Plan Review Stops For Permit 04031163 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2004-07-28 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-08-04 |
Time |
10:41 |
Rev Time |
1.00 |
Received By |
alange |
Date |
2004-07-28 |
Time |
13:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2004-04-09 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2004-07-27 |
Time |
19:54 |
Rev Time |
2.00 |
Received By |
alange |
Date |
2004-04-09 |
Time |
09:00 |
Sent To |
|
|
Notes |
2004-04-09 00:00:00 | DENIED | | 1.BEFORE A PERMIT TO CONSTRUCT, MAY | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | SET OF PLANS MUST BE STAMPED BY THAT | | OFFICE, AND A COPY OF THE PAID RECEIPT | | ATTACHED TO THE PERMIT APPLICATION. | | PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | | | 2. THE NOTICE OF COMMENCEMENT SHALL BE | | RECORDED AT PALM BEACH COUNTY | | COURTHOUSEAND A COPY SUBMITTED TO THIS | | OFFICE | | BEFORE A PERMIT CAN BE ISSUED.BLANK | | FORMS ARE AVAILABLE FROM THIS OFFICE. | | | | 3.SUBMIT AN ELEVATION CERTIFICATE. | | STRUCTURE IS IN A FLOOD ZONE. | | | | 4.BUILDING VALUATION OF $15,000 | | TOO LOW.VALUE HAS BEEN RECALCULATED | | BASED UPON SBCCI BUILDING VALUATION | | DATA TO $68,802.ADITIONAL PERMIT FEES | | ARE DUE. | | | | 5.CITY OF WEST PALM BEACH CODE | | SEC. 94-546 (B) (1) PROVISIONS FOR | | FLOOD HAZARD REDUCTION. | | RESIDENTIOAL CONSTRUCTION. ALL NEW | | CONSTRUCTION OR SUBSTANTIAL IMPROVEMENT | | OF ANY EXISTING RESIDENTIAL STRUCTURE | | SHALL HAVE THE LOWEST FLOOR, INCLUDING | | BASEMENT, ELEVATED TO SIX INCHES ABOVE | | THE BASE FLOOD ELEVATION. SEE ATTACHED | | PAGES. | | | | 6. WINDOW BUCKS SHALL COMPLY WITH | | FBC 1707.4.4.2 BUCKS SHALL EXTEND BEYOND | | THE INTERIOR FACE OF THE WINDOW FRAME | | SUCH THAT FULL SUPPORT OF THE FRAME IS | | PROVIDED.HAVE BUCK DETAIL REFLECT THIS | | | | ANY QUESTIONS CALL ME. | | | | ART LANGE | | BUILDING PLANS EXAMINER | | 805-6672 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2006-04-20 |
Time |
07:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2006-03-27 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2006-03-27 |
Time |
07:42 |
Rev Time |
0.33 |
Received By |
btrobaug |
Date |
2006-03-27 |
Time |
07:39 |
Sent To |
PC |
|
Notes |
2006-03-27 00:00:00 | | | | | ALL CHANGES TO THE PLAN MUST BE MADE BY | | THE DESIGNER OF RECORD. HAVE PLANS | | REDRAWN AND RESEALED BY THE ARCHITECT | | AND RESUBMIT | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2004-07-21 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2004-07-21 |
Time |
11:04 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2004-07-21 |
Time |
10:30 |
Sent To |
P |
|
Notes |
2004-07-21 00:00:00 | | | PROVISO | | ~~~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | THE DEN LISTS "EXISTING ELECTRICAL TO | | REMAIN". THERE IS WORK IN THIS ROOM, SEE | | SHEET A-1, THIS ROOM MUST COMPLY WITH | | 210.52. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2004-06-14 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-07-19 |
Time |
12:44 |
Rev Time |
1.00 |
Received By |
btrobaug |
Date |
2004-04-02 |
Time |
11:55 |
Sent To |
M |
|
Notes |
