Plan Review Details - Permit 04040333
Plan Review Stops For Permit 04040333
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-05-10 Cont ID  
Sent By shill Date 2004-05-10 Time 08:41 Rev Time 1.00
Received By shill Date 2004-05-10 Time 08:41 Sent To  
Notes
2004-05-10 00:00:00PROVISO - SUBMIT ORIG SOILS, REVISE S2A

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-04-17 Cont ID  
Sent By dpalmer Date 2004-04-17 Time 07:19 Rev Time 0.25
Received By dpalmer Date 2004-04-17 Time 07:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-04-13 Cont ID  
Sent By mcarsill Date 2004-04-13 Time 15:08 Rev Time 0.00
Received By mcarsill Date 2004-04-13 Time 15:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-22 Cont ID  
Sent By shill Date 2004-05-10 Time 08:41 Rev Time 0.00
Received By shill Date 2004-04-05 Time 16:17 Sent To  
Notes
2004-04-06 00:00:004/5/04 TO Z
 4/6/04 TO COMM BD#23

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-05-05 Cont ID  
Sent By pkrauss Date 2004-05-05 Time 15:10 Rev Time 0.30
Received By pkrauss Date 2004-05-05 Time 15:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-04-20 Cont ID  
Sent By hmoser Date 2004-04-20 Time 14:44 Rev Time 0.25
Received By hmoser Date 2004-04-20 Time 14:44 Sent To  
Notes
2004-04-20 00:00:00PLAN DENIED
 1) MODEL AND LOT NUMBERS ON ENERGY
 CALCULATIONS DO NOT MATCH PLANS
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-05-13 Cont ID  
Sent By kstevens Date 2004-05-13 Time 12:58 Rev Time 0.50
Received By kstevens Date 2004-05-13 Time 12:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-04-21 Cont ID  
Sent By kstevens Date 2004-04-21 Time 17:45 Rev Time 0.50
Received By kstevens Date 2004-04-21 Time 17:45 Sent To  
Notes
2004-04-21 00:00:00DENIED
 REFERENCED: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT P-105 A WATER HAMMER ARRESTOR IS
 REQUIRED AT THE REFRIG. PER SECTION
 604.9 AT UNITS A, B, & C. NO WATER DROP
 SHOWN FOR REFRIG. IN B UNIT ON WATER
 RISER DIAGRAM.
 2) SHT P-201 BUILDING 2 FLOOR PLAN.
 PLEASE CLARIFY THE PURPOSE FOR THIS
 SHEET.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-04-06 Cont ID  
Sent By mmclean Date 2004-04-06 Time 12:59 Rev Time 0.00
Received By mmclean Date 2004-04-06 Time 12:59 Sent To I
Notes
***NONE***