Plan Review Details - Permit 04031090
Plan Review Stops For Permit 04031090
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-08-13 Cont ID  
Sent By shill Date 2004-08-13 Time 12:00 Rev Time 1.00
Received By shill Date 2004-08-13 Time 12:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2004-07-20 Cont ID  
Sent By csiegber Date 2004-08-06 Time 15:49 Rev Time 2.00
Received By shill Date 2004-07-13 Time 12:32 Sent To  
Notes
2004-07-13 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 ALL COMMENTS ARE REGARDING THE
 APPLICATION FOR LOCAL PRODUCT APPROVAL,
 STEEL EDGE OUTSWING GLAZED ENTRY DOOR.
 NOTE - SEE ATTACHED CHECKLIST FROM THE
 WWW.FLORIDABUILDING.ORG WEBSITE.
  
 1.)INDICATE APPROVAL METHOD (LINE 1).
  
 2.)PROVIDE A CERTIFICATE OF
 INDEPENDENCE FOR THE EVALUATOR (CERTIFI-
 CATION AGENCY), FAC9B72.040(5)(G),
 FAC9B72.110 (SEE ATTACHED).
  
 3.)PROVIDE AN ORIGINAL APPLICATION
 FOR LOCAL PRODUCT APPROVAL.
  
 ***NO RESUB FEE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-06-23 Cont ID  
Sent By csiegber Date 2004-06-25 Time 15:14 Rev Time 1.00
Received By shill Date 2004-06-23 Time 15:04 Sent To  
Notes
2004-06-23 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE COVER SHEET CONTAINS THE NAME
 OF DAVID LAWRENCE ARCHITECTURE INC.
 A CERTIFICATE OF AUTHORIZATION IS
 REQUIRED, SEE PREVIOUS LIST.
  
 2.)SEE PREVIOUS LIST, ITEM #3.THE
 SHUTTER SCHEDULE AND KEY PLAN DO NOT
 CORRELATE WITH THE FLOOR PLAN.FOR
 INSTANCE, OPEINING D ON THE FLOOR PLAN
 IS SHOWN AS A 2'8X5'3 WINDOW; ON THE
 SHUTTER SCHEDULE IT IS OPENING 6, 78X80.
 OPENING #7 IS ALSO INCORRECT.PLEASE
 CHECK ALL OPENING SIZES.
  
 3.)SEE PREVIOUS LIST, ITEM #5.NOW
 THE STATE PRODUCT APPROVAL HAS AN
 APPROVED STATUS BUT THE TEST REPORT
 IS MISSING FOR THE MULLIONS.
  
 4.)SEE PREVIOUS LIST, ITEM #4. PROVIDE
 THE STATE PRODUCT APPROVAL FOR THE
 ODL DOOR.I WAS UNABLE TO DETERMINE
 WHICH PRODUCT APPROVAL, IF ANY, WAS THE
 CORRECT ONE ON THE FLORIDA STATE
 WEBSITE.CONTACTING THE ODL TECHNICAL
 REPRESENTATIVE, [email protected], MAY
 ASSIST IN DETERMINING THE CORRECT
 PRODUCT APPROVAL AND TEST REPORT THAT
 YOU NEED TO SUBMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-06-04 Cont ID  
Sent By dpalmer Date 2004-06-22 Time 19:22 Rev Time 2.00
Received By shill Date 2004-06-04 Time 08:32 Sent To  
Notes
2004-06-04 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LIST.DAVID
 LAWRENCE ARCHITECTURE INC. IS REQUIRED
 TO HAVE A CERTIFICATE OF AUTHORIZATION
 (SHEET 1).PLEASE PROVIDE.MASTERS
 CANNOT BE REDLINED, SEE SHEET 9.1 TITLE
 BLOCK.
  
 2.)EMERGENCY ESCAPE SHALL BE PROVIDED
 DURING THE THREAT OF A STORM, TO BE
 PROVIDED ON THE FIRST FLOOR, FBC1005.4.5
 THE IMPACT DOOR IS ON THE SECOND FLOOR.
  
