Plan Review Stops For Permit 04031736 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2004-06-15 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2004-06-15 |
Time |
17:08 |
Rev Time |
1.00 |
Received By |
shill |
Date |
2004-06-15 |
Time |
17:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2004-05-24 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2004-05-24 |
Time |
16:28 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2004-05-24 |
Time |
16:24 |
Sent To |
|
|
Notes |
2004-05-24 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 04031736 | | ADD: 2805 N AUSTRALIAN AV | | CONT:ROBERT TURSO | | TEL: (561)358-4246 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | 2ND REVIEW | | ACTION: DENIED | | | | 1) FL BLD CODE 1606.1.5: COMPONENTS & | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | TESTING REPORTS,MISSING REPORTS ARE AS | | FOLLOWS: | | A) SLIDING EGRESS WINDOWS | | B) GLASS BLOCK | | C) STORM PANELS | | | | 2) PRODUCT APPROVALS SUBMITTED WITH | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | PLEASE SEE THE STATE WEBSITE AT | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | SUBMITTED WITH A COVER SHEET THAT LISTS | | THE PRODUCT IDENTITY NUMBER FROM THE | | STATE. IF THE PRODUCT DOES NOT HAVE | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | SPECIFIC FORM PER RULE 9B-72. SEE | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2004-04-28 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2004-04-28 |
Time |
16:11 |
Rev Time |
2.00 |
Received By |
jwitmer |
Date |
2004-04-28 |
Time |
15:43 |
Sent To |
|
|
Notes |
2004-04-28 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 04031736 | | ADD: 2805 N AUSTRALIAN AVE | | CONT: ROBERT A TURSO | | TEL: (561)358-4246 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | 1ST REVIEW | | ACTION: DENIED | | | | 1) FL BLD CODE 104.2.1.2 | | ADDITIONAL INFORMATION REQUIRED, | | PLANS ARE IMCOMPLETE: | | A) PLANS DO NOT INDICATE WHAT TYPE OF | | OCCUPANCY ON THE 1ST FLOOR? | | B) FIRST FLOOR PLANS DO NOT INDICATE | | IF THIS IS A SINGLE TENANT USE? OR | | C) IF A TENANT SEPERATION WALL IS | | REQUIRED? | | D) 1ST FLOOR SHOW PATH OF TRAVEL FOR | | OCCUPANCY? | | E) SURVEY INDICATES THE BUILDING .5' | | AWAY FROM PROPERTY LINE, PROVIDE MIN | | MINIMUM BUILDING TYPE, ALLOWABLE | | OPENINGS AND RATING ON THIS EXTERIOR | | WALL?TABLE 600 ISSUES | | F) PLANS INDICATE A 2ND STORY W/ A | | RESIDENTIAL USE? WHAT SUB CLASS? R-1 | | R-2 OR R-3. | | G) PLANS DO NOT PROVIDE OCCUPANCY | | SEPERATION BETWEEN THE UNITS BELOW | | AND THE PROPOSED RESIDENTIAL UNIT | | ABOVE. | | H) PLANS DO NOT INDICATE IF THE 2ND | | STORY IS EXISTING OR NEW? | | I) PLANS DO NOT GIVE ANY INFORMATION ON | | THE COMPONENTS AND CLADDING, | | WINDOWS | | EXTERIOR DOOR | | SKYLIGHTS | | GLASS BLOCK | | ROOFING ASSEMBLIES | | PRODUCT APPROVALS SUBMITTED WITH | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | PLEASE SEE THE STATE WEBSITE AT | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | SUBMITTED WITH A COVER SHEET THAT LISTS | | THE PRODUCT IDENTITY NUMBER FROM THE | | STATE. IF THE PRODUCT DOES NOT HAVE | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | SPECIFIC FORM PER RULE 9B-72. SEE | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | FL BLD CODE 1606.1.5: