2004-07-29 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 04031716 |
| ADD: 507 24TH ST/ 508 25TH ST |
| VILLAGE CENTER APARTMENTS |
| CONT: CARLISLE CONSTRUCTION, LLC |
| TEL: (305)898-2198 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1ST REVIW |
| ACTION: DENIED |
| |
| THIS PLAN CAME IN UNDER A SINGLE PERMIT, |
| WITH AN ALLEYWAY BETWEEN THE (2) LOTS |
| THIS PROJECT WILL BE CONSIDERED AS (2) |
| LOTS, (2) BUILDINGS & (2) PERMITS. |
| |
| 1) PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| FOR EACH PERMIT. |
| |
| 2) TABLE 600 ISSUES, 2ND THROUGH 5TH |
| FLOORS EXTEND PAST OR OVER THE PROPERTY |
| LINE, (OVER THE ALLEYWAY) OR PUBLIC |
| WAY. PROVIDE DOCUMENTATION APPROVAL FROM |
| THE CITY, PLANNING AS WELL AS LEGAL. |
| |
| 3)) THE PROPOSED BUILDING STRUCTURE |
| TRANSGRESSES LEGAL BOUNDARY LINES |
| BETWEEN THE LOTS WHICH COMBINE TO FORM |
| 'THE SITE'.SUBMIT A COPY OF THE 'UNITY |
| OF TITLE' DOCUMENT SO THAT FBC TABLE 600 |
| BOUNDARY LINE REQUIREMENTS MAY BE DEEMED |
| NOT APPLICABLE. |
| THIS REQUIREMENT WILL BE REQUIRED |
| FOR BOTH PROJECTS ON BOTH SIDES OF THE |
| ALLEYWAY. |
| |
| 4) FL S. S. 553.71(7) " THRESHOLD |
| BUILDING" MEANING ANY BUILDING WHICH IS |
| GREATER THAN (3) STORIES OR 50 FT IN |
| HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN |
| CY CLASSIFICATION AS DEINED IN THE |
| FLORIDA BUILDING CODE WHICH EXCEEDS |
| 5,000 SQ FT IN AREA AND AN OCCUPANT |
| CONTENT OF GREATER THAN 500 PERSONS. |
| 105.13.1 THE ENFORCING AGENCY SHALL |
| REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| SRUCTURAL INSPECTIONS ON A THRESHOLD |
| BUILDING PURSUANT TO A STRUCTURAL INSPEC |
| TION PLAN PREPARED BY THE ENGINEER OF |
| RECORD. THE STRUCTURAL INSPECTION PLAN |
| MUST BE SUBMITTED TO THE ENFORCING AGEN- |
| CY PRIOR TO THE ISSUANCE OF A BUILDING |
| PERMIT FOR THE CONSTRUCTION OF A THRESH- |
| OLD BUILDING. THE PURPOSE OF THE SRUCTUR |
| AL INSPECTION PLAN IS TO PROVIDE SPECIF- |
| IC INSPECTION PROCEDURES AND SCHEDULES |
| SO THAT THE BUILDING CAN BE ADEQUATELY |
| INSPECTED FOR COMPLIANCE WITH THE |
| PERMITTED DOCUMENTS. |
| |
| 5)WPB AMENDMENT 105.13.6. W.P.B. |
| CONSTRUCTION SERVICES DEPARTMENT |
| REQUEST FOR THRESHOLD BUILDINGS A |
| SPECIAL INSPECTOR AS REQUIRED BY S. |
| 553.79(5) FLORIDA STATUTES TO THE MIN- |
| IMUM INSPECTIONS REQUIRED BY THIS CODE. |
| CONTACT HAROLD PISKURA MANAGER OF THE |
| SPECIAL INSPECTOR PROGRAM AT (561) |
| 805-6711 FOR FURTHER INFORMATION BEFORE |
| THE PERMIT MAY BE ISSUED. |
| |
