Plan Review Details - Permit 04040818
Plan Review Stops For Permit 04040818
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-10-13 Cont ID  
Sent By jwitmer Date 2004-10-13 Time 09:34 Rev Time 1.11
Received By jwitmer Date 2004-09-15 Time 15:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-05-25 Cont ID  
Sent By csiegber Date 2004-09-01 Time 13:12 Rev Time 0.55
Received By jwitmer Date 2004-05-25 Time 09:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-28 Cont ID  
Sent By jwitmer Date 2004-04-28 Time 16:47 Rev Time 0.55
Received By jwitmer Date 2004-04-28 Time 16:47 Sent To  
Notes
2004-04-28 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04040818
 ADD: 5601 CORPORATE WAY# 108
 CONT: K& M COMMERCIAL
 TEL: (561)358-3331
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 4) NOTE # 4 WALL FINISHES:
 104.2.1 W.P.B. ADMINISTRATIVE CODE
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC
 AND THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE
 TERM "LEGAL" OR ITS RQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION".
  
 5) SINKS 11-4.24.2 SINKS SHALL BE MOUNT-
 ED WITH THE COUNTER OR RIM NO HIGHER
 THAN 34".
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-11-02 Cont ID  
Sent By dpalmer Date 2004-11-02 Time 15:18 Rev Time 0.33
Received By dpalmer Date 2004-11-02 Time 15:18 Sent To  
Notes
2004-11-02 00:00:00REV'S OK.
 REVISED LOAD CALCS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-09-21 Cont ID  
Sent By csiegber Date 2004-10-27 Time 10:33 Rev Time 0.25
Received By dpalmer Date 2004-09-21 Time 15:42 Sent To  
Notes
2004-09-21 00:00:00***** UNSAT *****
  
 1)NOTE: PLEASE CLARIFY LOAD CALCULATIONS
 AS THEY SEEM BE FIGURED AT 208V.
 PLEASE SEE RISER INDICATES PANEL AS
 3-PHASE>? IF 3-PHASE, PLEASE FIGURE
 LOAD CALCS ACCORD.
 NEC 220
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-05-08 Cont ID  
Sent By dpalmer Date 2004-05-08 Time 17:28 Rev Time 0.33
Received By dpalmer Date 2004-05-08 Time 17:28 Sent To  
Notes
2004-05-08 00:00:00******** PROVISO/ REVISION NEEDED *****
  
 1)NOTE: PLEASE SUBMIT AND SHOW ALL NEW
 CIRCUITING ON PLANS AND CORRELATE WITH
 A PANEL SCHEDULE TO BE SUBMITTED BEFORE
 FINAL INSPECTION.
 MUST BE REVIEWED, STAMPED AND RETURNED
 TO JOBSITE FOR FINAL INSPECTION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-19 Cont ID  
Sent By dpalmer Date 2004-04-19 Time 05:25 Rev Time 0.25
Received By dpalmer Date 2004-04-19 Time 05:25 Sent To  
Notes
2004-04-19 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE SEE 2002 NEC 700.12E FOR
 CIRCUITING OF EM LTS.
 PLEASE SEE NOTE #6 MENTIONS TO WIRE
 AHEAD OF DISC. LOCAL BRANCH CIRCUITING
 IS REQ'D AHEAD OF ANY LOCAL DEVICE
 SWITCHING.
  
 2)NOTE; PLEASE BE SURE RAISED SEALED
 CAN BE CLEARLY VISABLE ON ALL SHEETS.
 SOME ARE VERY FAINT.
 FS 481.221.
  
 3)NOTE: MIN CIRCUITING WILL BE REQ'D ON
 PLANS ALONG WITH A PANEL SCHEDULE BEFORE
 FINAL. THIS MAY BE DONE AT THIS TIME TO
 AVOID REVISION FEES AT A LATER DATE.
  
