Plan Review Stops For Permit 04040670 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2005-01-18 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2005-01-18 |
Time |
13:25 |
Rev Time |
0.55 |
Received By |
jwitmer |
Date |
2005-01-18 |
Time |
13:24 |
Sent To |
|
|
Notes |
2005-01-18 00:00:00 | BUILDING REV # 3 12-22-04JW |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2004-10-22 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2004-10-22 |
Time |
10:23 |
Rev Time |
0.33 |
Received By |
jwitmer |
Date |
2004-10-22 |
Time |
10:23 |
Sent To |
PC |
|
Notes |
2004-10-22 00:00:00 | 10-22-04 REVISON BOTKINJW |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2004-06-25 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-10-14 |
Time |
10:21 |
Rev Time |
0.55 |
Received By |
jwitmer |
Date |
2004-06-25 |
Time |
11:29 |
Sent To |
|
|
Notes |
2004-06-25 00:00:00 | BUILDING OK TO ISSUE |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2004-05-19 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2004-05-19 |
Time |
13:27 |
Rev Time |
0.55 |
Received By |
jwitmer |
Date |
2004-05-19 |
Time |
13:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2004-04-27 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2004-04-27 |
Time |
12:02 |
Rev Time |
1.00 |
Received By |
jwitmer |
Date |
2004-04-27 |
Time |
12:02 |
Sent To |
PC |
|
Notes |
2004-04-27 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 04040670 | | ADD: 515 PALM ST | | CONT: BURKHARDT CONSTRUCTION | | TEL: (561)659-1400 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | 1ST REVIEW | | ACTION: DENIED | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | 2) FL BLD CODE 1606.1.5: COMPONENTS & | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | TESTING REPORTS,MISSING REPORTS ARE AS | | FOLLOWS: | | A) FRONT DOOR & SIDELIGHT | | B) STORM SHUTTERS | | PRODUCT APPROVALS SUBMITTED WITH | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | PLEASE SEE THE STATE WEBSITE AT | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | SUBMITTED WITH A COVER SHEET THAT LISTS | | THE PRODUCT IDENTITY NUMBER FROM THE | | STATE. IF THE PRODUCT DOES NOT HAVE | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | SPECIFIC FORM PER RULE 9B-72. SEE | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | 3)TABLE 704.1 OCCUPANCY SEPERATION | | REQUIREMENTS; GULF STREAM MARINE, THE | | WALL SEPERATING THE WAREHOUSE FROM THE | | OFFICE ALSO NEEDS TO HAVE A 2HR RATING. | | SEE 704.2.2(4) IF THE OFFICE SPACE COMPL | | IES WITH SECTION ABOVE (< 1/3RD OF THE | | MAJOROCCUPANCY FLOOR AREA IN WHICH IT IS | | LOCATED, THEN NO RATING WOULD BE NECESS- | | ARY. AS DESIGNED THE DOOR SEPERATING THE | | OFFICE FROM THE WAREHOUSE NEEDS TO BE | | A 1 1/2 HR RATING. | | | | 4)NEW KITCHENETTE SINK HEIGHT MAX. 34" | | 11-4.24.2 | | | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2004-11-17 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-11-17 |
Time |
13:45 |
Rev Time |
0.33 |
Received By |
dpalmer |
Date |
2004-11-17 |
Time |
13:33 |
Sent To |
FIRE |
|
Notes |
2004-11-17 00:00:00 | STAMPED 4-SETS |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2004-06-15 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-06-15 |
Time |
17:19 |
Rev Time |
0.33 |
Received By |
dpalmer |
Date |
2004-06-15 |
Time |
17:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2004-05-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-05-14 |
Time |
07:11 |
Rev Time |
0.33 |
Received By |
dpalmer |
Date |
2004-05-14 |
Time |
07:05 |
Sent To |
|
|
Notes |