| 6)W.P.B. AMENDMENT 105.13.4.4 ALL |
| PLANS FOR THE BUILDING WHICH ARE |
| REQUIRED TO BE SIGNED AND SEALED BY THE |
| ARCHITECT OR ENGINEER OF RECORD CON- |
| TAIN A STATEMENT THAT, TO THE BEST OF |
| THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, |
| THE PLANS AND SPECIFICATIONS COMPLY WITH |
| THE APPLICABLE FIRE-SAFETY STANDARDS AS |
| DETERMINED BY THE LOCAL AUTHORITY IN |
| ACCORDANCE WITH THIS SECTION AND 633 |
| FLORIDA STATUTE. |
| |
| 7) PROVIDE 3 CURRENT COPIES OF SIGNED & |
| SEALED SURVEYS WITH PROPOSED IMPROVEMENT |
| TO BE COMPLETED. |
| |
| 8) FL BLD CODE 1804.2.2.QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| WHERE THE BEARING CAPACITY OF THE SOIL |
| IS NOT DEFINITLY KNOWN OR IS IN QUESTION |
| THE BUILDING OFFICIAL MAY REQUIRE EXPLOR |
| ATIONS, TEST OR OTHER ADEQUATE PROOF AS |
| TO THE PERMISSIBLE SAFE BEARING |
| CAPACITY. REQUIRED TEST AND RECOMMENDA- |
| TIONS SUBMITTED TO VERIFY BEARING CAPA- |
| CITY SHALL BE CERTIFIED BY A GEOTECH- |
| NICALREPORT FROM A DESIGN PROFESSIONAL |
| PROPERLY LICENSED IN THE STATE OF |
| FLORIDA. |
| |
| 9) FL BLD CODE CHAP 13 ENERGY EFFICENCY |
| PROVIDE ENERGY CALS/ W MANUAL "J" |
| |
| 10) WRONG JURISDICTION, SEE LS3.00 |
| |
| 11) SEE PD 1 OF 2, PLANS INDICATE A 6% |
| GRADE AT THE ACCESSIBLE PARKING SPACE & |
| ACCESS ISLE. 11-4.6.3 SLOPES NOT TO |
| EXCEED 1:50 OR 2%. |
| |
| 12)SHEET A3.01 INDICATES A COLUMN DETAIL |
| AT THE ENTRY TO THE ALLEY FROM DIXIE, |
| NO SECTION OR PAGE? ADD INFO REQUIRED! |
| |
| 13) SHEET LS 3.01 INDICATES THE WEST END |
| OF THE PROJECT IS WITHIN 3 FT OF THE |
| PROPERTY LINE, REQUIRING A 3 HR WALL. |
| PROVIDE EQUIVLANT THICKNESS OF BLOCK, |
| SEE TABLE 709.3.1. |
| |
| 14) SHEET A9.01 DOOR SCHEDULE MISSING |
| 45 MIN RATING ON THE TRASH CHUTE TERMIN- |
| ATION ROOM. TABLE705.1.2. |
| |
| 15) A3.09 TRASH CHUTE ENCLOSURE (SHAFT) |
| REQUIRES A 2HR RATED BLOCK. SHEET A7.01 |
| INDICATES A UL DESIGN NUMBER, BUT WE |
| WILL NEED THE EQUIVALENT THICKNESS FROM |
| THE BLOCK MANUFACTURER.TABLE 709.3.1. |
| |
| 16) SHEET A3.07 PROVIDE INFORMATION, |
| REQUIRED STRETCHER REQUIREMENT FOR |
| ELEVATORS 3003.4.1. |
| |
| 17) ARCHITECTURAL SHEETS INDICATE THE |
| USE OF EFIS FOAM TRIM ON THE EXTERIOR OF |
| THE BUILDING. ON BUILDINGS OF TYPE III, |
| V AND VI CONSTRUCTION, TRIM SHALL BE SE- |
| CURED TO THE WALL WITH METAL OR OTHER |
| APPROVED BRACKETS OR FASTENERS. PROVIDE |
| ADDTIONAL INFORMATION? |
| |
| 18) A8.01 GUARDRAILS ARETO COMPLY WITH: |
| FBC 1608.2.2THE GUARDRAIL SHALL BE |
| DESIGNED AND CONSTRUCTED FOR A |
