Plan Review Details - Permit 04041242
Plan Review Stops For Permit 04041242
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-06-24 Cont ID  
Sent By pkrauss Date 2004-07-08 Time 07:11 Rev Time 0.55
Received By jwitmer Date 2004-06-24 Time 11:41 Sent To  
Notes
2004-06-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04041242
 ADD: 319 BELVEDERE RD
 CONT: NEWBOLD
 TEL: (561)644-5764
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 COMMENTS SAME AS FIRST REVIEW!
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-05-14 Cont ID  
Sent By jwitmer Date 2004-05-14 Time 07:57 Rev Time 1.22
Received By jwitmer Date 2004-05-14 Time 07:57 Sent To PC
Notes
2004-05-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04041242
 ADD: 319 BELVEDERE RD/ SUITE# 2
 CONT: NEWBOLD CONSTRUCTION
 TEL: (561)644-5764
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) CURRENT CODE IN USE, 2001 FLORIDA
 BUILDING CODE, 2002 UPDATE, WEST PALM
 BEACH AMENDMENTS, CORRECT.
  
 2) INTERIOR DOORS, TO COMPLY WITH
 11-4.13.5 CLEAR WIDTH, DOORWAYS SHALL
 HAVE A MINIMUM CLEAR OPENING OF 32"
 WITHTHE DOOR OPEN 90 DEGREES, MEASURED
 BETWEEN THE FACE OF THE DOOR AND THE
 OPPOSITE STOP.
  
 3)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 4)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 5) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 6)1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-06-22 Cont ID  
Sent By dpalmer Date 2004-06-22 Time 20:44 Rev Time 0.33
Received By dpalmer Date 2004-06-22 Time 20:41 Sent To  
Notes
2004-06-22 00:00:00********** UNSAT 2ND TIME ********
  
 1)NOTE: PLEASE SEE MOST NOTES FROM FIRST
 REVIEW STILL NEED TO BE ADDRESSED.
  
 2 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 3)NOTE: PLEASE SEE CIRCUITING IS STILL
 NOT SHOWN ON PLANS AND NEEDS TO
 CORRELATE WITH SUBMITTED PANEL SCHEDULE.
  
 4)NOTE: PLEASE SEE PREVIOUS NOTES.
  
 5)NOTE: PLEASE SEE ATTACHED COPY OF
 FS 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL.
 THIS IS GIVEN AS A NOTICE ONLY.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING. ONE SET
 FO OLD SHEETS MAY BE SUBMITTED FOR
 REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-21 Cont ID  
Sent By dpalmer Date 2004-04-21 Time 06:03 Rev Time 0.33
Received By dpalmer Date 2004-04-21 Time 06:03 Sent To  
Notes
2004-04-21 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SHOW ALL MIN CIRCUITING
 REQ'D UNDER 2002 NEC AND CORRELATE WITH
 A PANEL SCHEDULE. PLEASE ALSO SHOW
 LOAD AND SIZE OF EXISITNG PANEL/SERVICE
 215.5, 215.3, 230.42, 220.
 PLEASE ALSO SEE 700.12E FOR CIRCUITING
 OF EM/EXT LTS.
  
 2)NOTE: PLEASE SEE 600.5 FOR NEW/EXIST-
 -ING REQ'D SIGN CIRCUIT.
  
 3)NOTE: PLEASE SEE FS 471, NO HANDDRAWN
 CHANGES ARE TO BE MADE TO SIGNED AND
 SEALED PLANS W/OUT ENGINEER.
  
 4)NOTE: PLEASE SEE NEC 517 FOR ALL
 REQ'D ITEMS TO BE LISTED ON PLANS.
 PLANS APPEAR TO SHOW TREATMENT AREAS
 THAT MAY MEET PARTS OF 517.
 517.2, 517.60 PLEASE PROVIDE ADDITIONAL
 INFORMATION FOR THE ABOVE.
  
 5)NOTE: PLEASE SEE COMMENTS FROM OTHER
 REVIEWERS THAT MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-04-22 Cont ID  
Sent By mcarsill Date 2004-04-22 Time 14:06 Rev Time 0.00
Received By mcarsill Date 2004-04-22 Time 14:06 Sent To  
Notes
2004-04-22 00:00:001) BUILDING ADDRESS REQUIRED. A MINIMUM
 OF 6" HIGH NUMBERS ARE REQUIRED.
  
