Plan Review Details - Permit 04031546
Plan Review Stops For Permit 04031546
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-04-16 Cont ID  
Sent By jleech Date 2004-07-01 Time 18:26 Rev Time 0.50
Received By alange Date 2004-04-16 Time 09:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-06-19 Cont ID  
Sent By jleahy Date 2004-06-19 Time 18:15 Rev Time 0.30
Received By jleahy Date 2004-06-19 Time 18:15 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-06 Cont ID  
Sent By csiegber Date 2004-06-18 Time 14:44 Rev Time 0.50
Received By btrobaug Date 2004-04-06 Time 07:23 Sent To  
Notes
2004-04-06 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
  
 PLEASE SUBMIT PLANS,ELECTRICAL CALCULAT-
 IONS FOR THE INTENDED SCOPE OF WORK PER
 104.1.3, 104.2.1 FLORIDA BUILDING CODE,
 2001 AND 215.5 NEC 2002. THIS WORK MUST
 BE PERMITTED TO, AND INSTALLED BY AN ELE
 CTRICAL CONTRACTOR PURSUANT TO CHAPTER
 489 FLORIDA STATUTES.
  
 A RISER DIAGRAM IS REQUIRED FOR THE NEW
 SERVICE.
  
 NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-06-18 Cont ID  
Sent By csiegber Date 2004-06-18 Time 14:42 Rev Time 0.00
Received By csiegber Date 2004-06-18 Time 14:42 Sent To E
Notes
2004-06-18 00:00:00TO BT BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-02 Cont ID  
Sent By csiegber Date 2004-04-02 Time 12:15 Rev Time 0.00
Received By csiegber Date 2004-04-02 Time 12:15 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-30 Cont ID  
Sent By mmclean Date 2004-04-02 Time 11:53 Rev Time 0.00
Received By alange Date 2004-03-30 Time 13:56 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-06-21 Cont ID  
Sent By pkrauss Date 2004-06-21 Time 11:16 Rev Time 0.20
Received By pkrauss Date 2004-06-21 Time 11:05 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-04-12 Cont ID  
Sent By jleahy Date 2004-06-19 Time 18:15 Rev Time 0.25
Received By pkrauss Date 2004-04-12 Time 07:19 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2004-07-01 Cont ID  
Sent By jleech Date 2004-07-01 Time 18:26 Rev Time 0.25
Received By jleech Date 2004-07-01 Time 18:26 Sent To B
Notes
2004-07-01 00:00:00NO RISER DIAGRAM SHOWN

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-04-15 Cont ID  
Sent By csiegber Date 2004-06-18 Time 14:42 Rev Time 0.50
Received By kstevens Date 2004-04-15 Time 13:01 Sent To B
Notes
2004-04-15 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) PER 61G1-16.003 THE PERSONAL SEAL,
 SIGNATURE AND DATE OF THE ARCHITECT
 SHALL ON ALLL DOCUMENTS TO BE FILED FOR
 PLUBLIC RECORD. DOCUMENTS SHALL BE SIGN-
 ED PERSONALLY AND SEALED BY THE RESPONS-
 IBLE ARCHITECT. - THE SEAL, SIGNATURE &
 DATE ARE COPIES. ORIGINAL SEAL, SIGNAT-
 URE AND DATE ARE REQUIRED. FS 481.0255
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status N Date 2004-04-12 Cont ID  
Sent By mmclean Date 2004-04-12 Time 15:28 Rev Time 0.00
Received By mmclean Date 2004-04-12 Time 15:28 Sent To B
Notes
2004-04-12 00:00:00GIVEN TO ART LANGE.NO WORK THAT
 REQUIRES ZONING REVIEW ALL WORK INTERIOR

Review Stop Z ZONING
Rev No 1 Status F Date 2004-04-02 Cont ID  
Sent By alange Date 2004-03-30 Time 13:56 Rev Time 0.00
Received By mmclean Date 2004-04-02 Time 11:53 Sent To I
Notes
2004-04-02 00:00:00DENIED, NEED TO PROVIDE 2 COPY OF SURVEY
 SHOWING THE WORK.CALLED CONTR MM