 3.)THE SHUTTER SCHEDULE AND KEY PLAN
 DO NOT CORRELATE WITH THE FLOOR PLAN.
 THE DOOR APPEARS TO BE IN THE WRONG
 LOCATION, 2ND FLOOR.EMERGENCY ESCAPE
 IS REQUIRED FBC1005.4.5.
  
 4.)DO NOT STAPLE DIFFERENT PRODUCT
 APPROVALS TOGETHER.EACH PRODUCT
 APPROVAL SHOULD INCLUDE THE FLORIDA
 STATEWIDE, LOCAL OR SITE SPECIFIC WITH
 A TEST REPORT.SEE PREVIOUS LIST IN
 REGARDS TO THE ODL DOOR, STILL NO
 STATE APPROVAL SUBMITTED.
  
 5.)THE STATE PRODUCT APPROVAL FOR
 THE MULLIONS IS PENDING.PLEASE PROVIDE
 A CURRENT (APPROVED STATUS) PRODUCT
 APPROVAL.ALSO THE DRAWINGS ARE FOR
 NORANDEX, NOT SIMONTON MULLIONS.
  
 6.)PROVIDE A TITLE BLOCK FOR THE
 ENGINEER ON THE TRUSS LAYOUT PAGE.
 SEE DESIGN CRITERIA, MASTERS CANNOT BE
 REDLINED.
  
 7.)TRUSS LOADING ON SHEET 3.1
 CONFLICTS WITH THE ENGINEERING.REVISE
 EITHER THE PLAN OR THE TRUSS ENGINEERING
 SO THAT THE TWO ARE CONSISTENT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-05-04 Cont ID  
Sent By dpalmer Date 2004-06-03 Time 16:33 Rev Time 2.00
Received By shill Date 2004-05-04 Time 09:46 Sent To M
Notes
2004-05-04 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)DAVID LAWRENCE ARCHITECTURE INC.
 IS REQUIRED TO HAVE A CERTIFICATE OF
 AUTHORIZATION.PROVIDE THE NUMBER
 (SHEET 1).IF YOU REMOVE THE NAME,
 MASTERS CANNOT BE REDLINED (CLEAN
 ORIGINALS REQUIRED), EACH SHEET.
  
 2.)SEE PREVIOUS LIST, ITEM #4.THE
 PRODUCT APPROVALS SUBMITTED FOR DOUBLE
 DOORS ARE INSWING OR IMPACT.ARE YOU
 USING IMPACT FOR THE REAR DOUBLE DOOR
 AS WELL AS THE FRONT?
  
 3.)WHERE IS THE KEY PLAN FOR THE
 HURRICANE INSTALLATION SCHEDULE?IS
 THE DOOR REQUIRED TO BE IMPACT STILL ON
 THIS SCHEDULE?
  
 4.)FLORIDA STATEWIDE, LOCAL OR SITE
 SPECIFIC PRODUCT APPROVAL REQUIRED FOR
 ALL WINDOWS AND DOORS.PLEASE PROVIDE
 FOR THE ODL IMPACT DOOR.
  
 5.)THE PRODUCT APPROVAL SUBMITTED FOR
 THE SINGLE IMPACT GLASS DOOR IS LIMITED
 TO 3'0, DOOR ON THE PLAN IS 3'3".
  
 6.)THE NON IMPACT DOOR PRODUCT
 APPROVAL SUBMITTED IS ALSO LIMITED IN
 SIZE TO 3'0.THE 2ND FLOOR DOOR IS 3'3.
  
 7.)THE SIMONTON WINDOW PRODUCT
 APPROVALS ARE ILLEGIBLE AND REQUIRE
 FL STATE, LOCAL OR SITE SPECIFIC
 PRODUCT APPROVAL.ONE SHEET WAS FOR
 A FIXED WINDOW, NO WINDOWS OF THAT
 TYPE ON THE PLAN.THE OTHER WAS FOR
 A SINGLE HUNG; THERE IS ALREADY AN
 APPROVED SINGLE HUNG WINDOW IN THE
 PACKAGE (TRACO).IS THIS AN ALTERNATE?
  