2004-05-14 00:00:00 | ***********UNSAT ******************* | | | | 1)NOTE: PLEASE SEE THAT ONE SET OF PLANS | | HAVE NOW BEEN RETAINED TO BE SENT OFF | | TO THE FBPE'S. | | WE HAVE REVIEWED LETTER WHICH MENTIONS | | WANTING TO USE DIFFERENT SIGNATURES. | | WE HAVE REFERENCED FS 471.025 WHICH | | REQUIRES LEGAL SIGNATURE. IT WILL BE THE | | DECISION OF THE BOARD TO RULE ON THIS. | | | | 2)NOTE: PLANS HAVE BEEN CORRECTED FOR | | PREVIOUS ELECTRICAL COMMENTS. DUE TO ONE | | SET BEING SENT OFF FOR REVIEW. | | TWO NEW SETS WOULD BE NEEDED. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2004-04-17 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-04-17 |
Time |
07:36 |
Rev Time |
0.33 |
Received By |
dpalmer |
Date |
2004-04-17 |
Time |
07:28 |
Sent To |
|
|
Notes |
2004-04-17 00:00:00 | *********** UNSAT ***************** | | | | 1)NOTE: PLEASE HAVE ENGINEER SIGN PLANS. | | SIGNATURE DOES NOT SEEM TO BE THE SAME | | AS PREVIOUS PLANS WE HAVE REVIEWED AND | | PLUMB PLANS ALSO. FS 471.025 | | PLEASE PROVIDE A COPY OF LEGAL LICENSE/ | | AND/OR DRIVERS LICENSE TO VERIFY SIGNAT- | | -URE. ANY PERSONNEL INFORMATION ON DL | | MAY BE CROSSED OUT. | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | RATED FOR THE AVAILABLE FAULT CURRENT. | | PER 110.9/215.5 | | SHOWN FOR NEW PANEL(S), BUT NOT FOR | | MAINS. | | | | 3)NOTE: PLEASE SEE 250.66 FOR SIZING | | OF GROUNDING ELECTRODE. | | | | 4)NOTE: PLEASE CORRELATE PLANS WITH | | RISER DIAGRAM. PLANS ONLY SHOW A METER | | ON BLDG. IS THE SERVICE IN ANOTHER | | LOCATION? | | | | 5)NOTE: PLEASE LABEL CLEAR FLOOR SPACE | | FOR PANELS IN STORAGE AREA.110.26 | | | | 6) NOTE: PLEASE SHOW ALL CONTINUOUS LOAD | | -S AT 125%(LIGHTING ETC)(LARGEST MOTORS) | | 215.2,215.3,230.42 ETC | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2005-01-24 |
|
|
Cont ID |
|
Sent By |
nmccray |
Date |
2005-01-24 |
Time |
15:59 |
Rev Time |
0.00 |
Received By |
nmccray |
Date |
2005-01-24 |
Time |
15:59 |
Sent To |
|
|
Notes |
2005-01-24 00:00:00 | REVISION DATED 12-23-04 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2004-11-22 |
|
|
Cont ID |
|
Sent By |
nmccray |
Date |
2004-11-22 |
Time |
13:16 |
Rev Time |
0.00 |
Received By |
nmccray |
Date |
2004-11-22 |
Time |
13:16 |
Sent To |
|
|
Notes |
2004-11-22 00:00:00 | REVISION DATED 11-10-04 ELECTRICAL |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2004-05-14 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2004-05-14 |
Time |
09:35 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2004-05-14 |
Time |
09:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2004-04-13 |
|
|
Cont ID |
|
Sent By |
nmccray |
Date |
2004-04-13 |
Time |
10:22 |
Rev Time |
0.00 |
Received By |
nmccray |
Date |
2004-04-13 |
Time |
10:22 |
Sent To |
|
|
Notes |
2004-04-13 00:00:00 | **************DENIED******************** | | | | 1) PLEASE INDICATE THE INTERIOR FINISH | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | 2) HOW DOES THE RENOVATION AFFECTS THE | | FIRE SPRINKLER COVERAGE. | | | | 3) SEPARATE SHOP DRAWING AND PERMIT | | APPLICATIONS ARE REQUIRED FOR FIRE | | SPRINKLER AND FIRE ALARM SYSTEM REMODEL. | | | | 4) BUILDING ADDRESS ARE REQUIRED ON | | PROPER ELEVATION. (MINIMUM OF 6" NUMBERS | | REQUIRED). | | | | 5) FIRE EXTINGUISHER ARE REQUIRED | | | | NATE MCCRAY, CAPTAIN | | 805-6722 OR 835-2910 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2005-01-03 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2005-01-03 |
Time |
16:03 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2005-01-03 |
Time |
16:03 |
Sent To |
E |
|
Notes |
2005-01-03 00:00:00 | TO "COMM BD#29 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2004-11-10 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-11-10 |
Time |
14:58 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-11-10 |
Time |
14:58 |
Sent To |
E |
|
Notes |
