Plan Review Details - Permit 04040670
Plan Review Stops For Permit 04040670
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-01-18 Cont ID  
Sent By jwitmer Date 2005-01-18 Time 13:25 Rev Time 0.55
Received By jwitmer Date 2005-01-18 Time 13:24 Sent To  
Notes
2005-01-18 00:00:00BUILDING REV # 3 12-22-04JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-10-22 Cont ID  
Sent By jwitmer Date 2004-10-22 Time 10:23 Rev Time 0.33
Received By jwitmer Date 2004-10-22 Time 10:23 Sent To PC
Notes
2004-10-22 00:00:0010-22-04 REVISON BOTKINJW

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-06-25 Cont ID  
Sent By csiegber Date 2004-10-14 Time 10:21 Rev Time 0.55
Received By jwitmer Date 2004-06-25 Time 11:29 Sent To  
Notes
2004-06-25 00:00:00BUILDING OK TO ISSUE

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-05-19 Cont ID  
Sent By jwitmer Date 2004-05-19 Time 13:27 Rev Time 0.55
Received By jwitmer Date 2004-05-19 Time 13:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-27 Cont ID  
Sent By jwitmer Date 2004-04-27 Time 12:02 Rev Time 1.00
Received By jwitmer Date 2004-04-27 Time 12:02 Sent To PC
Notes
2004-04-27 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04040670
 ADD: 515 PALM ST
 CONT: BURKHARDT CONSTRUCTION
 TEL: (561)659-1400
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) FRONT DOOR & SIDELIGHT
 B) STORM SHUTTERS
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3)TABLE 704.1 OCCUPANCY SEPERATION
 REQUIREMENTS; GULF STREAM MARINE, THE
 WALL SEPERATING THE WAREHOUSE FROM THE
 OFFICE ALSO NEEDS TO HAVE A 2HR RATING.
 SEE 704.2.2(4) IF THE OFFICE SPACE COMPL
 IES WITH SECTION ABOVE (< 1/3RD OF THE
 MAJOROCCUPANCY FLOOR AREA IN WHICH IT IS
 LOCATED, THEN NO RATING WOULD BE NECESS-
 ARY. AS DESIGNED THE DOOR SEPERATING THE
 OFFICE FROM THE WAREHOUSE NEEDS TO BE
 A 1 1/2 HR RATING.
  
 4)NEW KITCHENETTE SINK HEIGHT MAX. 34"
 11-4.24.2
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-11-17 Cont ID  
Sent By dpalmer Date 2004-11-17 Time 13:45 Rev Time 0.33
Received By dpalmer Date 2004-11-17 Time 13:33 Sent To FIRE
Notes
2004-11-17 00:00:00STAMPED 4-SETS

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-06-15 Cont ID  
Sent By dpalmer Date 2004-06-15 Time 17:19 Rev Time 0.33
Received By dpalmer Date 2004-06-15 Time 17:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-05-14 Cont ID  
Sent By dpalmer Date 2004-05-14 Time 07:11 Rev Time 0.33
Received By dpalmer Date 2004-05-14 Time 07:05 Sent To  
Notes
2004-05-14 00:00:00***********UNSAT *******************
  
 1)NOTE: PLEASE SEE THAT ONE SET OF PLANS
 HAVE NOW BEEN RETAINED TO BE SENT OFF
 TO THE FBPE'S.
 WE HAVE REVIEWED LETTER WHICH MENTIONS
 WANTING TO USE DIFFERENT SIGNATURES.
 WE HAVE REFERENCED FS 471.025 WHICH
 REQUIRES LEGAL SIGNATURE. IT WILL BE THE
 DECISION OF THE BOARD TO RULE ON THIS.
  