 8.)PROVIDE WINDOW MULLION PRODUCT
 APPROVALS.FL STATE, LOCAL OR SITE
 SPECIFIC REQUIRED IN ADDITION TO THE
 TEST REPORT.
  
 9.)THE TRUSS SHEETS SUBMITTED ARE
 LOOSE.COLLATE, SUBMIT TWO IDENTICAL
 BOUND (STAPLED) COPIES.SOME SHEETS
 ARE LACKING A TITLE BLOCK.A FULL
 SIGNATURE IS REQUIRED, NOT INITIALS PER
 FBPE AND BUILDING OFFICIAL.BCLL IS
 SHOWN AS 0; REVISE TO BE CONSISTENT WITH
 THE PLANS AND FBC TABLE 1604.1.
  
 10.) ADDITIONAL FEES DUE $190, SEE
 ATTACHED BZ238899.THIS IS A MAJOR
 WORKING DRAWING REVIEW, NOT A PERMIT
 APPLICATION WITH RESUBS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-29 Cont ID  
Sent By dpalmer Date 2004-04-27 Time 19:41 Rev Time 2.00
Received By shill Date 2004-03-29 Time 09:32 Sent To  
Notes
2004-03-29 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)ONE MEANS OF EGRESS TO BE PROVIDED
 IN THE EVENT OF A HURRICANE, FBC1005.4.5
  
 2.)GENZ ENGINEERING MUST HAVE A
 CERTIFICATE OF AUTHORIZATION TO
 PRACTICE ENGINEERING.THIS CA NUMBER
 IS TO BE ON EACH SHEET, FAC61G15-23.002.
  
 3.)DOCUMENTS ISSUED BY THE ARCHITECT
 AND FILED FOR PUBLIC RECORD ARE TO
 BE SEALED (ENERGY CALC), FAC61G1-16.001.
  
 4.)THE PRODUCT APPROVALS SUBMITTED
 WERE FOR INSWING DOORS; PLAN SPECIFIES
 OUTSWING.CLARIFY WITH ARCHITECT.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-07-01 Cont ID  
Sent By dpalmer Date 2004-07-01 Time 13:26 Rev Time 0.33
Received By dpalmer Date 2004-07-01 Time 13:24 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-06-22 Cont ID  
Sent By shill Date 2004-06-29 Time 13:00 Rev Time 0.25
Received By dpalmer Date 2004-06-22 Time 19:17 Sent To B
Notes
2004-06-22 00:00:00***** UNSAT *****
  
 1)NOTE: PLEASE SEE NOTE #1 FROM PREVIOUS
 REVIEW. BATH RECEPT IS STILL SHOWN
 CONNECTED TO AN ADDTIONAL HALLWAY RECEPT
 PLEASE SEE 210.52D,210.11C3
 NO OTHER RECEPTS ARE PERMITTED ON THIS
 GFI CIRCUIT.
  
 THESE PLANS ARE FOR A"MASTER" AND NO
 REDLINES CAN BE DONE. PLANS MUST BE 100%
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-06-03 Cont ID  
Sent By csiegber Date 2004-06-18 Time 11:36 Rev Time 0.50
Received By dpalmer Date 2004-06-03 Time 16:33 Sent To B
Notes
2004-06-03 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE RECEPT SHOWN FOR
 SECOND FLOOR BATH. NOW SHOWS RECEPT IN
 BATH CONNECTING TO RECEPT IN HALL UP-
 -STAIRS. APPEARS TO BE A MISPRINT?
  
 2)NOTE: PLEASE ADD NOTE TO RISER NOTE
 #1 TO BE IN SLAB.
  
