Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-04-06 Cont ID  
Sent By pkrauss Date 2004-04-06 Time 16:23 Rev Time 0.40
Received By pkrauss Date 2004-04-06 Time 16:20 Sent To  
Notes
2004-04-06 00:00:00PROVISO:
 RETURN AIR JUMPER SHALL BE SIZED AS
 FOLLOWS:
 1ST FLOOR
 ROOM WITH 10" X 6" SUPPLY DUCT SHALL
 HAVE A MINIMUM OF 12" RETURN AIR JUMPER.
  
 2ND FLOOR
 BEDROOM #2 SUPPLY AIR = 9" RETURN SHALL
 BE A MINIMUM OF 12".
  
 BEDROOM #1 SUPPLY AIR = 10" RETURN SHALL
 BE A MINIMUM OF 13".
  
 MASTER BEDROOM = TOTAL SUPPLY AIR 10"
 & 4" RETURN AIR SHALL BE A MINIMUM OF
 14".
  
 AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 PLEASE SEE THE ATTACHED SCHEDULE FOR
 FUTURE RETURN AIR JUMPERS & THROUGH THE
 WALL TRANSFER GRILLES.
  