDWRITTEN ON PLANS. | | PLEASE ADJUST FOR FUTURE PROJECTS. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2004-04-28 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-04-28 |
Time |
05:14 |
Rev Time |
0.75 |
Received By |
dpalmer |
Date |
2004-04-28 |
Time |
05:07 |
Sent To |
|
|
Notes |
2004-04-28 00:00:00 | ********** UNSAT *********** | | | | 1)NOTE: PLEASE CORRELATE RISER DIAGRAM | | AND PANEL SCHEDULES SUBMITTED. | | PANEL 17LA IS SHOWN ON SCHEDULES BUT | | NOT ON RISER? | | PANEL 17L INDICATES 225A MCB ON RISER | | YET BLANKS FOR MLO/MCB ARE SHOWN ON | | SCHEDULE? | | | | 2)NOTE" PLEASE CLARIFY REQ'D EQUIPMENT | | GROUNDING CONDUCTOR TO AND FROM TRANS- | | -FORMER.? 250.30, 250.110 ETC. | | PLEASE ALSO CLARIFY METHOD OF EQUIPMENT | | GRNDS FOR OTHER FEEDS. | | | | 3)NOTE: PLEASE CLARIFY LOCATION OF ALL | | EELECTRICAL EQUIPMENT SHOWN. PANELS? | | TRANSFORMER ETC. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2004-11-08 |
|
|
Cont ID |
|
Sent By |
nmccray |
Date |
2004-11-08 |
Time |
11:38 |
Rev Time |
0.00 |
Received By |
nmccray |
Date |
2004-11-08 |
Time |
11:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2004-06-29 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2004-04-28 |
Time |
10:32 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2004-04-28 |
Time |
10:32 |
Sent To |
|
|
Notes |
2004-04-28 00:00:00 | 1) DEMOLITION, RENOVATION AND | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | 2) SEPARATE PLANS AND PERMITS | | REQUIRED FOR FIRE ALARM SYSTEM REMODEL. | | | | 3) SEPARATE PLANS AND PERMIT REQUIRED | | FOR FIRE SPRINKLER REMODEL. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2004-10-28 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-10-28 |
Time |
11:40 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-10-28 |
Time |
11:40 |
Sent To |
E |
|
Notes |
2004-10-28 00:00:00 | TO DP DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2004-10-28 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-10-28 |
Time |
11:39 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-10-28 |
Time |
11:39 |
Sent To |
M |
|
Notes |
2004-10-28 00:00:00 | TO PK BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2004-08-26 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-08-26 |
Time |
15:16 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-08-26 |
Time |
15:16 |
Sent To |
E |
|
Notes |
2004-08-26 00:00:00 | TO DP DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2004-06-18 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-06-18 |
Time |
14:48 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-06-18 |
Time |
14:48 |
Sent To |
|
|
Notes |
2004-06-18 00:00:00 | TO COMM BD#32 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2004-05-17 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2004-05-17 |
Time |
09:05 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2004-04-27 |
Time |
16:21 |
Sent To |
PC |
|
Notes |
2004-04-27 00:00:00 | TO COMM BD#6 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2004-11-22 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2004-11-22 |
Time |
17:06 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2004-11-22 |
Time |
16:58 |
Sent To |
|
|
Notes |
2004-11-22 00:00:00 | REVISION SUBMITTED 10-28-04 / JOB CO | | DATED 11-12-04.REVISION APPROVED |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2004-07-02 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-10-28 |
Time |
11:39 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2004-07-02 |
Time |
11:16 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2004-05-14 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2004-05-14 |
Time |
16:24 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2004-05-14 |
Time |
16:24 |
Sent To |
|
|
Notes |
2004-05-14 00:00:00 | APPROVED/STAMPED 5-6-04 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2004-07-03 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2004-07-03 |
Time |
15:19 |
Rev Time |
1.00 |
Received By |
kstevens |
Date |
2004-07-03 |
Time |
15:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2004-05-14 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2004-05-14 |
Time |
16:12 |
Rev Time |
1.50 |
Received By |
kstevens |
Date |
2004-05-14 |
Time |
16:11 |
Sent To |
|
|
Notes |
2004-05-14 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 BUILDING | | FBC-2001 CHAPTER 11 | | | | 1) SHT A1.2 A DRINKING FOUNTAIN IS REQ- | | UIRED PER TABLE 403.1. ALSO SEE SECTION | | 410.1 | | 2) SHT A1.2 SINKS SHALL COMPLY WITH SEC. | | 11-4.24 AND ALL SUBSECTIONS. SHOW CLEAR | | FLOOR SPACE, HEIGHT, KNEE CLEARANCE, EX- | | POSED PIPES AND SURFACES ECT. | | 3) SHT P-1 FLOOR DRAINS ARE NOT APPROVED | | FOR INDIRECT WASTE. SEE SECTIONS 802.3 | | AND 802.3.2. | | 4) SHT P-1 SUBMIT CALCULATIONS FOR POINT | | LOADING OF BOTTON CHORD OF THE BAR JOIST | | AT WATER HEATER. INDICATE WHERE THE LOAD | | IS BEING TRANSFERRED TO. SECTION 1614.2. | | 1. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|
|