Plan Review Details - Permit 04031496
Plan Review Stops For Permit 04031496
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-04-15 Cont ID  
Sent By alange Date 2004-04-15 Time 16:42 Rev Time 0.50
Received By alange Date 2004-04-15 Time 16:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-12 Cont ID  
Sent By pkrauss Date 2004-04-06 Time 06:56 Rev Time 0.75
Received By alange Date 2004-04-12 Time 11:20 Sent To  
Notes
2004-04-12 00:00:00 
 DENIED
 1.BEDROOM WINDOWS DO NOT MEET EGREES
 OPENING REQUIREMENTS.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2004-04-14 Cont ID  
Sent By dpalmer Date 2004-04-14 Time 13:58 Rev Time 0.25
Received By dpalmer Date 2004-04-14 Time 13:58 Sent To  
Notes
2004-04-14 00:00:00ELECTRICCAL TO BE DONE UNDER SEPARATE
 PERMIT. NO ELECTRICAL CONT SIGNED ON.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-03 Cont ID  
Sent By csiegber Date 2004-04-01 Time 11:32 Rev Time 0.50
Received By btrobaug Date 2004-04-03 Time 08:54 Sent To P
Notes
2004-04-03 00:00:00 
 SUBMIT PLANS AND CALCULATIONS FOR THE
 INTENDED SCOPE OF WORK PER 104.1.3,
 104.2.1 FBC AND 215.5 NEC 2002.
 THIS WORK MUST BE PERMITTED AND
 INSTALLED BY AN ELECTRICAL CONTRACTOR
 PURSUANT TO CH 489FS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-01 Cont ID  
Sent By csiegber Date 2004-04-01 Time 11:32 Rev Time 0.00
Received By csiegber Date 2004-04-01 Time 11:32 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date 2004-04-12 Cont ID  
Sent By mmclean Date 2004-03-31 Time 16:52 Rev Time 0.00
Received By csiegber Date 2004-03-26 Time 16:41 Sent To  
Notes
2004-03-26 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-04-06 Cont ID  
Sent By kstevens Date 2004-04-03 Time 09:39 Rev Time 0.20
Received By pkrauss Date 2004-04-06 Time 06:55 Sent To B
Notes
2004-04-06 00:00:00PLEASE PROVIDE THE FOLLOWING INFORMATION
 WITH MECHANICAL PERMIT APPLICATION:
  
 1.PROVIDE A COMPLETED FORM 600C OR
 ENERGY & MANUAL J CALCALUTIONS FOR
 COMPLIANCE WITH 2001 FBC CHAPTER 13
 SUB-CHAPTER 600.
  
 2.PROVIDE DETAIL OF AHU & CONDENSER
 UNIT LOCATION.
  
 3.PROVIDE DUCT & GRILLE SIZE, MATERIAL
 AND LAYOUT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-04-03 Cont ID  
Sent By btrobaug Date 2004-04-03 Time 08:58 Rev Time 0.25
Received By kstevens Date 2004-04-03 Time 09:38 Sent To M
Notes
2004-04-03 00:00:00NO PLUMBING PLANS SUBMITTED - PLUMBING
 PERMIT REQUIRED

Review Stop Z ZONING
Rev No 1 Status N Date 2004-03-31 Cont ID  
Sent By csiegber Date 2004-03-26 Time 16:41 Rev Time 0.00
Received By mmclean Date 2004-03-31 Time 16:52 Sent To I
Notes
2004-03-31 00:00:00NO ZONING REQUIRED MM