2004-04-18 00:00:00 | *********** UNSAT ************** |
| |
| 1)NOTE: PLEASE SUBMIT A PANEL SCHEDULE |
| SHOWING ALL MIN CIRCUITS. |
| |
| 2) NOTE: PLEASE LIST ALL THE REQ'D |
| DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| SCHEDULE. PER 210.52D, 210.11C3 |
| |
| 3)NOTE: PLEAS LIST ARC FAULT PER 2002 |
| NEC. |
| |
| 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| |
| 5 )NOTE: PLEASE SEE MISSING REQ'D EGRESS |
| LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| PER 210.70 AND LS-101 5-8 |
| PLEASE ALSO SHOW SW TO CONTROL WHICH LTS |
| SHOW STAIRWAY/ LTS ETC. |
| |
| 6) NOTE: PLEASE SEE MISSING RECEPTS FOR |
| FRONT AND/OR REAR OF DWELLING. |
| 210.52E |
| |
| 7) NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| UNIT. |
| IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| TO FLOORS ABOVE AND IN THE VICINITY OF |
| BEDROOMS. |
| PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| A MIN OF 3' FROM BATHROOM DOORS AND |
| KITCHENS. |
| ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| |
| 8 )NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| PER PER 220, 215.5 |
| |
| 9)NOTE:PLEASE CLARIFY IF EXIST PANEL |
| SHOWN IS TO REMAIN? PLEASE SEE 110.26 |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |