Plan Review Details - Permit 04031305
Plan Review Stops For Permit 04031305
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-25 Cont ID  
Sent By csiegber Date 2004-03-25 Time 14:26 Rev Time 0.00
Received By csiegber Date 2004-03-25 Time 14:26 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-04-02 Cont ID  
Sent By csiegber Date 2004-03-25 Time 14:26 Rev Time 0.35
Received By pkrauss Date 2004-04-02 Time 15:05 Sent To  
Notes
2004-04-02 00:00:00PROVISO:
 RETURN AIR FROM THE MASTER BEDROOM SHALL
 BE A MINIMUM OF 10" - REVISED 2001
 FBC(M) 601.4 EXCEPTION #1 & 3.ALL
 SUPPLY AIR INTO THE MASTER SUITE IS TO
 BE INCLUDED FOR THE TOTAL SUPPLY AIR TO
 THAT AREA.RETURN AIR SHALL BE 1 1/2
 TIMES THE CROSS SECTIONAL AREA (SQ IN)
 OF THE SUPPLY TO THAT AREA.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.