Plan Review Details - Permit 04031253
Plan Review Stops For Permit 04031253
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-04-16 Cont ID  
Sent By jwitmer Date 2004-04-16 Time 07:28 Rev Time 3.00
Received By jwitmer Date 2004-04-15 Time 15:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-04-15 Cont ID  
Sent By dpalmer Date 2004-04-15 Time 07:20 Rev Time 1.00
Received By dpalmer Date 2004-04-15 Time 06:53 Sent To  
Notes
2004-04-15 00:00:00REDLINED, WORK IN-SCOPE OF THIS PERMIT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-03-26 Cont ID  
Sent By mcarsill Date 2004-03-26 Time 16:07 Rev Time 0.00
Received By mcarsill Date 2004-03-26 Time 16:07 Sent To  
Notes
2004-03-26 00:00:001) PROVIDE SEPARATE PLANS AND PERMITS
 FOR KITCHEN HOOD, DUCT AND SUPPRESSION
 SYSTEM REMODEL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-09-15 Cont ID  
Sent By csiegber Date 2004-09-15 Time 16:03 Rev Time 0.00
Received By csiegber Date 2004-09-15 Time 16:03 Sent To P
Notes
2004-09-15 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-09-15 Cont ID  
Sent By csiegber Date 2004-09-15 Time 09:26 Rev Time 0.00
Received By csiegber Date 2004-09-15 Time 09:26 Sent To  
Notes
2004-09-15 00:00:00TO COMM BD#

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-06-28 Cont ID  
Sent By csiegber Date 2004-06-28 Time 15:54 Rev Time 0.00
Received By csiegber Date 2004-06-28 Time 15:54 Sent To P
Notes
2004-06-28 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-05-17 Cont ID  
Sent By csiegber Date 2004-05-17 Time 08:49 Rev Time 0.00
Received By csiegber Date 2004-05-17 Time 08:49 Sent To  
Notes
2004-05-17 00:00:00TO KS BOX/RESUB
 TO COMM BD#18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-25 Cont ID  
Sent By csiegber Date 2004-03-25 Time 08:00 Rev Time 0.00
Received By csiegber Date 2004-03-25 Time 08:00 Sent To  
Notes
2004-03-25 00:00:00TO COMM BD#35

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2004-06-01 Cont ID  
Sent By pkrauss Date 2004-06-01 Time 10:40 Rev Time 0.15
Received By pkrauss Date 2004-06-01 Time 10:40 Sent To  
Notes
2004-06-01 00:00:00NO MECHANICAL PLANS OR PERMIT WITH THIS
 APPLICATION.
 MECHHOOD & SUPPRESSION UNDER SEPARATE
 PERMIT WITH PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-04-15 Cont ID  
Sent By pkrauss Date 2004-04-14 Time 07:01 Rev Time 1.10
Received By pkrauss Date 2004-04-14 Time 06:44 Sent To  
Notes
2004-04-14 00:00:00PERMIT TO BE APPLIED FOR SEPARATELY,
 PLANS TO BE SUBMITTED WITH PERMIT
 APPLICATION.
 1.PLAN SHEET MP303 INDICATES DUCT WORK
 FOR HOOD #1.PLEASE PROVIDE DUCT LAYOUT
 FOR HOOD #2.
  
 2.PLEASE INDICATE ELEVATION OF GREASE
 DUCT.PLAN SHEET MP303 & K-4 STATE THE
 FANS ARE ON THE ROOF.PROVIDE DETAIL
 OF CLEARANCE TO COMBUSTIBLES OR THE
 CLEARANCE REDUCTION METHOD THAT WILL
 BE USED (I.E. SHAFT, FIRE WRAP, FLAMEBAR
 DUCT?).
  
 3.SEPARATE PERMIT REQUIRED FOR THE
 HOOD & FIRE SUPPRESSION.CONTRACTOR IS
 NOT SIGNED ON WITH BUILDING PERMIT.
  
 4.PROVIDE INSTALLATION DETAIL FOR THE
 ROOF MOUNTED FANS. PLANS NOTE A 10 FT
 SEPARATION BETWEEN EXHAUST & FRESH AIR
 INTAKES.
  
 5.EXHAUST FANS ARE TO BE A MINIMUM OF
 40" ABOVE THE THE ROOF SURFACE PER NFPA
 96.
  
