Plan Review Details - Permit 04041857
Plan Review Stops For Permit 04041857
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-10-14 Cont ID  
Sent By jgomez Date 2004-10-14 Time 12:22 Rev Time 0.33
Received By jgomez Date 2004-10-14 Time 12:22 Sent To PC
Notes
2004-10-14 00:00:00GARAGE DOOR PRODUCT APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-07-20 Cont ID  
Sent By csiegber Date 2004-08-30 Time 10:01 Rev Time 0.33
Received By jgomez Date 2004-07-20 Time 16:25 Sent To PC
Notes
2004-07-20 00:00:001-DETAIL E/4 AND RESIDENTIAL NOTES ON
 DRAWING #2 DON'T MATCH. CLARIFY
 FASTENER SPACING. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 2-SECTION A/4: SPECIFY WHERE ARE TABLES
 6 AND 8 TAKEN FROM?. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 3-PROVIDE COPIES OF GARAGE DOOR DRAWINGS
 SUBMITTED TO SBCCI FOR APPROVAL. NEED
 DRAWINGS SIGNED AND SEALED ON DATE
 NOTED ON SBCCI EVALUATION REPORT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-06-04 Cont ID  
Sent By csiegber Date 2004-06-22 Time 14:35 Rev Time 1.00
Received By jgomez Date 2004-06-04 Time 18:23 Sent To PC
Notes
2004-06-04 00:00:00BUILDING REVIEW PROVISO:
 1-PROVIDE REVISED SURVEY WITH FEMA
 REVISION.
 2-DETAIL E/4 AND RESIDENTIAL NOTES ON
 SHEET #2 DON'T MATCH. CLARIFY FASTENER
 SPACING. SEC. 104.2.1.2 CITY AMENDMENT
 TO FBC 2001.
 3-SECTION A/4: SPECIFY WHERE ARE TABLES
 6 AND 8 FOR ROOF TILE FASTENING TAKEN
 FROM. SEC. 104.2.1.1 CITY AMENDMENTS
 TO FBC 2001.
 4-GARAGE DOORS PRODUCT APPROVAL: PROVIDE
 COMPLETE PACKAGE ONLY FOR DOOR MODEL
 TO BE INSTALLED IN THIS PROJECT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-05-21 Cont ID  
Sent By csiegber Date 2004-05-27 Time 16:30 Rev Time 1.00
Received By jgomez Date 2004-05-21 Time 13:36 Sent To PC
Notes
2004-05-21 00:00:00CHECKLIST:
 1-PROVIDE COPY OF IMPACT FEES PAID
 RECEIPT.
 2-DETAIL E/4 AND RESIDENTIAL NOTES ON
 SHEET #2 DON'T MATCH. CLARIFY FASTENER
 SPACING. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 3-SECTION A/4: SPECIFY WHERE ARE TABLES
 6 AND 8 FOR ROOF TILE FASTENING TAKEN
 FROM. SEC. 104.2.1.1 CITY AMENDMENTS
 TO FBC 2001.
 4-PROVIDE COPIES OF GARAGE DOOR DWGS
 THAT WERE SUBMITTED TO SBCCI FOR
 APPROVAL. NEED DRAWINGS THAT WERE
 SIGNED AND SEALED ON THE DATE NOTED ON
 SBCCI EVALUATION REPORT.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-05-10 Cont ID  
Sent By dpalmer Date 2004-05-10 Time 05:34 Rev Time 0.25
Received By dpalmer Date 2004-05-10 Time 05:34 Sent To M
Notes
2004-05-10 00:00:00*********** PROVISO ************
  
 1)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
 SUBMIT THE ABOVE BEFORE ROUGH, DUE THE
 UNKNOWN # OF FIXTURES BEING INSTALLED
 AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE BEFORE ROUGH,
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-08-30 Cont ID  
Sent By csiegber Date 2004-08-30 Time 10:01 Rev Time 0.00
Received By csiegber Date 2004-08-30 Time 10:01 Sent To B
Notes
2004-08-30 00:00:00TO JG DESK/SUBMITTAL/NEW PA'S

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-08-30 Cont ID  
Sent By csiegber Date 2004-08-30 Time 09:37 Rev Time 0.00
Received By csiegber Date 2004-08-30 Time 09:37 Sent To B
Notes
2004-08-30 00:00:00TO JG DESK/SUBMITTAL/NEW PA'S

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-06-22 Cont ID  
Sent By csiegber Date 2004-06-22 Time 14:35 Rev Time 0.00
Received By csiegber Date 2004-06-22 Time 14:35 Sent To B
Notes
2004-06-22 00:00:00TO JG DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-05-27 Cont ID  
Sent By csiegber Date 2004-05-27 Time 16:30 Rev Time 0.00
Received By csiegber Date 2004-05-27 Time 16:30 Sent To B
Notes
2004-05-27 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-21 Cont ID  
Sent By mmclean Date 2004-04-28 Time 11:47 Rev Time 0.00
Received By jgomez Date 2004-04-27 Time 16:36 Sent To PC
Notes
2004-04-29 00:00:00TO SFD RACK/E
2004-04-27 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-06-10 Cont ID  
Sent By dpalmer Date 2004-05-10 Time 05:40 Rev Time 0.30
Received By pkrauss Date 2004-05-14 Time 12:25 Sent To  
Notes
2004-06-10 00:00:00APPROVED 5-14-04

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-05-18 Cont ID  
Sent By kstevens Date 2004-05-18 Time 18:01 Rev Time 0.33
Received By kstevens Date 2004-05-18 Time 18:01 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-04-28 Cont ID  
Sent By mmclean Date 2004-04-28 Time 11:47 Rev Time 0.00
Received By mmclean Date 2004-04-28 Time 11:47 Sent To I
Notes
***NONE***