COMPONENTS & | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | TESTING REPORTS,MISSING REPORTS. | | J) PLANS INDICATE IN A SWING DOOR IN- | | STALLING A NEW WINDOW IN A EXISTING | | OPENING, THE MANUFACTURER OF THE DOOR | | WILL NEED TO APPROVE CHANGE SINCE DOOR | | WAS NOT TESTED THAT WAY. | | K) PLANS INDICATE THE USE OF A NEW | | TRAFFICABLE ROOF DECK PROVIDE PRODUCT | | APPROVAL, ALSO PROVIDE ENGINEERS REPORT | | FOR THE ADDITIONAL LIVE LOADS THAT MAY | | OCCUR. | | L) EXTERIOR HANDRAIL NEEDS TO BE 42" | | HIGH,1015.2 HEIGHT. GUARDRAILS SHALL | | FORM A VERTICAL PROTECTIVE BARRIER NOT | | LESS THAN 42" HIGH. | | 1015.3 OPENINGS. OPEN GUARDRAILS | | SHALL HAVE INTERMEDIATE RAILS OR ORNA- | | MENTAL PATTERNS SUCH AS A 4" DIAMETER | | SPHERE CAN NOT PASS THROUGH. A BOTTOM | | RAIL OR CURB SHALL BE PROVIDED THAT WILL | | REJECT THE PASSAGE OF 2" DIAMETER | | SPHERE. | | | | PLANS ARE INCOMPLETE A THOROUGH REVIEW | | CAN NOT BE COMPLETED AT THIS TIME. MORE | | COMMENTS MAY ARISE FROM THE ADDITIONAL | | INFORMATION REQUESTED. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2004-05-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-05-20 |
Time |
08:38 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2004-05-20 |
Time |
08:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2004-04-17 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-04-17 |
Time |
08:23 |
Rev Time |
1.00 |
Received By |
dpalmer |
Date |
2004-04-17 |
Time |
08:20 |
Sent To |
|
|
Notes |
2004-04-17 00:00:00 | *********** UNSAT ************** | | | | 1)NOTE: PLEASE SEE FS 471.219 FOR REQ'D | | CERTIFICATE OF AUTH # REQ'D. | | PLEASE SEE FAC 61G1-16.004 FOR ABOVE | | LICENSE # TO BE INCLUDED ON TITLE BLOCK. | | | | | | 2)NOTE: PLEASE SEE 104.1.1, PLEASE | | PROVIDE MORE INFORMATION IN CHANGE OF | | USE OR PORTION OF BLDG. | | PLANS APPEAR TO SHOW A NEW RESIDENCE | | BEING BUILT INTO THE SECOND FLOOR OF A | | COMMERCIAL BLDG? | | | | 3)NOTE: PLEASE SEE PLANS INDICATE OFCI | | IN LOCATIONS FOR GFCI. IS THIS THE SAME? | | STAIR LOCATION SEEMS TO SHOW WHAT APPEAR | | -S TO WALL SCONES WITH OFCI?? | | | | 4)NOTE: PLEASE SHOW ALL RECEPTS SERVING | | KITCHEN COUNTERSPACE AS GFI/GFI | | PROTECTED. 210.8A6 | | | | 5)NOTE: PLEASE VERIFY REQ'D RECEPTS FOR | | BATHROOM(S) PER 210.52D, 210.11C3, AND | | GFCI PER 210.8 | | | | 6) NOTE: SMOKE DETECTORS ARE REQUIRED | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | ON EACH LEVEL OF A MULTI-LEVEL DWELLING | | UNIT. | | IN CLOSE PROXIMITY OF STAIRWAYS LEADING | | TO FLOORS ABOVE AND IN THE VICINITY OF | | BEDROOMS. | | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE | | A MIN OF 3' FROM BATHROOM DOORS AND | | KITCHENS. | | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 | | | | 7 )NOTE: PLEASE SEE MISSING REQ'D EGRESS | | LIGHTING AND/OR CLARIFY EGRESS LIGHTING | | PER 210.70 AND LS-101 5-8 | | HALLWAY LEADING INTO FOYER OF UNIT APPEA | | -RS TO SHOW MEANS OF EGRESS TO OUTSIDE | | AND ALSO FROM LAUNDRY ROOM. PLEASE | | CLARIFY IF THESE ARE GRADE LEVEL ACCESS? | | PLEASE ALSO CLARIFY NEW OR EXISTING | | BATHROOM LIGHTING? | | | | 8) NOTE: PLEASE SHOW OUTLET SPACING PER | | 210.52. 