Plan Review Details - Permit 04040301
Plan Review Stops For Permit 04040301
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-05-10 Cont ID  
Sent By shill Date 2004-05-10 Time 15:35 Rev Time 1.00
Received By shill Date 2004-05-10 Time 15:35 Sent To  
Notes
2004-05-10 00:00:00SUBMIT ORIG SOILS, REVISE S2A
 PROVISO

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-04-17 Cont ID  
Sent By dpalmer Date 2004-04-17 Time 10:43 Rev Time 0.33
Received By dpalmer Date 2004-04-17 Time 10:43 Sent To  
Notes
2004-04-17 00:00:00OK, STAMPED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-04-15 Cont ID  
Sent By mcarsill Date 2004-04-15 Time 15:40 Rev Time 0.00
Received By mcarsill Date 2004-04-15 Time 15:40 Sent To  
Notes
2004-04-15 00:00:001) WET FIRE HYDRANTS ARE REQUIRED
 PRIOR TO, DURING AND AFTER CONSTRUCTION.
  
 2) PORTABLE FIRE EXTINGUISHERS ARE
 REQUIRED.
  
 3) EGRESS WINDOWS ARE REQUIRED.
  
 4) SMOKE DETECTORS ARE REQUIRED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-22 Cont ID  
Sent By shill Date 2004-05-10 Time 15:35 Rev Time 0.00
Received By shill Date 2004-04-05 Time 16:20 Sent To  
Notes
2004-05-07 00:00:004/29/2004RESUB P/REVIEW B#24
2004-04-06 00:00:004/5/04 TO Z
 4/6/04 TO COMM BD#24

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-04-21 Cont ID  
Sent By pkrauss Date 2004-04-21 Time 12:12 Rev Time 0.35
Received By pkrauss Date 2004-04-21 Time 12:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-05-13 Cont ID  
Sent By kstevens Date 2004-05-13 Time 17:29 Rev Time 0.33
Received By kstevens Date 2004-05-13 Time 17:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-04-21 Cont ID  
Sent By kstevens Date 2004-04-21 Time 18:35 Rev Time 0.25
Received By kstevens Date 2004-04-21 Time 18:35 Sent To  
Notes
2004-04-21 00:00:00DENIED
 REFERENCED: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT P-105 A WATER HAMMER ARRESTOR IS
 REQUIRED AT THE REFRIG. PER SECTION
 604.9 AT UNITS A, B, & C. NO WATER DROP
 SHOWN FOR REFRIG. IN B UNIT ON WATER
 RISER DIAGRAM.
 2) SHT P-201 BUILDING 2 FLOOR PLAN.
 PLEASE CLARIFY THE PURPOSE FOR THIS
 SHEET.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-04-06 Cont ID  
Sent By mmclean Date 2004-04-06 Time 12:35 Rev Time 0.00
Received By mmclean Date 2004-04-06 Time 12:35 Sent To I
Notes
***NONE***