Plan Review Details - Permit 04040679
Plan Review Stops For Permit 04040679
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-06-25 Cont ID  
Sent By jwitmer Date 2004-06-25 Time 13:46 Rev Time 1.11
Received By jwitmer Date 2004-06-25 Time 13:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-06-10 Cont ID  
Sent By jwitmer Date 2004-06-10 Time 15:22 Rev Time 0.75
Received By jwitmer Date 2004-06-10 Time 15:22 Sent To PC
Notes
2004-06-10 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04020679
 ADD: 2301 CENTREPARK DR# 175
 CONT: LEIGHTON MC GINN
 TEL: (561)863-4455
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND: REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) NOTE 4 FROM PREVIOUS REVIEW,
 DOOR 119. 1012.4 DURING ITS SWING, ANY
 DOOR IN A MEANS OF EGRESS SHALL LEAVE
 UNOBSTRUCTED AT LEAST ONE HALF OF THE
 REQUIRED WIDTH OF A CORRIDOR, PASSAGEWAY
 OR LANDING. PLANS INDICATE THE PASSAGE-
 WAY TO BE 4'-0"WIDE. THE DOOR SCHEDULE
 INDICATES THE DOOR IS 3'-0" WIDE. THE
 CLEAR FLOOR SPACE LEFT IS 12". THE MINI-
 MUM CORRIDOR WIDTH IS 36" FOR LESS THAN
 50 OCCUPANTS TABLE 1004, FOOTNOTE # 10.
 THE MINIMUM CLEAR WIDTH WHEN THE DOOR IS
 OPEN IS 18". THE MINIMUM CORRIDOR WIDTH
 WOULD BE 4'-6" FOR A OCCUPANT LOAD LESS
 THAN 50.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-05-10 Cont ID  
Sent By jwitmer Date 2004-05-10 Time 13:46 Rev Time 1.50
Received By jwitmer Date 2004-05-10 Time 13:46 Sent To PC
Notes
2004-05-10 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04040679
 ADD: 2301 CENTREPARK DR# 175
 CONT: LEIGHTON MC GINN
 TEL: (561)863-4455
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3) SEE DOOR # 105 & 119:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 4) DOOR# 119: 1012.4 DURING ITS SWING,
 ANY DOOR IN A MEANS OF EGRESS SHALL
 LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF
 THE REQUIRED WIDTH OF AN CORRIDOR,
 PASSAGEWAY OR LANDING.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-06-17 Cont ID  
Sent By dpalmer Date 2004-06-17 Time 19:01 Rev Time 0.33
Received By dpalmer Date 2004-06-17 Time 19:01 Sent To  
Notes
2004-06-17 00:00:00PASSED AND STAMPED ELECTRICAL SHEETS
 PENDING POSSIBLE REVIEW COMMENTS BY
 OTHER TRADES. (DOORS) SHOWN ON E-SHEETS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-05-28 Cont ID  
Sent By dpalmer Date 2004-05-28 Time 08:05 Rev Time 0.25
Received By dpalmer Date 2004-05-28 Time 08:05 Sent To  
Notes
2004-05-28 00:00:00******** UNSAT ***********
  
 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 SAME AS FIRST REVIEW.
 THIS IS ALSO SHOWN ON ELECTRICAL PLANS.
  
 PLEASE HAVE ALL OLD VOIDED SHEETS REMOVE
 -D AND ONLY INSERT NEW SHEETS TO MAKE
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 ELECTRICAL OK, SEE FIRE COMMENTS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-17 Cont ID  
Sent By dpalmer Date 2004-04-17 Time 09:48 Rev Time 0.33
Received By dpalmer Date 2004-04-17 Time 09:48 Sent To  
Notes
2004-04-17 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 FOR DOORS OPENING INTO EGRESS.
 PLEASE SEE THAT THIS COMMENT MAY HAVE
 AN AFFECT ON LAY OUT AND/OR ELECTRICAL.
  
 2)NOTE: PLEASE INDICATE AIC RATING FOR
 NEW 200A MAIN AT METER. 110.9
 SHOWN FOR NEW PANELS.
  