2',6`,12` RULE. | | BEDROOM, WALL ARE LIVING RM | | | | 9)NOTE: PLEASE SEE 210.52H FOR MISSING | | HALLWAY RECEPT. | | | | 10)NOTE: PLEASE NOTE, WE ARE UNDER THE | | 2002 NEC AND ARC FAULT PROTECTION IS | | REQ'D FOR ALL BEDROOM OUTLETS. THIS IS | | INCLUDE SD'S. | | | | 11)NOTE: PLEASE CLARIFY SERVICE. SHOWS | | ONE METER, MAIN AND PANEL, YET THIS | | PANEL ONLY FEEDS WHAT APPEARS TO BE | | THIS RESIDENTIAL UNIT? | | RISER HAS A DIVISION LINE FOR BLDG EXT, | | AND APPEARS TO SHOW MAIN INSIDE? | | PLEASE SHOW LOCATION OF SERVICE/RISER | | ON PLANS. PLEASE ALSO VERIFY ADDITIONAL | | ELECTRICAL SERVICE. 230.2, 230.70, 230. | | 72 ETC. | | | | 12)NOTE: PLEASE SHOW LOCATION OF NEW | | COND UNIT, DISC AND RECEPT PER 440.11, | | 210.63. | | | | 13)NOTE: PLEASE SEE 424.3B FOR OCP OF | | AHU, HEAT. SHOWS 40A OCP FOR 10KW. | | | | 14)NOTE: PANEL SCHEDULE APPEARS TO SHOW | | ONLY ONE CIRCUIT FOR 3 BEDROOMS?? | | | | 15)NOTE: PLEASE SEE 210.52C2 FOR GFI | | RECEPT REQ'D FOR ISLAND. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2004-05-28 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2004-05-20 |
Time |
09:59 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2004-05-20 |
Time |
09:59 |
Sent To |
|
|
Notes |
2004-05-20 00:00:00 | 1) DEMOLITION, RENOVATION, AND | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | 2) EGRESS WINDOWS TO COMPLY WITH | | ALL REQUIREMENTS OF THE FLORIDA | | BUILDING CODE AND THE FLORIDA FIRE | | PREVENTION CODE. | | | | 3) THE REQUIRED ELECTRIC POWERED SMOKE | | DETECTORS SHALL BE LOCATED AT LEAST | | THREE FEET FROM AIR CONDITIONER | | DIFFUSERS. | | | | 4) BUILDING ADDRESS REQUIRED ON PROPER | | ELEVATION. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2004-04-15 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2004-04-15 |
Time |
13:24 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2004-04-15 |
Time |
13:24 |
Sent To |
|
|
Notes |
2004-04-15 00:00:00 | 1) CHANGE OF USE. NEW USE TO COMPLY | | WITH THE PROPOSED NEW USE CODES. | | | | 2) COULD NOT LOCATE ANY SMOKE | | DETECTORS WITHIN THE RESIDENTIAL UNIT. | | | | 3) PLEASE REVIEW RESIDENTIAL PORTIONS | | OF THE FIRE CODE WITH REGARDS TO THESE | | PLANS. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2004-06-08 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-06-08 |
Time |
11:36 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-06-08 |
Time |
11:36 |
Sent To |
|
|
Notes |
2004-06-08 00:00:00 | TO COMM BD#52 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2004-05-18 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-05-18 |
Time |
16:37 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-05-18 |
Time |
16:37 |
Sent To |
|
|
Notes |
2004-05-18 00:00:00 | TO COMM BD#19 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2004-05-17 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2004-05-18 |
Time |
14:45 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-05-17 |
Time |
11:16 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2004-04-28 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2004-05-07 |
Time |
08:47 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-03-31 |
Time |
15:39 |
Sent To |
|
|
Notes |
2004-04-14 00:00:00 | TO COMM BD#58 | 2004-03-31 00:00:00 | TO COMM. BOARD #16 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2004-06-01 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2004-06-01 |
Time |