| CONCENTRATED LOAD OF 200 LB APPLIED IN |
| ANY DIRECTION AT THE TOP OF THE |
| GUARDRAIL, A CONCENTRATED HORIZONTAL |
| LOAD OF 200 LB APPLIED ON A 1 SQ FT AREA |
| AT ANY POINT, AND A LINE LOAD OF 50 PLF |
| APPLIED HORIZONTALLY AT THE REQUIRED |
| GUARDRAIL HEIGHT WITH A SIMULTANEOUS |
| LINE LOAD OF 100 PLF APPLIED VERTICALLY |
| DOWNWARD ON THE TOP OF THE GUARDRAIL. |
| THESE LOADS SHALL NOT BE APPLIED |
| SIMULTANEOUSLY (UNLESS NOTED ABOVE) BUT |
| SHALL BE APPLIED INDIVIDUALLY TO PRODUCE |
| MAXIMUM STRESS IN EACH OF THE COMPONENTS |
| OR SUPPORTS.SUBMIT CALCULATIONS. |
| |
| 19)A8.02 DETAIL# 4, THERE ARE (2) ISSUES |
| A) PLYWOOD SHEATHING CAN'T BE USED ON |
| EXTERIOR WALLS TYPE V CONSTRUCTION. |
| B) IT APPEARS THIS SAME NOTE INDICATES |
| PLYWOOD TO BE USED AS SIDING? |
| |
| 20) THIS SAME PAGE DETAIL# 2, INDICATES |
| THE USE OF PLYWOOD FOR ROOF SHEATHING, |
| TABLE 600 ROOF CEILING ASSEMBLIES FOR |
| (1 HR PROTECTED) REQUIRES A 1HR RATING. |
| |
| 21) S-2.01 SEE DESIGN LIVE LOADS: |
| COORIDORS (ABOVE THE FIRST FLOOR) SHOLD |
| BE 80 LBS. TABLE 1604.1. |
| |
| 22) SAME PAGE WIND ZONE FOR ENTIRE CITY |
| OF W.P.B. IS 140 HPH, CORRECT.ALSO THE |
| EXPOSURE IS A "B" ZONE NOT A "C". |
| |
| 23) THE LIGHT GAGE STEEL DESIGN DATA |
| ALSO DOESN'T MATCH THE BUILDING DESIGN |
| CRITERIA,1606.1.7/1606.1.8. |
| |
| 24)FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) WINDOWS FIXED & OPERABLE |
| B) MULLIONS VERTICAL & HORIZONTAL |
| C) EXTERIOR DOORS SOLID & GLAZED |
| D) STORM SHUTTERS |
| E) LOUVERS |
| F) EFIS SYSTEMS |
| G) TRUSS STRAPS AND ANCHORS |
| H) ROOFING ASSEMBLIES |
| |
| 25) PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LIST |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE.IF THE PRODUCT DOES NOT HAVE STATE |
| WIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| LOCAL PRODUCT APPROVAL PER RULE 9B-72. |
| SEE ATTACHMENT. |
| |
| 26)PROVIDE STORM PANEL INFORMATION WITH |
| INSTALLATION SCHEDULE AND KEY PLAN WITH |
| SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| FOR ALL NON-IMPACT GLAZING. |
| FBC 1606.1.4. |
| |
| 27)FL BLD CODE 2001 SECTION 103.6, |
| 1606.1.4, 1707.4 & 3401.7.2.4. |
| PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| SCHEDULE SUMMARIZING & IDENTIFYING |
| OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| BAR REINFORCING REQUIREMENTS, WALL PRES- |
| SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| SUBMITTED AT TIME OF PERMIT APPLICATION |
| TO FACILITATE PLAN REVIEW AND PERMIT |