 PLEASE SEE FIRE REVIEW COMMENTS THAT
 WILL AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status   Date 2004-10-01 Cont ID  
Sent By mcarsill Date 2004-10-01 Time 14:19 Rev Time 0.00
Received By mcarsill Date 2004-10-01 Time 14:19 Sent To  
Notes
2004-10-01 00:00:001) DEMOLITION, RENOVATION AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-05-05 Cont ID  
Sent By mcarsill Date 2004-05-05 Time 11:14 Rev Time 0.00
Received By mcarsill Date 2004-05-05 Time 11:14 Sent To  
Notes
2004-05-05 00:00:001) ANOTHER EXIT SIGN IS NEEDED TO
 DIRECT PERSONS INTO OFFICE # 3.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-04-13 Cont ID  
Sent By mcarsill Date 2004-04-13 Time 12:48 Rev Time 0.00
Received By mcarsill Date 2004-04-13 Time 12:47 Sent To  
Notes
2004-04-13 00:00:001) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) ELECTRICAL PAGE ONLY SHOWS ONE EXIT
 DIRECTION BACK THROUGH RECEPTION AREA.
 IF THAT IS THE PROPOSED CONDITION,
 A DEAD-END CONDITION EXISTS GREATER
 THAN THE CODES ALLOW. ANOTHER EXIT
 SIGN DIRECTING PERSONS INTO OFFICE
 # 3 IS REQUIRED AND THE INTERIOR DOOR
 FOR OFFICE # 3 CANNOT BE SUBJECT TO
 LOCKING. PLEASE REVISE PLANS AS
 NECESSARY.
  
 3) DEMOLITION DEBRIS SHALL BE REMOVED
 FROM THE SITE DAILY.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-27 Cont ID  
Sent By csiegber Date 2004-10-27 Time 10:33 Rev Time 0.00
Received By csiegber Date 2004-10-27 Time 10:33 Sent To E
Notes
2004-10-27 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-09-01 Cont ID  
Sent By csiegber Date 2004-09-01 Time 13:12 Rev Time 0.00
Received By csiegber Date 2004-09-01 Time 13:12 Sent To B
Notes
2004-09-01 00:00:00TO COMM BD#24

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-05-04 Cont ID  
Sent By csiegber Date 2004-05-04 Time 15:10 Rev Time 0.00
Received By csiegber Date 2004-05-04 Time 15:10 Sent To  
Notes
2004-05-04 00:00:00TO COMM BD#11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-28 Cont ID  
Sent By csiegber Date 2004-05-04 Time 15:09 Rev Time 0.00
Received By csiegber Date 2004-04-13 Time 10:37 Sent To  
Notes
2004-04-13 00:00:00TO COMM BD#20

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-04-27 Cont ID  
Sent By pkrauss Date 2004-04-27 Time 08:41 Rev Time 0.20
Received By pkrauss Date 2004-04-27 Time 08:41 Sent To  
Notes
2004-04-27 00:00:00NO MECHANICAL PLANS OR CONTRACTOR
 INDICATED WITH PERMIT APPLICATION.
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 WITH MECHANICAL PERMIT APPLICATION.
 1.PLANS - DUCT/GRILLE SIZE MATERIAL &
 LAYOUT.
  
 2.OUTSIDE AIR CALCULATIONS PER 2001
 FBC(M) TABLE 403.3.
  
 3.PROVIDE EQUIPMENT SCHEDULE.
  
 4.INDICATE CONDENSATE LINE SIZE,
 MATERIAL AND TERMINATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-10-09 Cont ID  
Sent By kstevens Date 2004-10-09 Time 07:44 Rev Time 0.50
Received By kstevens Date 2004-10-09 Time 07:44 Sent To  
Notes
2004-10-09 00:00:00REVISION OK - CHANGED LOCATION FOR W/C
 AND LAV

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-05-22 Cont ID  
Sent By kstevens Date 2004-05-22 Time 05:51 Rev Time 0.50
Received By kstevens Date 2004-05-22 Time 05:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-04-26 Cont ID  
Sent By kstevens Date 2004-04-26 Time 18:48 Rev Time 0.50
Received By kstevens Date 2004-04-26 Time 18:32 Sent To  
Notes
2004-04-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES.
  
 1) SHT 2 AIR CHAMBERS NOT APPROVED. SEE
 SECTION 604.9 WATER HAMMER ARRESTORS
 WHERE REQUIRED, PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS FOR LOCATION.
 NOT IN CEILING.
 2) NOT ALL SIGNATURES ARE THE SAME ON
 THE SEAL. NOT ALL SEALS READABLE.
 NOT ALL SHEETS SIGNED AND SEALED.
 TITLE BLOCK REQUIRES A SPACE FOR ARCHIT-
 ECTS PRINTED NAME.FAC-61G1-16.002 -003
 -004. FS481.2055
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]