2004-04-02 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE PANEL SCHEDULE NOTES INDICATE A | | 200 AMP SERVICE. THE RISER IS LABLED | | 150 AMP. PLEASE CORRELATE. | | | | 2} PER 220.31 THERE IS NO DEMAND TAKEN | | FOR THE A/C. ALSO NOTE THAT THIS LOAD | | CALCULATION ALLOWS ALL BUT THE 1ST | | 8000VA TO BE TAKEN @ 40%. RECALCULATE | | LOAD AND INDICATE METHOD USED. (ARTICLE | | #.) | | | | 3} THE LOADS FOR THE HEAT STRIP & COND. | | UNIT ARE REVERSED ON THE SCHEDULE. | | | | 4} RECEPTACLES NEED TO BE ADDED IN THE | | BEDROOM TO COMPLY WITH 210.52(A). | | | | 5} PLEASE PROVIDE A PANEL SCHEDULE SO | | THAT BRANCH CIRCUIT CODE COMPLIANCE CAN | | BE DETERMINED. | | | | 6} PLEASE LIST ALL THE REQ'D | | DEDICATED BATH(S) CIRCUIT(S) ON PANEL | | SCHEDULE. PER 210.52D, 210.11C3 | | | | 7} PLEASE LIST THE REQ'D ARC | | FAULT PROTECTED CURCUIT(S) ON PANEL | | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" | | IN BEDROOMS ARE TO BE PROTECTED , | | INCLUDING, LTS, RECEPTS, SD'S ETC. | | | | 8} ISLAND RECEPTACLES MUST BE GFI | | PER210.8(A)(6). | | | | 9} A RECEPTACLE MUST BE ADDED AT THE | | BACK OF THE HOUSE (OUTSIDE PER | | 210.52(E). | | | | 10} SEE PLUMBING COMMENTS FOR TITLE | | BLOCK & SEAL REQUIREMENTS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL, | | ALSO NOTE CODE REDLINED SET OF PLANS. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
10 |
Status |
N |
Date |
2006-06-12 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-06-12 |
Time |
08:42 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-06-12 |
Time |
08:42 |
Sent To |
M |
|
Notes |
2006-06-12 00:00:00 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
9 |
Status |
N |
Date |
2006-05-23 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-05-23 |
Time |
11:39 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-05-23 |
Time |
11:39 |
Sent To |
M |
|
Notes |
2006-05-23 00:00:00 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
8 |
Status |
N |
Date |
2006-04-15 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-04-15 |
Time |
14:24 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-04-15 |
Time |
14:24 |
Sent To |
E |
|
Notes |
2006-04-15 00:00:00 | TO "BTROBAUG" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
7 |
Status |
N |
Date |
2006-03-17 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-03-17 |
Time |
16:51 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-03-17 |
Time |
16:51 |
Sent To |
E |
|
Notes |
2006-03-17 00:00:00 | TO "BTROBAUG" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2004-08-04 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-08-04 |
Time |
10:41 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-08-04 |
Time |
10:41 |
Sent To |
B |
|
Notes |
2004-08-04 00:00:00 | TO AL DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2004-08-02 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2004-08-03 |
Time |
16:17 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-08-02 |
Time |
14:10 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2004-07-19 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-07-19 |
Time |
12:44 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-07-19 |
Time |
12:44 |
Sent To |
E |
|
Notes |
2004-07-19 00:00:00 | TO BT DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2004-07-12 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2004-07-19 |
Time |
11:16 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-07-12 |
Time |
14:12 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2004-03-26 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-03-26 |
Time |
16:44 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-03-26 |
Time |
16:44 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2004-03-23 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2004-03-26 |
Time |
16:06 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-03-23 |
