Plan Review Details - Permit 04040894
Plan Review Stops For Permit 04040894
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-09-21 Cont ID  
Sent By jgomez Date 2004-09-21 Time 16:42 Rev Time 0.33
Received By jgomez Date 2004-09-21 Time 16:42 Sent To PC
Notes
2004-09-21 00:00:00GARAGE DOOR PRODUCT APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-05-24 Cont ID  
Sent By csiegber Date 2004-08-30 Time 10:04 Rev Time 1.00
Received By jgomez Date 2004-05-24 Time 16:46 Sent To PC
Notes
2004-05-24 00:00:00BUILDING REVIEW PROVISO:
 1-PROVIDE SOIL TEST REPORT.
 2-DETAIL E/4 AND RESIDENTIAL NOTES ON
 SHEET #2 DON'T MATCH. CLARIFY FASTENER
 SPACING. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 3-FLOOD ZONE AO: NEED TO PROVIDE THE
 ELEVATION CERTIFICATE.
 4-PROVIDE COPIES OF GARAGE DOOR DWGS
 THAT WERE SUBMITTED TO SBCCI FOR
 APPROVAL. NEED DWGS WITH SIGNING AND
 SEALING DATE AS NOTED ON SBCCI
 EVALUATION REPORT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-05-07 Cont ID  
Sent By csiegber Date 2004-05-21 Time 09:21 Rev Time 0.50
Received By jgomez Date 2004-05-07 Time 11:44 Sent To PC
Notes
2004-05-07 00:00:00CHECKLIST:
 1-NEED ENERGY CALCULATIONS THAT ARE
 CALCULATED FOR WORST CASE SCENARIO OR
 SITE SPECIFIC ACCORDING TO CARDINAL
 ORIENTATION OF THE HOUSE. ENERGY CALCS
 SUBMITTED DON'T MATCH ORIENTATION OF
 THIS HOUSE AND IS NOT WORST CASE
 EITHER. AS REQUIRED BY CHAPTER 13 OF
 FBC 2001.
 2-PROVIDE SOIL TEST REPORT.
 3-DETAIL E/4 AND RESIDENTIAL NOTES ON
 SHEET #2 DON'T MATCH. CLARIFY SPACING
 OF FASTENER. SECTION 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 4-SECTION A/4: SPECIFY WHERE ARE TABLES
 6 AND 8 FOR ROOF TILE FASTENERS TAKEN
 FROM. SEC. 104.2.1.1 CITY AMENDMENTS
 TO FBC 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-04-16 Cont ID  
Sent By dpalmer Date 2004-04-16 Time 13:15 Rev Time 0.25
Received By dpalmer Date 2004-04-16 Time 13:15 Sent To M
Notes
2004-04-16 00:00:00REDLINED , ALLSD'S TO BE INSTALLED PER
 NFPA-72 8-1.4.2

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-08-30 Cont ID  
Sent By csiegber Date 2004-08-30 Time 10:04 Rev Time 0.00
Received By csiegber Date 2004-08-30 Time 10:04 Sent To B
Notes
2004-08-30 00:00:00TO JG DESK/SUBMITTALS/NEW PA'S

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-05-21 Cont ID  
Sent By csiegber Date 2004-05-21 Time 09:21 Rev Time 0.00
Received By csiegber Date 2004-05-21 Time 09:21 Sent To B
Notes
2004-05-21 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-07 Cont ID  
Sent By mmclean Date 2004-04-15 Time 09:56 Rev Time 0.00
Received By jgomez Date 2004-04-13 Time 12:33 Sent To PC
Notes
2004-04-15 00:00:00TO SFD RACK/E
2004-04-13 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-04-26 Cont ID  
Sent By dpalmer Date 2004-04-16 Time 13:15 Rev Time 0.30
Received By pkrauss Date 2004-04-26 Time 08:57 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-05-03 Cont ID  
Sent By pkrauss Date 2004-04-26 Time 08:57 Rev Time 0.25
Received By jleech Date 2004-05-03 Time 18:45 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-04-15 Cont ID  
Sent By mmclean Date 2004-04-15 Time 09:56 Rev Time 0.00
Received By mmclean Date 2004-04-15 Time 09:56 Sent To I
Notes
***NONE***