Plan Review Details - Permit 04040815
Plan Review Stops For Permit 04040815
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-13 Cont ID  
Sent By csiegber Date 2004-04-13 Time 10:30 Rev Time 0.00
Received By csiegber Date 2004-04-13 Time 10:30 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-04-19 Cont ID  
Sent By csiegber Date 2004-04-13 Time 10:30 Rev Time 0.35
Received By pkrauss Date 2004-04-19 Time 07:22 Sent To  
Notes
2004-04-19 00:00:00PROVISO:
 PLEASE NOTE RETURN AIR JUMPERS SHALL BE
 SIZED AS FOLLOWS:
 1.MASTER BEDROOM RETURN SHALL BE 12".
 ALL AIR INTO THE MASTER SUITE IS TO BE
 INCLUDED FOR THE TOTAL OF SUPPLY AIR
 INTO THAT SPACE.REVISED 2001 FBC(M)
 601.4 #1 & 3.
  
 2.BEDROOM 1, RETURN AIR JUMPER SHALL
 BE A MINIMUM OF 8" PER REVISED 2001
 FBC(M) 601.4 #1.
  
 3.BEDROOM 2, RETURN AIR SHALL BE A
 MINIMUM OF 12".
  
 SEE THE ATTACHED SCHEDULE FOR PROPER
 SIZING FOR RETURN AIR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.