Time |
08:47 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2006-06-19 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-06-19 |
Time |
14:55 |
Rev Time |
0.25 |
Received By |
tgordon |
Date |
2006-06-19 |
Time |
14:55 |
Sent To |
|
|
Notes |
2006-06-19 00:00:00 | REVISION TO MECH. PLANS. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2006-05-25 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-05-25 |
Time |
10:31 |
Rev Time |
0.45 |
Received By |
tgordon |
Date |
2006-05-25 |
Time |
10:31 |
Sent To |
|
|
Notes |
2006-05-25 00:00:00 | MECHANICAL REVISION | | *** DENIED *** | | 1) TWO A/C SYSTEMS ARE LISTED ON PLANS | | ONLY ONE IS TO BE INSTALLED, PLEASE | | CORRECT. | | | | 2) PLEASE SHOW SUPPLY AIR DUCT SIZES TO | | MIXING BOX, CLOSET, AND BATHROOM. | | | | 3) PLEASE EXPLAIN WHAT APPLIANCE THE 6" | | VTO IS FOR. | | | | 4) PLEASE SHOW JOB ADDRESS ON MECHANICAL | | PLANS. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2004-04-05 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2004-06-14 |
Time |
14:40 |
Rev Time |
0.30 |
Received By |
pkrauss |
Date |
2004-04-05 |
Time |
15:22 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2004-07-27 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2004-07-27 |
Time |
19:54 |
Rev Time |
0.33 |
Received By |
jleech |
Date |
2004-07-27 |
Time |
19:54 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2004-03-31 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2004-07-21 |
Time |
11:04 |
Rev Time |
0.33 |
Received By |
kstevens |
Date |
2004-03-31 |
Time |
15:05 |
Sent To |
E |
|
Notes |
2004-03-31 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1) SHT A-2 SANITARY RISER DIAGRAM DOES | | NOT MEET CODE REQUIREMENTS. | | A) MINIMUM 3" TO WATER CLOSET. TABLE | | 710.1(1) FOOTNOTE A. | | B) CLEAN OUT REQUIRED 4' ABOVE FLOOR AT | | WASHMACHINE. SECTION 708.9 | | C) STANDPIPE REQUIRED AT WASH MACHINE | | SECTIONS 1002.1 & 802.4. | | D) WASH MACHINE SHALL CONNECT BELOW | | WASTE ARM OF THE KITCHEN SINK. SECTION | | 706.3 | | 2)ENGINEERS SHALL LEGIBLY INDICATE THEIR | | NAME, ADDRESS AND LICENSE NUMBER ON EACH | | SHEET. IF PRACTICING THROUGH A DULY | | AUTHORIZED ENGINEERING BUSINESS, ENGIN- | | EERS, ENGINEERS SHALL LEGIBLY INDICATE | | THEIR NAME AND LICENSE NUMBER, AS WELL | | AS, THE NAME, ADDRESS AND CERTIFICATE OF | | AUTHORIZATION NUMBER OF THE ENGINEERING | | BUSINESS ON EACH SHEET. A TITLE BLOCK | | WILL SATISFY THIS REQUIREMENT. FAC | | 61G15-23.002(2) - FS 471.025 | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2004-08-03 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2004-08-03 |
Time |
16:16 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2004-08-03 |
Time |
16:16 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2004-07-19 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-08-02 |
Time |
14:10 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2004-07-19 |
Time |
11:16 |
Sent To |
I |
|
Notes |
2004-07-19 00:00:00 | DENIED, NEED TO HAVE 6FT SEPARATION FROM | | ADDITION AND SHED.CALLED & LEFT MSG |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2004-03-26 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-07-12 |
Time |
14:12 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2004-03-26 |
Time |
16:06 |
Sent To |
I |
|
Notes |
2004-03-26 00:00:00 | DENIED, SITE PLAN NOT TO SCALE.NEED TO | | PROVIDE A SITE PLAN TO SCALE WITH SET | | BACKS OR TWO COPY OF SURVEY SHOWING | | THE ADDITION WITH SETBACKS CALLED OWNER |
|
|