 2)NOTE: PLANS HAVE BEEN CORRECTED FOR
 PREVIOUS ELECTRICAL COMMENTS. DUE TO ONE
 SET BEING SENT OFF FOR REVIEW.
 TWO NEW SETS WOULD BE NEEDED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-17 Cont ID  
Sent By dpalmer Date 2004-04-17 Time 07:36 Rev Time 0.33
Received By dpalmer Date 2004-04-17 Time 07:28 Sent To  
Notes
2004-04-17 00:00:00*********** UNSAT *****************
  
 1)NOTE: PLEASE HAVE ENGINEER SIGN PLANS.
 SIGNATURE DOES NOT SEEM TO BE THE SAME
 AS PREVIOUS PLANS WE HAVE REVIEWED AND
 PLUMB PLANS ALSO. FS 471.025
 PLEASE PROVIDE A COPY OF LEGAL LICENSE/
 AND/OR DRIVERS LICENSE TO VERIFY SIGNAT-
 -URE. ANY PERSONNEL INFORMATION ON DL
 MAY BE CROSSED OUT.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 SHOWN FOR NEW PANEL(S), BUT NOT FOR
 MAINS.
  
 3)NOTE: PLEASE SEE 250.66 FOR SIZING
 OF GROUNDING ELECTRODE.
  
 4)NOTE: PLEASE CORRELATE PLANS WITH
 RISER DIAGRAM. PLANS ONLY SHOW A METER
 ON BLDG. IS THE SERVICE IN ANOTHER
 LOCATION?
  
 5)NOTE: PLEASE LABEL CLEAR FLOOR SPACE
 FOR PANELS IN STORAGE AREA.110.26
  
 6) NOTE: PLEASE SHOW ALL CONTINUOUS LOAD
 -S AT 125%(LIGHTING ETC)(LARGEST MOTORS)
 215.2,215.3,230.42 ETC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2005-01-24 Cont ID  
Sent By nmccray Date 2005-01-24 Time 15:59 Rev Time 0.00
Received By nmccray Date 2005-01-24 Time 15:59 Sent To  
Notes
2005-01-24 00:00:00REVISION DATED 12-23-04

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-11-22 Cont ID  
Sent By nmccray Date 2004-11-22 Time 13:16 Rev Time 0.00
Received By nmccray Date 2004-11-22 Time 13:16 Sent To  
Notes
2004-11-22 00:00:00REVISION DATED 11-10-04 ELECTRICAL

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-05-14 Cont ID  
Sent By mcarsill Date 2004-05-14 Time 09:35 Rev Time 0.00
Received By mcarsill Date 2004-05-14 Time 09:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-04-13 Cont ID  
Sent By nmccray Date 2004-04-13 Time 10:22 Rev Time 0.00
Received By nmccray Date 2004-04-13 Time 10:22 Sent To  
Notes
2004-04-13 00:00:00**************DENIED********************
  
 1) PLEASE INDICATE THE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 2) HOW DOES THE RENOVATION AFFECTS THE
 FIRE SPRINKLER COVERAGE.
  
 3) SEPARATE SHOP DRAWING AND PERMIT
 APPLICATIONS ARE REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM SYSTEM REMODEL.
  
 4) BUILDING ADDRESS ARE REQUIRED ON
 PROPER ELEVATION. (MINIMUM OF 6" NUMBERS
 REQUIRED).
  
 5) FIRE EXTINGUISHER ARE REQUIRED
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-01-03 Cont ID  
Sent By mjacobs Date 2005-01-03 Time 16:03 Rev Time 0.00
Received By mjacobs Date 2005-01-03 Time 16:03 Sent To E
Notes
2005-01-03 00:00:00TO "COMM BD#29

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-11-10 Cont ID  
Sent By csiegber Date 2004-11-10 Time 14:58 Rev Time 0.00
Received By csiegber Date 2004-11-10 Time 14:58 Sent To E
Notes
2004-11-10 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-10-14 Cont ID  
Sent By csiegber Date 2004-10-14 Time 10:21 Rev Time 0.00
Received By csiegber Date 2004-10-14 Time 10:21 Sent To B
Notes
2004-10-14 00:00:00TO JW DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-11 Cont ID  
Sent By csiegber Date 2004-06-11 Time 16:00 Rev Time 0.00
Received By csiegber Date 2004-06-11 Time 16:00 Sent To  
Notes
2004-06-11 00:00:00TO COMM BD#44

