Plan Review Details - Permit 04041067
Plan Review Stops For Permit 04041067
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-05-24 Cont ID  
Sent By dpalmer Date 2004-06-07 Time 08:49 Rev Time 0.50
Received By lsmith Date 2004-05-04 Time 14:34 Sent To  
Notes
2004-05-04 00:00:00PROVISO:
  
 SUBMIT COPY OF CONTRACT TO VERIFY VALUE
 FOR PERMIT FEES.
  
 5/24: FEES ADJUSTED FOR NEW CONTRACT
 AMOUNT OF 38989.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-06-07 Cont ID  
Sent By dpalmer Date 2004-06-07 Time 08:49 Rev Time 0.33
Received By dpalmer Date 2004-06-07 Time 08:49 Sent To B
Notes
2004-06-07 00:00:00******** PROVISO/REVISION *********
  
 1)NOTE: PLEASE SEE WIRING DIAGRAM HAS
 NOW BEEN REVISED TO INCLUDE ALL
 EQUIPMEN, HOWEVER NOT ALL WIRE/CONDUIT
 SIZES ARE SHOWN.
 PLEASE REVISE DIAGRM BEFORE ANY ELEC-
 -TRICAL INSPECTION.**
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-05-24 Cont ID  
Sent By csiegber Date 2004-06-02 Time 07:59 Rev Time 0.33
Received By dpalmer Date 2004-05-24 Time 14:17 Sent To B
Notes
2004-05-24 00:00:00********* UNSAT ****************
  
 1)NOTE: PLEASE SEE NOTES FROM FIRST
 REVIEW.
 PLEASE CORRELATE WIRING DIAGRAM WHICH
 SHOWS ALL EQUIPMENT BEING INSTALLED.
  
 2)NOTE: PLEASE SEE COPY OF FS 553.80(2)
 (B).THIS IS GIVEN WITH RESPECT TO THE
 DESIGN PROFESSIONAL.
  
 3)NOTE: PLEASE SEE LOAD CALCULATION
 SUBMITTED. PLEASE CORRELATE LOAD SHOWN
 ON HEAT PUMP WITH LOAD CALCS.
 PLEASE SEE 220.16 FOR MIN LAUNDRY/WASHER
 LOAD TO BE 1500 W.
  
  
 PLEASE INCLUDE SPECS FOR HEAT PUMP.
 CIRCLE OR LABEL UNIT/MODEL TO BE USED.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-03 Cont ID  
Sent By csiegber Date 2004-05-18 Time 15:43 Rev Time 0.50
Received By dpalmer Date 2004-05-03 Time 17:03 Sent To B
Notes
2004-05-03 00:00:00********* UNSAT ***************
  
 1)NOTE: PLEASE CORRELATE PLANS.
 PLANS CALL FOR HEAT PUMP , BLOWER ETC,
 YET WIRING DIAGRAM DOES NOT REFLECT ALL
 EQUIPMENT?
  
 2)NOTE: PLEASE SEE LOAD CALCS SUBMITTED,
 MENTIONS TWO LTS? ONLY ONE SHOWN ON PLAN
 -S??
  
 3)NOTE:MIN KW FOR LAUNDRY LOAD IS 1.5KW
 220.16B
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-03-16 Cont ID  
Sent By adarroug Date 2005-03-16 Time 10:46 Rev Time 0.00
Received By adarroug Date 2005-03-16 Time 10:46 Sent To P
Notes
2005-03-16 00:00:00TO "KSTEVENS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-06-02 Cont ID  
Sent By csiegber Date 2004-06-02 Time 07:59 Rev Time 0.00
Received By csiegber Date 2004-06-02 Time 07:59 Sent To E
Notes
2004-06-02 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-05-18 Cont ID  
Sent By csiegber Date 2004-05-18 Time 15:43 Rev Time 0.00
Received By csiegber Date 2004-05-18 Time 15:43 Sent To E
Notes
2004-05-18 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-22 Cont ID  
Sent By alange Date 2004-04-22 Time 13:16 Rev Time 0.00
Received By alange Date 2004-04-22 Time 13:16 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-20 Cont ID  
Sent By csiegber Date 2004-04-20 Time 14:33 Rev Time 0.00
Received By csiegber Date 2004-04-20 Time 14:33 Sent To Z
Notes
2004-04-20 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-14 Cont ID  
Sent By csiegber Date 2004-04-14 Time 11:17 Rev Time 0.00
Received By csiegber Date 2004-04-14 Time 11:17 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-03-26 Cont ID  
Sent By jleech Date 2005-03-26 Time 08:56 Rev Time 1.00
Received By jleech Date 2005-03-26 Time 08:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-05-03 Cont ID  
Sent By alange Date 2004-04-22 Time 13:16 Rev Time 1.00
Received By pschmitz Date   Time   Sent To E
Notes
2004-05-03 00:00:00BACK FLOW PREVENTER PRIOR TO COMMENCING
 WORK, PES

Review Stop Z ZONING
Rev No 2 Status P Date 2004-04-22 Cont ID  
Sent By sgraham Date 2004-04-22 Time 10:16 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-04-19 Cont ID  
Sent By csiegber Date 2004-04-20 Time 14:33 Rev Time 0.00
Received By mmclean Date 2004-04-19 Time 11:14 Sent To  
Notes
2004-04-19 00:00:00DENIED, DECK SHOULD BE 3FT IN REAR, NEED
 TO PROVIDE 2 COPY OF SURVEY SHOWING THE
 SETBACK.CALLED CONTR FILE B MM