Plan Review Details - Permit 04040459
Plan Review Stops For Permit 04040459
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-16 Cont ID  
Sent By csiegber Date 2004-04-16 Time 08:16 Rev Time 0.00
Received By csiegber Date 2004-04-16 Time 08:16 Sent To P
Notes
2004-04-16 00:00:00TO GAS/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-06 Cont ID  
Sent By csiegber Date 2004-04-06 Time 14:04 Rev Time 0.00
Received By csiegber Date 2004-04-06 Time 14:04 Sent To P
Notes
2004-04-06 00:00:00TO GAS

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-06-05 Cont ID  
Sent By pschmitz Date 2004-06-05 Time 13:10 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2004-06-05 00:00:00REVISION: RELOCATE TAKAGI WTR HTR.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-04-24 Cont ID  
Sent By pschmitz Date 2004-04-24 Time 09:51 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2004-04-24 00:00:00PROVISO:PLUMBING PLAN REVIEW
 INSPECTOR SHALL VERIFY TOTAL DISTANCE ,
 BTU'S OF APPLIANCE WITH MANFACTURES
 INSTALLATION MANUAL.
 REQUIRED FOR INSPECTION.

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-04-10 Cont ID  
Sent By csiegber Date 2004-04-16 Time 08:16 Rev Time 0.50
Received By kstevens Date 2004-04-10 Time 09:39 Sent To  
Notes
2004-04-10 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. TYPE OF GAS, (LP OR NATURAL)
 2. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 3. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]