Plan Review Details - Permit 04041478
Plan Review Stops For Permit 04041478
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-11-22 Cont ID  
Sent By adarroug Date 2005-11-22 Time 16:53 Rev Time 0.00
Received By adarroug Date 2005-11-22 Time 16:53 Sent To M
Notes
2005-11-22 00:00:00TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-05-17 Cont ID  
Sent By csiegber Date 2004-05-17 Time 15:00 Rev Time 0.00
Received By csiegber Date 2004-05-17 Time 15:00 Sent To M
Notes
2004-05-17 00:00:00TO PK DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-22 Cont ID  
Sent By alange Date 2004-04-22 Time 11:35 Rev Time 0.00
Received By alange Date 2004-04-22 Time 11:35 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-11-23 Cont ID  
Sent By rregueir Date 2005-11-23 Time 07:31 Rev Time 0.00
Received By rregueir Date 2005-11-23 Time 07:31 Sent To PC
Notes
2005-11-23 00:00:00REVISED EQUIPMENT SCHEDULE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-05-27 Cont ID  
Sent By pkrauss Date 2004-05-27 Time 07:58 Rev Time 0.35
Received By pkrauss Date 2004-05-27 Time 07:58 Sent To  
Notes
2004-05-27 00:00:00PROVISO:
 ORIGINAL PERMIT APPLICATION REQUIRED.
  
 PLEASE CONTACT CHIEF MECHANICAL
 INSPECTOR, HAROLD MOSER (805-6732) FOR A
 PRE-INSPECT, TRANSFERS MAY NOT BE
 REQUIRED.
  
 TRANSFER GRILLES ARE NOT SIZED PROPERLY.
 AS PER THE 2001 FBC(M) 601.4 EXCEPTION
 #2, A MINIMUM OF 50 SQ INCHES OF GRILLE
 AREA TO 100 CFM OF SUPPLY AIR WITH A 1"
 UNDERCUT OF THE DOOR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-05-04 Cont ID  
Sent By csiegber Date 2004-05-17 Time 15:00 Rev Time 0.40
Received By pkrauss Date 2004-05-04 Time 07:02 Sent To  
Notes
2004-05-04 00:00:00DENIED:
 1.PLEASE PROVIDE A COMPLETED FORM 600C
 OR ENERGY & MANUAL J CALCULATIONS AS
 REQUIRED PER 2001 FBC CHAPTER 13 SUB-
 CHAPTER 101.4.1.1 & 600.1.C.
  
 2.PER THE REVISED 2001 FBC(M) 601.4
 EFFECTIVE JUNE 30, 2003; BALANCED AIR
 REQUIRED.PLEASE SEE THE ATTACHED
 SCHEDULE FOR PROPER SIZING.
  
 3.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.