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-27 Cont ID  
Sent By csiegber Date 2004-04-12 Time 09:44 Rev Time 0.00
Received By jwitmer Date 2004-04-12 Time 09:44 Sent To PC
Notes
2004-04-12 00:00:00TO COMM BD#7

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2004-05-14 Cont ID  
Sent By pkrauss Date 2004-05-14 Time 15:03 Rev Time 0.10
Received By pkrauss Date 2004-05-14 Time 15:03 Sent To  
Notes
2004-05-14 00:00:00MECHANICAL PERMIT 04041479

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-05-14 Cont ID  
Sent By pkrauss Date 2004-05-14 Time 15:01 Rev Time 0.00
Received By pkrauss Date 2004-05-04 Time 06:58 Sent To  
Notes
2004-05-04 00:00:00CANNONT LOCATE PLAN.MECHANICAL WORK
 SUBMITTED & APPROVED UNDERPERMIT
 04041479.

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-01-25 Cont ID  
Sent By kstevens Date 2005-01-25 Time 14:31 Rev Time 2.00
Received By kstevens Date 2005-01-25 Time 14:31 Sent To  
Notes
2005-01-25 00:00:00AS-BUILT-ACCESSIBLITY CODES TO BE
 ADDRESSED BY FIELD INSPECTOR. - FILE
 COPY OF PLANS NOT FOUND AFTER EXTENSIVE
 SEARCH

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-06-23 Cont ID  
Sent By kstevens Date 2004-06-23 Time 12:09 Rev Time 0.50
Received By kstevens Date 2004-06-23 Time 12:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-06-03 Cont ID  
Sent By kstevens Date 2004-06-03 Time 08:05 Rev Time 0.75
Received By kstevens Date 2004-06-03 Time 08:05 Sent To  
Notes
2004-06-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) FROM PREVIOUS REVIEW: SHOW LOCATION
 OF WATER COOLER. WATER COOLER SHALL CON-
 FORM TO ARI-1010. SUBMIT MANUF. SPECIFI-
 CATION SHEETS INDICATING ARI-1010 COM-
 PLIANCE. SECTION 410.1.
 2) FROM PREVIOUS REVIEW: KITCHENETTE
 SINK. SHOW COMPLIANCE WITH SECTION
 11-4.24.3 KNEE CLEARANCE. AT LEAST 27"
 AND 19" DEEP REQUIRED. - 11-4.24 DEPTH
 OF SINK SHALL BE 6-1/2" DEEP MAX. - AND
 11-4.24.6 EXPOSED PIPES AND SURFACES NOT
 SHOWN.
 3) A TURNING AREA COMPLYING WITH 11-4.2.
 3 IS REQUIRED FOR KITCHENETTE SINK. SEE
 FIGURES 3A OR 3B.
 4) SEE COMMENTS FROM ELECTRICAL PLAN
 REVIEW CONCERNING SIGNATURE REQUIREMENTS
 FOR ENGINEER. FAC 61G15-23.002(1)(2) &
 FS 471.025.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-04-22 Cont ID  
Sent By kstevens Date 2004-04-22 Time 15:59 Rev Time 0.50
Received By kstevens Date 2004-04-22 Time 15:59 Sent To  
Notes
2004-04-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) A DRINKING FOUNTAIN IS REQUIRED PER
 TABLE 403.1. ALSO SEE SECTION 410.1
 2) SHTS A-1 & A-2 THE SINK IN THE KITCH-
 ENETTE SHALL COMPLY WITH SECTION 11-4.24
 AND ALL SUBSECTIONS. PROVIDE A DETAIL.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]