 6.AIR VELOCITY THROUGH THE GREASE DUCT
 SYSTEMS SHALL BE NOT LESS THAN 1,500 FPM
 & NOT GREATER THAN 2,500 FPM. 2001 FBC/M
 506.3.6
  
 7.PLEASE PROVIDE DETAIL FOR THE ANSUL
 SYSTEM FOR HOOD #2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 4 Status F Date 2004-10-14 Cont ID  
Sent By kstevens Date 2004-10-14 Time 10:15 Rev Time 2.50
Received By kstevens Date 2004-10-14 Time 10:15 Sent To  
Notes
2004-10-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FBC-2001 CHAPTER 1
  
  
 FROM PREVIOUS REVIEWS NUMBERS 1 & 2
 6) SHTS K1, K2, K3, & K4 - IF THE DESIGN
 PROFESSIONAL IS AN ARCHITECT OR ENGINEER
 LEGALLY REGISTERED UNDER THE LAWS OF THE
 STATE REGULATING THE PRACTICE OF ARCHIT-
 ECTURE OR ENGINEERING, THEN HE/SHE SHALL
 AFFIX HIS/HER OFFICIAL SEAL TO SAID
 DRAWINGS, SPECIFICATIONS AND ACCOMPANY-
 ING DATA AS REQUIRED BY FLORIDA STATUTE.
 SECTION 104.2.2
 *******NEW COMMENTS*******
 1D) ONLY ONE COPY OF SHTS K1, K2, K3, &
 K4, WERE SUBMITTED WITH THE DBPR STAMP.
 MINIMUM OF TWO SETS ARE REQUIRED AND THE
 WORK SHEETS FROM DBPR ATTACHED TO EACH
 SET FOR REVIEW ARE REQUIRED. SECTION
 104.2.1
 2D) INDICATE THE TABLE USED IN THE FBC-
 2001 FUEL GAS CODE FOR THE SIZING OF THE
 GAS PIPING. MOST REMOTE FIXTURE FROM THE
 METER APPEARS TO BE THE POOL HEATER. ALL
 PIPING SHALL BE SIZED FROM THIS DISTANCE
 (MIN. 430' NEXT HIGHEST LENGTH IS 500')
 3D) SHT MP3O3-1 SHOWS 2.5 PSI METER. ALL
 NATURAL GAS SIZING TABLES ARE 2 PSI.
 PLEASE CLARIFY METER PRESSURE.
 4D) SUBMIT MANUF. SHEETS FOR GAS REGUL-
 ATORS.
 5D) SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 553.80(2)(B)
 ********WHEN RESUBMITTING PLANS*********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION. - LOOSE SHEETS NOT ACCEPT-
 ABLE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-07-17 Cont ID  
Sent By csiegber Date 2004-09-15 Time 16:03 Rev Time 1.50
Received By kstevens Date 2004-07-17 Time 10:27 Sent To  
Notes
2004-07-17 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FBC-2001 FUEL GAS
  
