Plan Review Details - Permit 04041650
Plan Review Stops For Permit 04041650
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-12-15 Cont ID  
Sent By jgomez Date 2004-12-14 Time 11:12 Rev Time 0.00
Received By jgomez Date 2004-12-14 Time 11:12 Sent To  
Notes
2004-12-14 00:00:00RE-STAMP DRAWINGS. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-11-02 Cont ID  
Sent By jgomez Date 2004-11-02 Time 14:33 Rev Time 0.00
Received By jgomez Date 2004-11-02 Time 14:33 Sent To PC
Notes
2004-11-02 00:00:00CHECKLIST:
 1-PLANS NEED TO BE SIGNED, SEALED AND
 DATED BY ENGINEER OF RECORD AS WELL
 AS
 REQUIRED BY CHAPTER 471 FL. STATUTES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-07-20 Cont ID  
Sent By csiegber Date 2004-10-29 Time 14:28 Rev Time 0.33
Received By jgomez Date 2004-07-20 Time 09:32 Sent To PC
Notes
2004-07-20 00:00:001-PROVIDE COPIES OF GARAGE DOOR DRAWINGS
 SUBMITTED TO SBCCI FOR APPROVAL. NEED
 DRAWINGS SIGNED AND DATED ON DATE
 NOTED ON SBCCI EVALUATION REPORT.
 2-FLOOD REVISION IS OK.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-05-19 Cont ID  
Sent By csiegber Date 2004-06-22 Time 14:33 Rev Time 1.00
Received By jgomez Date 2004-05-19 Time 14:07 Sent To PC
Notes
2004-05-19 00:00:00BUILDING REVIEW PROVISO:
 1-PROVIDE COPIES OF GARAGE DOORS DWGS
 THAT WERE SUBMITTED TO SBCCI FOR
 APPROVAL. NEED SAME DATE THAT ENGINEER
 SIGNED AND SEALED DWGS AS INDICATED
 ON SBCCI REPORT.
 2-FLOOD ZONE AO: NEED TO PROVIDE THE
 ELEVATION CERTIFICATE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-12-27 Cont ID  
Sent By dpalmer Date 2004-12-27 Time 14:00 Rev Time 0.25
Received By dpalmer Date 2004-12-27 Time 14:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-12-15 Cont ID  
Sent By dpalmer Date 2004-12-15 Time 13:22 Rev Time 0.33
Received By dpalmer Date 2004-12-15 Time 13:22 Sent To P
Notes
2004-12-15 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE SEE PLANS CAME IN FOR A
 RE-STAMP AND HAVE HAD CHANGES MADE TO
 PLANS.
 OWES A REVISION FEE.
 NEEDS TO SUBMIT TWO REVISED SETS FOR
 ELECTRICAL.
 ELECTRICAL SHEET SUBMITTED WAS VOIDED
 DUE TO STAMPING IN ERROR.
  
 PLEASE SUBMIT TWO NEW REVISED ELECTRICAL
 SHEETS AND PAY REV FEE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-05-06 Cont ID  
Sent By dpalmer Date 2004-05-06 Time 07:46 Rev Time 0.25
Received By dpalmer Date 2004-05-06 Time 07:29 Sent To M
Notes
2004-05-06 00:00:00***** PROVISO/ REDLINED***************
  
 1)NOTE: PLEASE SEE MIN LOAD FOR RANGE
 TO BE 8KW PER 220.19
  
 2)NOTE: MAX LOAD FOR 1-P20A CIRCUIT IS
 1.9KW. WASHER/IRRG PUMP SHOWN AS 2KW
  
 SD'S TO BE INSTALLED PER NFPA-72 8-1.4.2
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-12-08 Cont ID  
Sent By mjacobs Date 2004-12-08 Time 15:05 Rev Time 0.00
Received By mjacobs Date 2004-12-08 Time 15:05 Sent To B
Notes
2004-12-08 00:00:00SENT TO "JG" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-10-29 Cont ID  
Sent By csiegber Date 2004-10-29 Time 14:28 Rev Time 0.00
Received By csiegber Date 2004-10-29 Time 14:27 Sent To B
Notes
2004-10-29 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-22 Cont ID  
Sent By csiegber Date 2004-06-22 Time 14:33 Rev Time 0.00
Received By csiegber Date 2004-06-22 Time 14:33 Sent To B
Notes
2004-06-22 00:00:00TO JG DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-19 Cont ID  
Sent By mmclean Date 2004-04-28 Time 15:41 Rev Time 0.00
Received By jgomez Date 2004-04-26 Time 13:18 Sent To PC
Notes
2004-04-29 00:00:00TO SFD RACK/E
2004-04-26 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-12-21 Cont ID  
Sent By prafter Date 2004-12-21 Time 08:28 Rev Time 0.45
Received By prafter Date 2004-12-21 Time 08:28 Sent To P
Notes
2004-12-21 00:00:00RESTAMP

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-12-27 Cont ID  
Sent By jleech Date 2004-12-27 Time 15:34 Rev Time 5.00
Received By jleech Date 2004-12-27 Time 15:34 Sent To  
Notes
2004-12-27 00:00:00OK PER PAT RAFTER 12/21/04 RE-STAMP. JHL

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-05-10 Cont ID  
Sent By dpalmer Date 2004-05-06 Time 07:46 Rev Time 0.30
Received By pkrauss Date 2004-05-10 Time 16:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-12-27 Cont ID  
Sent By kstevens Date 2004-12-27 Time 15:27 Rev Time 0.25
Received By kstevens Date 2004-12-27 Time 15:27 Sent To  
Notes
2004-12-27 00:00:00RESTAMP OK

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-05-18 Cont ID  
Sent By kstevens Date 2004-05-18 Time 17:37 Rev Time 0.33
Received By kstevens Date 2004-05-18 Time 17:37 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-04-28 Cont ID  
Sent By mmclean Date 2004-04-28 Time 15:41 Rev Time 0.00
Received By mmclean Date 2004-04-28 Time 15:41 Sent To I
Notes
***NONE***