Plan Review Stops For Permit 04040422 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2004-05-25 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2004-05-25 |
Time |
11:09 |
Rev Time |
1.00 |
Received By |
shill |
Date |
2004-05-25 |
Time |
11:09 |
Sent To |
|
|
Notes |
2004-05-25 00:00:00 | PROVISO - SUBMIT REVISION (SHOW ZONE 3 | | S4A, PROVIDE AREA CALCS), PROVIDE | | ORIGINAL SOILS REPORT |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2004-04-26 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2004-04-26 |
Time |
08:37 |
Rev Time |
2.00 |
Received By |
shill |
Date |
2004-04-26 |
Time |
08:37 |
Sent To |
|
|
Notes |
2004-04-26 00:00:00 | ****CORRECTIONS***** | | | | SEE 04040354 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2004-04-17 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-04-17 |
Time |
06:30 |
Rev Time |
0.25 |
Received By |
dpalmer |
Date |
2004-04-17 |
Time |
06:30 |
Sent To |
|
|
Notes |
2004-04-17 00:00:00 | OK, STAMPED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2004-04-13 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2004-04-13 |
Time |
14:03 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2004-04-13 |
Time |
14:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2004-04-26 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2004-04-06 |
Time |
14:22 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2004-04-06 |
Time |
08:34 |
Sent To |
|
|
Notes |
2004-04-06 00:00:00 | TO Z | | 4/13/04 TO COMM BD#22 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2004-05-07 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2004-05-07 |
Time |
12:46 |
Rev Time |
0.10 |
Received By |
pkrauss |
Date |
2004-05-07 |
Time |
12:46 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2004-04-20 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2004-04-20 |
Time |
14:59 |
Rev Time |
0.25 |
Received By |
hmoser |
Date |
2004-04-20 |
Time |
14:59 |
Sent To |
|
|
Notes |
2004-04-20 00:00:00 | PLAN DENIED | | PLANS AND ENERGY CALCULATIONS DO NOT | | MATCH | | 1) BTU ON EQUIPMENT | | 2) SQ.FT.OF APT. | | 3) MODEL AND LOT NUMBER OF APT. | | PLAN REVIEW BY HAROLD MOSER | | (561)805-6732 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2004-05-17 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2004-05-17 |
Time |
14:18 |
Rev Time |
0.33 |
Received By |
kstevens |
Date |
2004-05-17 |
Time |
14:18 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2004-04-21 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2004-05-07 |
Time |
12:46 |
Rev Time |
0.25 |
Received By |
kstevens |
Date |
2004-04-21 |
Time |
17:22 |
Sent To |
|
|
Notes |
2004-04-21 00:00:00 | DENIED | | REFERENCED: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | | | 1) SHT P-204 A WATER HAMMER ARRESTOR IS | | REQUIRED AT THE REFRIG. PER SECTION | | 604.9 AT UNITS B, & C. NO WATER DROP | | SHOWN FOR REFRIG. IN B UNIT ON WATER | | RISER DIAGRAM. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2004-04-06 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-04-06 |
Time |
08:33 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2004-04-06 |
Time |
14:22 |
Sent To |
I |
|
Notes |
|
|