08:25 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2004-06-01 |
Time |
08:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2004-04-16 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2004-04-16 |
Time |
10:49 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2004-04-16 |
Time |
10:44 |
Sent To |
|
|
Notes |
2004-04-16 00:00:00 | DENIED: | | PLEASE CLARIFY SCOPE OF WORK.PLANS | | INDICATE EXISTING A/C SYSTEM & A NEW | | PACKAGE UNIT. | | | | FORM 600C INDICATES PACKAGE UNIT, PLAN | | SHEET MEP-1 SHOWS LOCATION OF THE AHU-2. | | IS THIS UNIT FOR THE STAIRWELL? THIS A | | DUCTLESS SYSTEM? | | | | PLAN SHEET A2.2 INDICATES RELOCATING | | THE CONDENSATE PUMP.PLEASE INDICATE | | WHERE THE NEW LOCATION WILL BE. | | | | PLAN SHEET MEP-1 INDICATES TRANSFER | | GRILLES FROM THE LAUNDRY ROOM AND | | EQUIPMENT ROOM.ARE THESE RETURN AIR | | JUMPERS? | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2004-06-21 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2004-06-21 |
Time |
11:21 |
Rev Time |
1.00 |
Received By |
kstevens |
Date |
2004-06-21 |
Time |
11:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2004-06-03 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2004-06-03 |
Time |
15:14 |
Rev Time |
0.33 |
Received By |
kstevens |
Date |
2004-06-03 |
Time |
15:14 |
Sent To |
|
|
Notes |
2004-06-03 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | | | 1) SHT MEP-2 SANITARY RISER DIAGRAM DOES | | NOT MEET CODE REQUIREMENTS. THE WASH | | MACHINE SHALL NOT CONNECT UPSTREAM OF | | THE LAUNDRY SINK AND TUB. SEE ATTACHED | | SANT. RISER DIAGRAM TO SEE AN EXAMPLE OF | | A RISER THAT MEETS CODE REQUIREMENTS. | | SECTION 104.2.1 | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2004-04-26 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2004-04-26 |
Time |
17:24 |
Rev Time |
0.75 |
Received By |
kstevens |
Date |
2004-04-26 |
Time |
17:24 |
Sent To |
|
|
Notes |
2004-04-26 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1) SHT A2.1 MORE INFORMATION REQUIRED. | | THIS SHEET SHOWS A DEMO OF ALL FIXTURES. | | INDICATE OCCUPANCY OF THIS FLOOR AND | | SUBMIT CALCULATIONS FOR MINIMUM FIXTURES | | PER TABLE 403.1 | | 2) SHT A2.1 ALL CAPPED AND DEMO'D PIPES | | SHALL BE INSPECTED PRIOR TO COVERING. | | 3) SHT A2.2 INDICATES TOILET REPLACEMENT | | AND TUB REPLACEMENT, BUT SHT MEP-2 PART- | | IAL SANITARY RISER INDICATES NEW WASHER | | BOX AND SINK. PLEASE CLAIRFY - SECTION | | 104.2.1 | | 4) CERTIFICATE OF AUTHORIZATION REQUIRED | | ON TITLE BLOCK PER FS 471.219(2)(3) | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2004-05-18 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2004-05-18 |
Time |
14:45 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2004-05-18 |
Time |
14:45 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2004-04-01 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-05-17 |
Time |
11:16 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2004-04-01 |
Time |
15:47 |
Sent To |
|
|
Notes |
2004-04-01 00:00:00 | DENEID, 1. NEED TO PROVIDE UNIT OF TITLE | | FOR LOT 13 & 14 AND PROVIDE A COPY OF | | SURVEY SHOWING THE UNITY OF TITLE. | | 2. BUILDING IS ENCROACH ONTO N SIDE OF | | PROPERTY.NEED TO REMOVE THE PORTITION | | THAT HANGS ON 2825 N AUSTRALIAN. | | CALLED CONTR FOR PICK UP FILE R MM |
|
|