 2) PLEASE PROVIDE FIRE EXTINGUISHERS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-22 Cont ID  
Sent By csiegber Date 2004-06-22 Time 10:22 Rev Time 0.00
Received By csiegber Date 2004-06-22 Time 10:22 Sent To  
Notes
2004-06-22 00:00:00TO COMM BD#51

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-14 Cont ID  
Sent By jwitmer Date 2004-05-14 Time 08:11 Rev Time 0.00
Received By jwitmer Date 2004-04-16 Time 16:12 Sent To PC
Notes
2004-04-16 00:00:00TO COMM BD#34

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-07-08 Cont ID  
Sent By pkrauss Date 2004-07-08 Time 07:10 Rev Time 0.15
Received By pkrauss Date 2004-07-08 Time 07:06 Sent To B
Notes
2004-07-08 00:00:00SEE COMMENTS FROM PREVIOUS REVIEW DATED
 7-1-04

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-07-01 Cont ID  
Sent By pkrauss Date 2004-07-01 Time 14:35 Rev Time 0.25
Received By pkrauss Date 2004-07-01 Time 14:35 Sent To P
Notes
2004-07-01 00:00:00PROVISO:
 RETURN AIR REQUIRED FROM NEW "EXAM
 ROOMS".PLAN DOES NOT INDICATE IF THE
 RETURN AIR IS DUCTED OR A PLENUM.
 PLEASE NOTE NO COMBUSTIBLES ALLOWED
 ABOVE THE CEILING IN THE RETURN AIR
 PLENUM PER 2001 FBC(M) 602.2.1.
  
 PROVIDE REVISED PLANS FOR ANY DEVIATION
 FROM THE APPROVED SET.REVISIONS ARE TO
 BE SUBMITTED PRIOR TO INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-04-27 Cont ID  
Sent By pkrauss Date 2004-04-27 Time 11:05 Rev Time 0.30
Received By pkrauss Date 2004-04-27 Time 11:05 Sent To  
Notes
2004-04-27 00:00:00MECHANICAL CONTRACTOR NOT LISTED ON
 PERMIT APPLICATION.PLAN SHEET 4 OF 5
 INDICATES A/C CONTRACTOR TO PROVIDE
 PLANS & EQUIPMENT INFORMATION WITH
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-04-28 Cont ID  
Sent By pkrauss Date 2004-07-01 Time 15:16 Rev Time 1.00
Received By kstevens Date 2004-04-28 Time 15:08 Sent To  
Notes
2004-04-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) NEW TOILET ROOM SHALL COMPLY WITH
 SECTIONS 11-4.16, 11-4.19, & 11-4.22 AND
 ALL SUBSECTIONS. SUBMIT A DETAIL SHOWING
 CLEAR FLOOR SPACE FOR W/C AND LAV, 5'
 TURNING AREA, HEIGHT OF W/C, MEASUREMENT
 OF WATER CLOSET AND LAV OFF WALL TO THE
 CENTERLINE OF FIXTURES, HEIGHT OF LAV.,
 GRAB BAR HEIGHT/LENGTH ECT.
 2) SINK IN RECEPTIONIST AREA SHALL COMPY
 WITH 11-4.24 AND ALL SUBSECTIONS. PROVI-
 DE A DETAIL SHOWING ALL REQUIREMENTS.
 3) SHT 5 OF 5 SANITARY RISER DIAGRAM
 DOES NOT MEET CODE REQUIREMENTS. SECTION
 909.1 ONLY THE FIXTURES WITHIN THE TOIL-
 ET ROOM SHALL DRAIN THROUGH THE WET VENT
 HORIZONTAL DRAIN. ALL OTHER FIXTURES
 SHALL DISCHARGE DOWNSTREAM OF THE WET
 VENTED TOILET ROOM FIXTURES. - D/TABLE
 NOT VENTED.
 4) MORE INFORMATION REQUIRED FOR D/TABLE
 PLEASE SUBMIT MANUF. INFORMATION FOR
 THIS FIXTURE. SHOW APPROVAL BY AN APPRO-
 VED TESTING AGENCY PER SECTION 303.2 &
 303.4
 5) SHT 5 OF 5 PLUMBING RISER DIAGRAM,
 MORE INFORMATION REQUIRED ON FIXTURE
 SHOWN AFTER MASSAGE ROOM SINK. THIS FIX-
 TURE IS NOT SHOWN ON FLOOR PLAN. PLEASE
 CALRIFY. SECTION 104.2.1
 6) A WATER RISER DIAGRAM IS REQUIRED PER
 SECTION 104.3.1.1. INDICATE ALL WATER
 HAMMER ARRESTORS REQUIRED BY SECTION
 604.9 TO BE LOCATED NEAR THE FIXTURE AS
 REQUIRED IN PDI-WH 201 AND MANUF. INSTA-
 LLATION INSTRUCTIONS.
 7) AN RPZ BACKFLOW IS REQUIRED ON WATER
 SERVICE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved