Plan Review Details - Permit 04041245
Plan Review Stops For Permit 04041245
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-07-23 Cont ID  
Sent By btrobaug Date 2004-07-23 Time 10:15 Rev Time 0.50
Received By btrobaug Date 2004-07-23 Time 10:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-22 Cont ID  
Sent By csiegber Date 2004-04-16 Time 14:59 Rev Time 0.33
Received By dpalmer Date 2004-04-22 Time 13:38 Sent To M
Notes
2004-04-22 00:00:00********** UNSAT ********
  
 1)NOTE: PLEASE SEE NEC TABLES FOR 2-#4
 AND 1-#8 IN 3/4 " CONDUIT
  
 PLEASE SEE PLANS ARE BEING SENT TO
 MECH PLAN REVIEW.
 PLEASE SEE COMMENTS FROM MECH REVIEWER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-16 Cont ID  
Sent By csiegber Date 2004-04-16 Time 14:59 Rev Time 0.00
Received By csiegber Date 2004-04-16 Time 14:59 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2004-07-23 Cont ID  
Sent By btrobaug Date 2004-07-23 Time 10:21 Rev Time 0.00
Received By btrobaug Date 2004-07-23 Time 10:21 Sent To  
Notes
2004-07-23 00:00:00DUCT WORK ISSUES RESOLVED, MECH PERMIT
 # 04070425./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-04-28 Cont ID  
Sent By dpalmer Date 2004-04-22 Time 13:55 Rev Time 0.40
Received By pkrauss Date 2004-04-28 Time 16:34 Sent To  
Notes
2004-04-28 00:00:00DENIED:
 PER 2001 FBC 507.2.1 TYPE II HOODS,
 TYPE II HOOD SHALL BE INSTALLED AT OR
 ABOVE ALL COMMERCIAL FOOD HEAT-PRODUCING
 APPLIANCES THAT PRODUCE FUMES, STEAM,
 ODOR OR HEAT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.