| ISSUANCE. |
| PROVIDE INFORMATION WHERE THE STORM |
| SHUTTERS ARE TO BE STORED, IF STORED |
| VERTICALLY HOW THEY WILL BE SUCURED SO |
| THEY WILL NOT FALL OVER. |
| |
| 28)1707.4.3 EACH EXTERIOR DOOR |
| ASSEMBLY NOT COVERED BY 1707.4.2 |
| (GLAZED DOORS) SHALL BE LISTED AND TEST- |
| ED FOR A PERIOD EQUAL TO THE QUANITY |
| 3600/ V WHERE THE TIME PERIOD IS IN |
| SECTIONS AND V IS IN MILES PER HR TAKEN |
| FROM FIGURE 1606. THE TIME PERIOD SHALL |
| ALSO INCLUDE A 10 SECOND PERIOD AT A |
| LOAD EQUAL TO 1.5 TIMES THE DESIGN |
| PRESSURE. |
| |
| 29) 1707.4.5.1 MULLIONS OCCURRING |
| BETWEEN INDIVIDUAL WINDOW AND GLASS |
| DOOR ASSEMBLIES. TESTING REPORTS ARE |
| REQUIRED BY AN APPROVED TESTING |
| LABORATORY OR BE ENGINEERED. |
| |
| 30) 1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| TO THE ROUGH OPENING SUBTRATE. |
| |
| 31) S8.01 ROOF PRESSURES, PLANS INDICATE |
| NEGATIVE PRESSURES AS HIGH AS -208.6. |
| FOR THE ROOFING ASSEMBLIES REPORTS, BE |
| SURE TO MEET THESE PRESSURES. |
| |
| 32) S3.00/ S7.01 SHEAR WALLS AND FOUNDA- |
| TIONS THE WIDTH AND LENGTH OF FOOTINGS |
| ARE GIVEN BUT NOT THE DEPTH NOR THE |
| NUMBER OF BARS OR SIZE OF BARS. |
| |
| 33) FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, |
| STRUCTURAL SHEETS DO NOT HAVE A TRUSS |
| ANCHOR SCHEDULE FOR THE STEEL TRUSSES |
| NORA TRUSS LAYOUT WITH UPLFT VALUES |
| AND LATERAL LOADING. |
| |
| 34) 1503.4.4 PROTECTION AGAINST DECAY & |
| TERMITES. CONDENSATE LINES & ROOF DOWN |
| SPOUTS SHALL DISCHARGE AT LEAST 1 FT. |
| AWAY FROM THE STRUCTURE SIDEWALL, |
| WHETHER BY UNDERGROUND PIPING, TAIL EX- |
| TENSIONS, OR SPLASH BLOCKS. |
| |
| 35)1511.7 ROOF MOUNTED MECHANICAL UNIT |
| S SHALL BE MOUNTED ON CURBS RAISED A |
| MINIMUM OF 8 INCHES ABOVE THE ROOF SUR- |
| FACE, OR WHERE ROOFING MATERIALS EXTEND |
| BENEATH THE UNIT, ON RAISED EQUIPMENT |
| SUPPORTS PROVIDING A MINIMUM CLEARENCE |
| HEIGHT IN ACCORDANCE WITH TABLE 1511.7. |
| |
| 36) A7.02 DOESN'T HAVE ANY INFORMATION |
| FOR SHAFT ENCLOSURES. 705.2.2 ALL OPEN- |
| INGS THROUGH THE FLOOR AND PENETRATIONS |
| THROUGH THE FLOOR SHALL BE PROTECTED BY |
| A SHAFT ENCLOSURE IN ACCORDANCE WITH |
| 705.2.3. |
| |
| 37)BEFORE A PERMIT TO CONSTRUCT, MAY |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIP- |
| TION OF THE REVISION MADE, IDENTIFYING |
| THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGE MAY BE FOUND, WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| JIM WITMER |
| BUILDING PLAN REVIEW |
| (561)805-6715 |
| FAX: (561)659-8026 |
| 3 |