Plan Review Details - Permit 04031481
Plan Review Stops For Permit 04031481
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-04-05 Cont ID  
Sent By pschmitz Date 2004-04-29 Time 18:48 Rev Time 0.50
Received By lsmith Date 2004-04-05 Time 11:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-04-03 Cont ID  
Sent By csiegber Date 2004-04-01 Time 12:51 Rev Time 0.25
Received By btrobaug Date 2004-04-03 Time 08:48 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-16 Cont ID  
Sent By csiegber Date 2004-04-16 Time 16:17 Rev Time 0.00
Received By csiegber Date 2004-04-16 Time 16:17 Sent To P
Notes
2004-04-16 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-01 Cont ID  
Sent By csiegber Date 2004-04-01 Time 12:51 Rev Time 0.00
Received By csiegber Date 2004-04-01 Time 12:51 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-26 Cont ID  
Sent By mmclean Date 2004-03-31 Time 12:20 Rev Time 0.00
Received By csiegber Date 2004-03-26 Time 16:14 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-04-29 Cont ID  
Sent By pschmitz Date 2004-04-29 Time 18:44 Rev Time 1.00
Received By pschmitz Date   Time   Sent To B
Notes
2004-04-29 00:00:00PROVISO:
 BACK FLOW PREVENTER PRIOR TO COMMENCING
 WORK, PES

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-04-03 Cont ID  
Sent By csiegber Date 2004-04-16 Time 16:17 Rev Time 0.50
Received By kstevens Date 2004-04-03 Time 09:26 Sent To B
Notes
2004-04-03 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES)
 2) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER. (ADD TO NOTES/GIVE DETAIL)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-03-31 Cont ID  
Sent By csiegber Date 2004-03-26 Time 16:14 Rev Time 0.00
Received By mmclean Date 2004-03-31 Time 12:20 Sent To I
Notes
***NONE***