 3) NOTE: PLEASE SHOW ALL CONTINUOUS LOAD
 -S AT 125%(LIGHTING ETC)(LARGEST MOTORS)
 215.2,215.3,230.42 ETC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-06-18 Cont ID  
Sent By mcarsill Date 2004-06-18 Time 12:08 Rev Time 0.00
Received By mcarsill Date 2004-06-18 Time 12:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2004-05-21 Cont ID  
Sent By mcarsill Date 2004-05-21 Time 12:06 Rev Time 0.00
Received By mcarsill Date 2004-05-21 Time 12:06 Sent To  
Notes
2004-05-21 00:00:001) DOOR 113 STILL OPENS INTO CORRIDOR
 112. THIS DOOR IS APPROXIMATELY THREE
 FEET WIDE AND THE CORRIDOR IS ONLY FOUR
 FEET TEN INCHES THUS LEAVING 32 INCHES
 FOR EXITING. IN BUSINESS OCCUPANICES,
 FORTY FOUR INCHES IS REQUIRED. ALSO
 IT APPEARS THAT THE EXIT ROUTE HAS
 BEEN CHANGED BUT THE ELECTRICAL PLANS
 STILL SHOW TWO EXIT SIGNS FROM THE
 WORK AREA/WORK ROOM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-04-13 Cont ID  
Sent By mcarsill Date 2004-04-13 Time 12:14 Rev Time 0.00
Received By mcarsill Date 2004-04-13 Time 12:14 Sent To  
Notes
2004-04-13 00:00:001) DOORS 113 AND 117 NEARLY BLOCK
 CORRIDORS 112 AND 118. THE CORRIDORS
 ARE FOUR FEET WIDE OR 4'-10 AND THE
 DOORS ARE THREE FEET WIDE, THUS LEAVING
 ONE FOOT OR ONE FOOT 10 INCHES FOR EXIT
 ACCESS.
  
 2) SEPARATE PLANS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER REMODEL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-06-17 Cont ID  
Sent By csiegber Date 2004-06-17 Time 11:22 Rev Time 0.00
Received By csiegber Date 2004-06-17 Time 11:22 Sent To  
Notes
2004-06-17 00:00:00TO COMM BD#17

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-05-20 Cont ID  
Sent By csiegber Date 2004-05-20 Time 16:24 Rev Time 0.00
Received By csiegber Date 2004-05-20 Time 16:24 Sent To  
Notes
2004-05-20 00:00:00TO COMM BD#27

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-10 Cont ID  
Sent By jwitmer Date 2004-05-10 Time 14:08 Rev Time 0.00
Received By jwitmer Date 2004-04-12 Time 10:41 Sent To PC
Notes
2004-04-12 00:00:00TO COMM BD#18

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-07-01 Cont ID  
Sent By pkrauss Date 2004-07-01 Time 07:39 Rev Time 0.40
Received By pkrauss Date 2004-07-01 Time 07:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-06-01 Cont ID  
Sent By pkrauss Date 2004-06-01 Time 06:39 Rev Time 0.45
Received By pkrauss Date 2004-06-01 Time 06:39 Sent To  
Notes
2004-06-01 00:00:00DENIED:
 RESPONSE LETTER FROM KAMM CONSULTING:
 DESIGN CAPACITY IS LESS THAN 2,000 CFM,
 THEREFORE DUCT SMOKE DETECTORS & ALARM/
 STROBE IS NOT REQUIRED.
  
 PLEASE PROVIDE MANUFACTURER SUBMITTAL
 DATA FOR THE CARRIER AHU & CU #4.
 PROVIDE A LETTER FROM THE MANUFACTURER'S
 ENGINEER SPECIFYING UNDER NO CONDITIONS
 WILL THE EQUIPMENT EXCEED 2,000 CFM.
 THE LETTER SHALL BE SIGNED, SEALED &
 DATED BY THE ENGINEER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-04-22 Cont ID  
Sent By pkrauss Date 2004-04-22 Time 08:26 Rev Time 0.45
Received By pkrauss Date 2004-04-22 Time 08:01 Sent To  
Notes
2004-04-22 00:00:00DENIED:
 PER 2001 FBC(M) 606.2.1, DUCT SMOKE
 DETECTORS ARE REQUIRED IN SYSTEMS THAT
 HAVE THE DESIGN CAPACITY GREATER THAN
 2,000 CFM.PROVIDE LETTER FROM
 MANUFACTURERS ENGINEER INDICATING THAT
 UNDER NO CIRCUMSTANCE, WILL AHU-4 BE
 ABLE TO PROVIDE GREATER THAN 2,000 CFM.
  
 FAN SHUTDOWN SHALL HAVE NOTIFICATION TO
 ALARM/STROBE IN NORMALLY OCCUPIED AREAS.
 2001 NFPA 90A 6.4.4.3 (1).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-07-03 Cont ID  
Sent By kstevens Date 2004-07-03 Time 14:09 Rev Time 1.00
Received By kstevens Date 2004-07-03 Time 14:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-04-26 Cont ID  
Sent By kstevens Date 2004-04-26 Time 18:28 Rev Time 0.50
Received By kstevens Date 2004-04-26 Time 18:28 Sent To  
Notes
2004-04-26 00:00:00PASSED/PROVISO
  
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES PER PDI-WH 201 & MANUF
 INSTALL. INSTRUCTIONS