Plan Review Details - Permit 04040411
Plan Review Stops For Permit 04040411
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-05-10 Cont ID  
Sent By shill Date 2004-05-10 Time 17:07 Rev Time 1.00
Received By shill Date 2004-05-10 Time 17:07 Sent To  
Notes
2004-05-10 00:00:00PROVISO - SUBMIT ORIG SOILS, REVISE S2A

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-04-17 Cont ID  
Sent By dpalmer Date 2004-04-17 Time 11:11 Rev Time 0.33
Received By dpalmer Date 2004-04-17 Time 11:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-04-23 Cont ID  
Sent By mcarsill Date 2004-04-23 Time 12:28 Rev Time 0.00
Received By mcarsill Date 2004-04-23 Time 12:28 Sent To  
Notes
2004-04-23 00:00:00PLEASE SEE COMMENTS FOR 04040387.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-22 Cont ID  
Sent By shill Date 2004-05-10 Time 17:07 Rev Time 0.00
Received By shill Date 2004-04-05 Time 16:07 Sent To  
Notes
2004-04-06 00:00:004/5/04TO Z
 4/6/04TO COMM BD#25

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-04-21 Cont ID  
Sent By pkrauss Date 2004-04-21 Time 14:02 Rev Time 0.05
Received By pkrauss Date 2004-04-21 Time 14:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-05-13 Cont ID  
Sent By kstevens Date 2004-05-13 Time 18:26 Rev Time 0.33
Received By kstevens Date 2004-05-13 Time 18:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-04-22 Cont ID  
Sent By kstevens Date 2004-04-22 Time 08:36 Rev Time 0.25
Received By kstevens Date 2004-04-22 Time 08:36 Sent To  
Notes
2004-04-22 00:00:00DENIED
 REFERENCED: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT P-105 A WATER HAMMER ARRESTOR IS
 REQUIRED AT THE REFRIG. PER SECTION
 604.9 AT UNITS A, B, & C. NO WATER DROP
 SHOWN FOR REFRIG. IN B UNIT ON WATER
 RISER DIAGRAM.
 2) SHT P-201 BUILDING 2 FLOOR PLAN.
 PLEASE CLARIFY THE PURPOSE FOR THIS
 SHEET.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-04-06 Cont ID  
Sent By mmclean Date 2004-04-06 Time 12:24 Rev Time 0.00
Received By mmclean Date 2004-04-06 Time 12:24 Sent To I
Notes
***NONE***