Plan Review Details - Permit 04041827
Plan Review Stops For Permit 04041827
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-06-28 Cont ID  
Sent By lsmith Date 2004-06-28 Time 08:27 Rev Time 1.00
Received By lsmith Date 2004-06-28 Time 08:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-05-21 Cont ID  
Sent By pkrauss Date 2004-06-25 Time 14:05 Rev Time 0.00
Received By lsmith Date 2004-05-21 Time 08:27 Sent To  
Notes
2004-05-21 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1. A NOTICE OF COMMENCEMENT MUST BE
 FILED AT THE COUNTY CLERK OFFICE AND A
 COPY SUBMITTED BEFORE A PERMIT CAN BE
 ISSUED.
  
 2. VERIFY TYPE OF WINDOW BEING
 INSTALLED IN THE DEN (S/H IMPACT).
  
 3. THE FLORIDA ENERGY EFFICIENCY CODE
 STATES THE EXTERIOR CEMENT WALLS ARE
 R-4.2 BUT THE PLANS SHOW R-12.9. PLEASE
 CLARIFY.
  
 4.VERIFY ALL USP & SIMPSON CONNECTORS
 ARE INSTALLED ACCORDING TO
 MANUFACTURERS SPECS. REVISE ON RF-1
  
 5. THE STATE PRODUCT APPROVAL IS MISSING
 FOR THE GOLF CART GARAGE DOOR.
  
 6. ROYAL WALL: SUBMIT A LETTER FROM A
 LICENSED THRESHOLD INSPECTOR STATING
 THAT AN INSPECTION WILL BE MADE AT THE
 MANUFACTURED SITE OF THE JOB SPECIFIC
 COMPONENTS TO VERIFY COMPLIANCE OF THE
 COMPONENTS WITH THE ENGINEERED DESIGN.
  
 7. STATE STATUTES REQUIRES ORIGINAL
 FULLSIGNATURES BY THE ARCHITECT AND
 ENGINEERON ALL PLANS & REPORTS.NO
 INITIALS AREPERMITTED. ALL SIGNATURES
 HAVE TO BE
 ORIGINAL, NOT PHOTO COPIES.
  
 8. THE FLORIDA PRODUCT APPROVAL FOR THE
 WEATHERGUARD STORM PANELS IS MISSING.
 PLEASE SUBMIT.
  
 9. ACCORDING TO SBCCI VALUATION TABLE
 THE A/C AREA IS BASED ON $76.96 PER SQ
 FT.THE UNCONDITIONED SPACE REMAINS AT
 $41.60.THE ADDITIONAL FEES AMOUNTS TO
 $65.09.
  
 10 THE SQ. FT. ON PLANS DOES NOT AGREE
 WITH APPLICATION.PLEASE CORRECT.
 SHOULD BE 4015 PER PLANS.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-06-23 Cont ID  
Sent By dpalmer Date 2004-06-23 Time 21:00 Rev Time 0.33
Received By dpalmer Date 2004-06-23 Time 21:00 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-07 Cont ID  
Sent By csiegber Date 2004-06-23 Time 10:59 Rev Time 0.33
Received By dpalmer Date 2004-05-07 Time 06:31 Sent To M
Notes
2004-05-07 00:00:00*** UNSAT ****
  
 1)NOTE: PLANS MUST CONTAIN SIGNATURE
 FOR ARCH.FS 481.221 MIN, FIRST AND LAST
 NAME.
 INITIALS ARE NOT ACCEPTABLE PER CONVER-
 -SATION WITH BOARD. FIRST NAME MUST ALSO
 BE SIGNED.
 SEAL MUST ALSO BE VISABLE FOR ALL INFOR-
 -MATION ON SEAL.
  
  
 2)NOTE: SD MUST BE MOVED INTO MASTER
 BEDROOM AREA PER NFPA-72 8-1
  
 ARCH MAY COME DOWN TO OFFICE AND SIGN
 PLANS WHICH WILL HELP WITH PROCESS.
 ELECTRICAL PLANS CAN BE REDLINED FOR
 SD.
 ELECTRICAL PLANS CAN NOT BE STAMPED AT
 THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-23 Cont ID  
Sent By csiegber Date 2004-06-23 Time 10:59 Rev Time 0.00
Received By csiegber Date 2004-06-23 Time 10:59 Sent To E
Notes
2004-06-23 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-21 Cont ID  
Sent By mmclean Date 2004-04-28 Time 18:21 Rev Time 0.00
Received By lsmith Date 2004-04-27 Time 14:28 Sent To  
Notes
2004-04-30 00:00:00TO SFD RACK/E
2004-04-27 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-06-25 Cont ID  
Sent By pkrauss Date 2004-06-25 Time 14:05 Rev Time 0.35
Received By pkrauss Date 2004-06-25 Time 13:55 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-05-11 Cont ID  
Sent By dpalmer Date 2004-06-23 Time 21:00 Rev Time 0.00
Received By pkrauss Date 2004-05-11 Time 12:14 Sent To B
Notes
2004-05-11 00:00:00DENIED:
 RETURN AIR FROM BEDROOM AREAS ARE NOT
 SIZED PROPERLY.PER THE REVISED 2001
 FBC(M) 601.4 EFFECTIVE JUNE 30, 2003,
 THE RETURN AIR SHALL BE SIZED AS
 FOLLOWS:
  
 BR SUITE #2 RETURN AIR JUMPER = 13" MIN
 BR SUITE #3 RETURN AIR = 10"
 MASTER SUITE RETURN AIR = 15"
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-05-08 Cont ID  
Sent By jleech Date 2004-05-08 Time 11:33 Rev Time 0.33
Received By jleech Date 2004-05-08 Time 11:33 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-04-28 Cont ID  
Sent By mmclean Date 2004-04-28 Time 18:21 Rev Time 0.00
Received By mmclean Date 2004-04-28 Time 18:21 Sent To I
Notes
***NONE***