2004-11-10 00:00:00 | TO DP DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2004-10-14 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-10-14 |
Time |
10:21 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-10-14 |
Time |
10:21 |
Sent To |
B |
|
Notes |
2004-10-14 00:00:00 | TO JW DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2004-06-11 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-06-11 |
Time |
16:00 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-06-11 |
Time |
16:00 |
Sent To |
|
|
Notes |
2004-06-11 00:00:00 | TO COMM BD#44 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2004-04-27 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-04-12 |
Time |
09:44 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2004-04-12 |
Time |
09:44 |
Sent To |
PC |
|
Notes |
2004-04-12 00:00:00 | TO COMM BD#7 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
N |
Date |
2004-05-14 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2004-05-14 |
Time |
15:03 |
Rev Time |
0.10 |
Received By |
pkrauss |
Date |
2004-05-14 |
Time |
15:03 |
Sent To |
|
|
Notes |
2004-05-14 00:00:00 | MECHANICAL PERMIT 04041479 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2004-05-14 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2004-05-14 |
Time |
15:01 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2004-05-04 |
Time |
06:58 |
Sent To |
|
|
Notes |
2004-05-04 00:00:00 | CANNONT LOCATE PLAN.MECHANICAL WORK | | SUBMITTED & APPROVED UNDERPERMIT | | 04041479. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2005-01-25 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2005-01-25 |
Time |
14:31 |
Rev Time |
2.00 |
Received By |
kstevens |
Date |
2005-01-25 |
Time |
14:31 |
Sent To |
|
|
Notes |
2005-01-25 00:00:00 | AS-BUILT-ACCESSIBLITY CODES TO BE | | ADDRESSED BY FIELD INSPECTOR. - FILE | | COPY OF PLANS NOT FOUND AFTER EXTENSIVE | | SEARCH |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2004-06-23 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2004-06-23 |
Time |
12:09 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2004-06-23 |
Time |
12:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2004-06-03 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2004-06-03 |
Time |
08:05 |
Rev Time |
0.75 |
Received By |
kstevens |
Date |
2004-06-03 |
Time |
08:05 |
Sent To |
|
|
Notes |
2004-06-03 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | FBC-2001 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1) FROM PREVIOUS REVIEW: SHOW LOCATION | | OF WATER COOLER. WATER COOLER SHALL CON- | | FORM TO ARI-1010. SUBMIT MANUF. SPECIFI- | | CATION SHEETS INDICATING ARI-1010 COM- | | PLIANCE. SECTION 410.1. | | 2) FROM PREVIOUS REVIEW: KITCHENETTE | | SINK. SHOW COMPLIANCE WITH SECTION | | 11-4.24.3 KNEE CLEARANCE. AT LEAST 27" | | AND 19" DEEP REQUIRED. - 11-4.24 DEPTH | | OF SINK SHALL BE 6-1/2" DEEP MAX. - AND | | 11-4.24.6 EXPOSED PIPES AND SURFACES NOT | | SHOWN. | | 3) A TURNING AREA COMPLYING WITH 11-4.2. | | 3 IS REQUIRED FOR KITCHENETTE SINK. SEE | | FIGURES 3A OR 3B. | | 4) SEE COMMENTS FROM ELECTRICAL PLAN | | REVIEW CONCERNING SIGNATURE REQUIREMENTS | | FOR ENGINEER. FAC 61G15-23.002(1)(2) & | | FS 471.025. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2004-04-22 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2004-04-22 |
Time |
15:59 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2004-04-22 |
Time |
15:59 |
Sent To |
|
|
Notes |
2004-04-22 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 11 | | | | 1) A DRINKING FOUNTAIN IS REQUIRED PER | | TABLE 403.1. ALSO SEE SECTION 410.1 | | 2) SHTS A-1 & A-2 THE SINK IN THE KITCH- | | ENETTE SHALL COMPLY WITH SECTION 11-4.24 | | AND ALL SUBSECTIONS. PROVIDE A DETAIL. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|
|