Plan Review Details - Permit 04041478
Plan Review Stops For Permit 04041478 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2005-11-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-11-22 |
Time |
16:53 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-11-22 |
Time |
16:53 |
Sent To |
M |
|
Notes |
2005-11-22 00:00:00 | TO "M" BOX/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2004-05-17 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-05-17 |
Time |
15:00 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-05-17 |
Time |
15:00 |
Sent To |
M |
|
Notes |
2004-05-17 00:00:00 | TO PK DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2004-04-22 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2004-04-22 |
Time |
11:35 |
Rev Time |
0.00 |
Received By |
alange |
Date |
2004-04-22 |
Time |
11:35 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2005-11-23 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2005-11-23 |
Time |
07:31 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2005-11-23 |
Time |
07:31 |
Sent To |
PC |
|
Notes |
2005-11-23 00:00:00 | REVISED EQUIPMENT SCHEDULE. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2004-05-27 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2004-05-27 |
Time |
07:58 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2004-05-27 |
Time |
07:58 |
Sent To |
|
|
Notes |
2004-05-27 00:00:00 | PROVISO: | | ORIGINAL PERMIT APPLICATION REQUIRED. | | | | PLEASE CONTACT CHIEF MECHANICAL | | INSPECTOR, HAROLD MOSER (805-6732) FOR A | | PRE-INSPECT, TRANSFERS MAY NOT BE | | REQUIRED. | | | | TRANSFER GRILLES ARE NOT SIZED PROPERLY. | | AS PER THE 2001 FBC(M) 601.4 EXCEPTION | | #2, A MINIMUM OF 50 SQ INCHES OF GRILLE | | AREA TO 100 CFM OF SUPPLY AIR WITH A 1" | | UNDERCUT OF THE DOOR. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2004-05-04 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-05-17 |
Time |
15:00 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2004-05-04 |
Time |
07:02 |
Sent To |
|
|
Notes |
2004-05-04 00:00:00 | DENIED: | | 1.PLEASE PROVIDE A COMPLETED FORM 600C | | OR ENERGY & MANUAL J CALCULATIONS AS | | REQUIRED PER 2001 FBC CHAPTER 13 SUB- | | CHAPTER 101.4.1.1 & 600.1.C. | | | | 2.PER THE REVISED 2001 FBC(M) 601.4 | | EFFECTIVE JUNE 30, 2003; BALANCED AIR | | REQUIRED.PLEASE SEE THE ATTACHED | | SCHEDULE FOR PROPER SIZING. | | | | 3.AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED PER 2001 FBC(M) | | 307.2.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
|