Plan Review Stops For Permit 04040487 |
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2004-04-06 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2004-04-06 |
Time |
16:23 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2004-04-06 |
Time |
16:20 |
Sent To |
|
|
Notes |
2004-04-06 00:00:00 | PROVISO: | | RETURN AIR JUMPER SHALL BE SIZED AS | | FOLLOWS: | | 1ST FLOOR | | ROOM WITH 10" X 6" SUPPLY DUCT SHALL | | HAVE A MINIMUM OF 12" RETURN AIR JUMPER. | | | | 2ND FLOOR | | BEDROOM #2 SUPPLY AIR = 9" RETURN SHALL | | BE A MINIMUM OF 12". | | | | BEDROOM #1 SUPPLY AIR = 10" RETURN SHALL | | BE A MINIMUM OF 13". | | | | MASTER BEDROOM = TOTAL SUPPLY AIR 10" | | & 4" RETURN AIR SHALL BE A MINIMUM OF | | 14". | | | | AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED PER 2001 FBC(M) | | 307.2.3. | | | | PLEASE SEE THE ATTACHED SCHEDULE FOR | | FUTURE RETURN AIR JUMPERS & THROUGH THE | | WALL TRANSFER GRILLES. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
|