Plan Review Details - Permit 04040105
Plan Review Stops For Permit 04040105
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-07-20 Cont ID  
Sent By jwitmer Date 2004-07-20 Time 13:52 Rev Time 1.00
Received By jwitmer Date 2004-07-20 Time 13:52 Sent To  
Notes
2004-07-20 00:00:00FIRE DEPARTMENT TRAINING FACILITY, NO
 ROOF OR WINDOWS OR DOORS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-27 Cont ID  
Sent By jwitmer Date 2004-04-27 Time 14:39 Rev Time 0.75
Received By jwitmer Date 2004-04-27 Time 14:39 Sent To PC
Notes
2004-04-27 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04040105
 ADD: 700 N CONGRESS AV
 CONT: RICHARD ANDREA
 TEL: (561)358-4797
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS INDICATE THIS STRUCTURE TO BE
 USED FOR TRAINING, WHAT TYPE?
 2) ALL INFORMATION, DRAWINGS, SPECIF-
 ICATIONS AND ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 CITY AMENDMENTS 104.2.1
 3) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 4) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL I
 S NOT DEFINITEY KNOWN, OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL P
 ROPERLY LICENSED IN THE STATE OF
 FLORIDA.
 5)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 6) WILL THE STRUCTURE BE DESIGNED AS A
 OPEN STRUCTURE? WILL THERE BE WINDOWS
 DOORS ND ROOF SYSTEM?
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2004-04-16 Cont ID  
Sent By dpalmer Date 2004-04-16 Time 20:42 Rev Time 0.25
Received By dpalmer Date 2004-04-16 Time 20:41 Sent To  
Notes
2004-04-16 00:00:00*** NOTE***
 NO PLANS SUBMITTED FOR REVIEW.
 PLEASE SEE FIRE PLAN REVIEW NOTES.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-04-15 Cont ID  
Sent By mamini Date 2004-04-15 Time 10:28 Rev Time 0.50
Received By mamini Date 2004-04-15 Time 10:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-07-12 Cont ID  
Sent By nmccray Date 2004-07-12 Time 16:01 Rev Time 0.00
Received By nmccray Date 2004-07-12 Time 16:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-04-06 Cont ID  
Sent By mcarsill Date 2004-04-06 Time 14:59 Rev Time 0.00
Received By mcarsill Date 2004-04-06 Time 14:59 Sent To  
Notes
2004-04-06 00:00:001) WHAT TYPE OF TRAINING WILL THE
 BUILDING BE USED FOR.
  
 2) NO MECHANICAL, ELECTRICAL, OR
 PLUMBING DRAWINGS PROVIDED WITH PLANS.
 ARE ANY MEP EQUIPMENT PLANNED FOR USE.
  
 3) NO DOOR OR WINDOW SCHEDULE PROVIDED.
  
 4) PLEASE PROVIDE MORE DETAILS FOR THE
 TRAINING SHELL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-12 Cont ID  
Sent By csiegber Date 2004-07-12 Time 14:30 Rev Time 0.00
Received By csiegber Date 2004-07-12 Time 14:30 Sent To  
Notes
2004-07-12 00:00:00TO COMM BD#26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-27 Cont ID  
Sent By jwitmer Date 2004-04-27 Time 14:39 Rev Time 0.00
Received By jwitmer Date 2004-04-02 Time 15:28 Sent To PC
Notes
2004-04-02 00:00:00TO COMM BD#4

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-04-10 Cont ID  
Sent By pkrauss Date 2004-04-10 Time 13:24 Rev Time 0.15
Received By pkrauss Date 2004-04-10 Time 13:24 Sent To  
Notes
2004-04-10 00:00:00NO MECHANICAL PLANS OR INFORMATION
 SUBMITTED FOR REVIEW.PLEASE PROVIDE
 INFORMATION WITH MECHANICAL PERMIT
 APPLICATION.NO MECHANICAL CONTRACTOR
 INDICATED ON BUILDING PERMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status N Date 2004-07-26 Cont ID  
Sent By kstevens Date 2004-07-26 Time 10:42 Rev Time 0.25
Received By kstevens Date 2004-07-26 Time 10:42 Sent To  
Notes
2004-07-26 00:00:00NO PLUMING WORK TO BE INSTALLED - BLDG
 WILL NOT BE OCCUPIED - TRAINING USE ONLY
 FOR FIRE FIGHTERS

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-04-17 Cont ID  
Sent By kstevens Date 2004-04-17 Time 13:36 Rev Time 0.50
Received By kstevens Date 2004-04-17 Time 13:35 Sent To  
Notes
2004-04-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) MORE INFORMATION REQUIRED. WHAT TYPE
 OF TRAINING WILL THIS TRAINING FACILITY
 BE USED FOR?
 2) INDICATE HOW MINIMUM FACILITIES PER
 TABLE 403.1 WILL BE COMPLIED WITH.
 3) ALL INFORMATION, DRAWINGS, SPECIFIC-
 ATIONS AND ACCOMPANYING DATA SHALL BEAR
 THE NAME AND SIGNATURE OF THE PERSON RE-
 SPONSIBLE FOR THE DESIGN.
 4) MORE COMMENTS MAY FOLLOW WHEN THE
 ANSWERS TO THESE COMMENTS ARE SUBMITTED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]