 1) BY REMOVING THE KITCHEN DRAWINGS, THE
 SHEETS WITH THE DBPR PLAN REVIEW STAMP,
 REQUIRED FOR PLAN REVIEW HAVE BEEN RE-
 MOVED.
 2) FROM PREVIOUS REVIEWS: TOTAL BTU'S ON
 GAS SYSTEM AND TOTAL DEVELOPED LENGTH
 (MOST REMOTE FROM METER) SHALL BE PRO-
 VIDED TO REVIEW GAS PLANS. SUBMIT A GAS
 RISER ISOMETRIC SHOWING EXISTING PIPING
 WITH PIPE SIZE, INDICATE THE DISTANCE TO
 THE MOST REMOTE OUTLET FROM THE METER IN
 THE SYSTEM.
 3) MANUF. SHEETS FOR THE GAS APPLIANCES
 WERE NOT SUBMITTED AND ARE REQUIRED FOR
 GAS REVIEW. THESE WHERE SUBMITTED EARL-
 IER BUT WERE NOT RESUBMITTED AT THIS
 TIME.
 4) I WILL TRY TO CONTACT R. COMPO CON-
 CERNING THE GREASE INTERCEPTORS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-06-03 Cont ID  
Sent By csiegber Date 2004-06-28 Time 15:54 Rev Time 1.50
Received By kstevens Date 2004-06-03 Time 09:46 Sent To  
Notes
2004-06-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1) FROM PREVIOUS REVIEW: SHT K-2 P-14, 3
 SHOWN ON FLOOR PLAN, BUT PLUBMING SCHED-
 ULE QUANTITY SHOWS 2. - PLANS SHALL BE
 CHANGED TO CORRELATE INFORMATION ON THE
 FLOOR PLAN AND PLUMBING SCHEDULE. - ALL
 OTHER INFORMATION FOR BAR AREA SHALL BE
 DELETED FROM PLAN AND SUBMITTED AS A
 REVISION UNDER PERMIT NUMBER FOR 2B.
 SECTION 104.2.1
 3) FROM PREVIOUS REVIEW: SHT MP 303 THE
 WATER RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. WATER TO P-19 CONNECTS DOWN-
 STREAM OF P-14 ON FLOOR PLAN, BUT UP-
 STREAM ON WATER RISER DIAGRAM. PLEASE
 CORRELATE PLANS. SECTION 104.2.1
 4) FROM PREVIOUS REVIEW: GREASE INTER-
 CEPTOR SHALL BE SIZED BY RODNEY COMPO,
 ENVIRONMENTAL COMPLIANCE. WASTE ORD.
 2938-96. PHONE #(561) 837-4074. NO INDI-
 CATION THAT MR. COMPO HAS BEEN CONTACTED
 5D) FROM PREVIOUS REVIEW: BTU LOAD OF
 EACH APPLIANCE AND TOTAL BTU LOAD ON THE
 SYSTEM. - IS THIS THE TOTAL GAS SYSTEM?
 5F) INDICATE THE DELIVER PRESSURE PER
 FBC-2001 FUEL GAS CODE SEC. 402.2 RES-
 PONSE INDICATES 2-5. PLEASE INDICATE
 PRESSURE AS THIS WOULD INDICATE VARIBLE
 PRESSURE IN SYSTEM. FROM PREVIOUS REVIEW
 5J) FROM PREVIOUS REVIEW: UNION TO BE
 DOWNSTREAM OF MANUAL VALVE. NO UNION
 SHOWN. - SAFETY SHUTOFF VALVE SHALL BE
 PROVIDED WITH READY ACCESS. NOT UNDER
 THE HOOD AND BEHIND GAS EQUIPMENT.
 SECTION 631.13.5
 6) FROM PREVIOUS REVIEW: SHTS K1, K2, K3
 & K4 - IF THE DESIGN PROFESSIONAL IS AN
 ARCHITECT OR ENGINEER LEGALLY REGISTERED
 UNDER THE LAWS OF THIS STATE REGULATING
 THE PRACTICE OF ARCHITECTURE OR ENGIN-
 EERING, THEN HE/SHE SHALL AFFIX HIS/HER
 OFFICIAL SEAL TO SAID DRAWINGS, SPECIFI-
 CATIONS AND ACCOMPANYING DATA, AS RE-
 QUIRED BY FLORIDA STATUTE. SEC. 104.2.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-03-29 Cont ID  
Sent By csiegber Date 2004-05-17 Time 08:49 Rev Time 2.00
Received By kstevens Date 2004-03-29 Time 11:59 Sent To  
Notes
2004-03-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT K-2 P-14, 3 SHOWN ON FLOOR PLAN,
 BUT PLUMBING SCHEDULE QUANTITY SHOWS 2.
 P-46 NOT FOUND ON FLOOR PLAN.
 P-47, 2 SHOWN ON FLOOR PLAN IN THE
 LOUNGE AREA, BUT SCHEDULE QUANTITY SHOWS
 1. PLEASE CLAIRFY. SECTION 104.2.1
 2) SHT MP 303 SANT. RISER DOES NOT RE-
 FLECT THE FLOOR PLAN. P-19 FIXTURES CON-
 NECT DOWNSTREAM OF P-14 ON FLOOR PLAN,
 BUT UPSTREAM OF P-14 ON RISER DIAGRAM.
 PLEASE CLAIRFY. SECTION 104.2.1
 3) SHT MP 303 WATER RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. SEE PREVIOUS
 COMMENT, AND P-5 WATER ON FLOOR PLAN
 SHOWS P-5 UPSTREAM OF LAST FLOOR SINK,
 BUT BETWEEN THE P-14'S ON RISER DIAGRAM.
 PLEASE CLAIRFY. SECTION 104.2.1
 4) GREASE INTECEPTOR REQUIRED SHALL BE
 SIZED BY RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE. WASTE ORD #2938-96. PHONE #
 (561) 837-4074
 5) THE FOLLOWING ARE REQUIREMENTS FOR
 THE GAS PERMIT. SEPARATE GAS PERMIT REQD
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. MAKE SURE GAS RISER IS IN
 ISOMETRIC FORM.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF USED).
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34). - BTU'S NOT SHOWN FOR EXHAUST
 AND MAKE UP AIR SYSTEM.
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). - MAKE SURE
 TO GIVE THE DISTANCE TO THE MOST REMOTE
 OUTLET IN THE BUILDING, NOT IN THE KIT-
 CHEN.
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 J. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. SHOW ON ISO
 METRIC.
 6) SHEETS K1, K2, & K,3 ARE NOT SIGNED
 AND SEALED AS REQUIRED PER 61G1-16.001
 7) SHEET MP 303 CERTIFICATE OF AUTHORIZ-
 ATION REQUIRED PER 61G15-23.002(2) AND
 FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]