Plan Review Details - Permit 04041894
Plan Review Stops For Permit 04041894
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-06-03 Cont ID  
Sent By pschmitz Date 2004-06-21 Time 16:57 Rev Time 0.50
Received By lsmith Date 2004-06-03 Time 12:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-06-01 Cont ID  
Sent By kstevens Date 2004-05-28 Time 14:44 Rev Time 0.75
Received By lsmith Date 2004-06-01 Time 14:54 Sent To  
Notes
2004-06-01 00:00:00SUBMIT CONTRACT TO VERIFY VALUE FOR
 PERMIT VALUATION.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-06-14 Cont ID  
Sent By dpalmer Date 2004-06-14 Time 09:21 Rev Time 0.33
Received By dpalmer Date 2004-06-14 Time 09:21 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-18 Cont ID  
Sent By csiegber Date 2004-06-11 Time 16:15 Rev Time 0.50
Received By dpalmer Date 2004-05-18 Time 17:39 Sent To P
Notes
2004-05-18 00:00:00************ UNSAT *************
  
 1)NOTE: PLEASE CORRELATE LOAD PLANS/
 MOTORS AND HEAT PUMP WITH LOAD CALCULAT-
 -IONS.
 PLEASE SEE LOAD SHOWN FOR HEAT PUMP
 DOES NOT CORRELATE WITH HEAT PUMP SPECS.
 PLEASE CIRCLE HEAT PUMP TO BE INSTALLED.
  
 PLEASE SEE PLANS SHOW A 3HP POOL PUMP,
 PLEASE SEE NEC 430 TABLES FOR LOAD OF
 3HP/230V PUMP.
  
 PLEASE SEE A BLOWER IS INCLUDED ON PLANS
 HOWEVER, THIS IS NOT IN LOAD CALCS?
  
 PLEASE SEE ALL CONTINUOUS LOADS(3 OR
 MORE HRS) IS TO BE FIGURED AT 125%.
 230.42,215.3,220.19 ETC.
  
 PLEASE RECONFIGURELOAD CALCUALTIONS.
  
 2)NOTE: PLEASE SEE FBC 104.2.1, ADDITION
 -AL ELECTRICAL LOAD CALCS SHALL CONTAIN
 A PRINTED NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-06-11 Cont ID  
Sent By csiegber Date 2004-06-11 Time 16:15 Rev Time 0.00
Received By csiegber Date 2004-06-11 Time 16:15 Sent To E
Notes
2004-06-11 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-05-18 Cont ID  
Sent By csiegber Date 2004-05-18 Time 16:46 Rev Time 0.00
Received By csiegber Date 2004-05-18 Time 16:46 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-05-14 Cont ID  
Sent By mmclean Date 2004-05-18 Time 09:48 Rev Time 0.00
Received By csiegber Date 2004-05-14 Time 10:00 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-27 Cont ID  
Sent By csiegber Date 2004-04-27 Time 16:17 Rev Time 0.00
Received By csiegber Date 2004-04-27 Time 16:17 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-06-21 Cont ID  
Sent By pschmitz Date 2004-06-21 Time 16:57 Rev Time 1.00
Received By pschmitz Date   Time   Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-05-28 Cont ID  
Sent By dpalmer Date 2004-06-14 Time 09:21 Rev Time 0.75
Received By kstevens Date 2004-05-28 Time 14:44 Sent To B
Notes
2004-05-28 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 WPB CITY CODE
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES)
 2) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER.
 3) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 4) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 5) FBC-2001 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 6) SEE ATTACHED SHEET CONCERNING THE
 WPB CITY ORD. 2853-95 SECTION 31-31
 BACKFLOW TO BE INSTALLED AND TESTED BY
 THE CITY PRIOR TO POOL PERMIT BEING
 ISSUED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2004-05-18 Cont ID  
Sent By mmclean Date 2004-05-18 Time 09:48 Rev Time 0.00
Received By mmclean Date 2004-05-18 Time 09:48 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-05-03 Cont ID  
Sent By csiegber Date 2004-05-14 Time 10:01 Rev Time 0.00
Received By mmclean Date 2004-05-03 Time 14:47 Sent To  
Notes
2004-05-03 00:00:00DENIED, NEED TO PROVIDE UTILITY EASEMENT
 APPROVAL.CALLED CONTR FILE H FOR P/U M