 CALLED FOR NEW SHEET.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-04-27 Cont ID  
Sent By shill Date 2004-06-02 Time 12:49 Rev Time 0.33
Received By dpalmer Date 2004-04-27 Time 19:41 Sent To B
Notes
2004-04-27 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE 40A OCP FOR OVEN ON
 #10 AWG.
  
 2)NOTE: PLEASE CORRELATE LOAD SHOWN FOR
 AHU, PANEL SCHEDULE SHOWS 11KW AND LOAD
 CALCS INDICATE 10KW. NOTE, MOST "10KW"
 HEATSTRIPS ARE ACTUALY 9.6 AND .4 FOR
 MOTOR OR THERE-ABOUTS.
 MECH PLANS SHOW OCP FOR A/C COND UNIT
 AT 25A'S.
  
 THESE PLANS ARE BEING SUBMITTED FOR
 MASTER PLANS AND CAN NOT BE REDLINED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-03-25 Cont ID  
Sent By shill Date 2004-04-27 Time 11:12 Rev Time 1.00
Received By btrobaug Date 2004-03-25 Time 12:07 Sent To B
Notes
2004-03-25 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE CONDUCTOR SIZE FOR THE SERVICE ON
 THE RISER DIAGRAM IS UNDERSIZED PER
 210.15(B)(6). MUST BE MINIMUM #2/0.
  
 2} PLEASE SEE 250.50 FOR GROUNDING AND
 AMMEND NOTE #4 ON RISER NOTES TO
 INCLUDE COLD WATER PIPE.
  
 3} THE LOAD CALCULATION IS INCORRECT,
 PLEASE RECALCULATE PER 220.3.
  
 4} THE OVEN CALCULATION MUST COMPLY WITH
 220.19, (8 KW MIN).
  
 5} THE NEUTRAL CALCULATION IS INCORRECT
 PER 220.22, SEE REVIEWED SET OF PLANS.
  
 6} THE AMPERAGE FOR ON THE PANEL
 SCHEDULE FOR THE AHU AND THE CU. DO NOT
 CORRELATE WITH THE MECHANICAL PLANS,
 PLEASE REVISE.
  
 7} A RECEPTACLE MUST BE ADDED AT THE CU
 PER 210.63.
  
 8} A SMOKE DETECTOR MUST BE ADDED IN
 "CLOSE PROXIMITY" OF THE STAIRWELL PER
 NFPA-72, AND 905.2.2 FBC.
  
 9} THE SMOKE DETECTOR NEAR THE UPPER
 BATH #2 MUST BE A MINIMUM OF 3' AWAY
 FROM THE DOOR PER 8-1.4.2 NFPA-72.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-09-27 Cont ID  
Sent By adarroug Date 2005-09-27 Time 13:08 Rev Time 0.00
Received By adarroug Date 2005-09-27 Time 13:08 Sent To B
Notes
2005-09-27 00:00:00TO "SHILL" DESK

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2004-08-06 Cont ID  
Sent By csiegber Date 2004-08-06 Time 15:49 Rev Time 0.00
Received By csiegber Date 2004-08-06 Time 15:49 Sent To B
Notes
2004-08-06 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-06-29 Cont ID  
Sent By shill Date 2004-06-29 Time 12:55 Rev Time 0.00
Received By shill Date 2004-06-29 Time 12:55 Sent To E
Notes
2004-06-29 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-06-25 Cont ID  
Sent By csiegber Date 2004-06-25 Time 15:14 Rev Time 0.00
Received By csiegber Date 2004-06-25 Time 15:14 Sent To B
Notes
2004-06-25 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-06-18 Cont ID  
Sent By csiegber Date 2004-06-18 Time 11:36 Rev Time 0.00
Received By csiegber Date 2004-06-18 Time 11:36 Sent To E
Notes
2004-06-18 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-06-02 Cont ID  
Sent By shill Date 2004-06-02 Time 12:49 Rev Time 0.00
Received By shill Date 2004-06-02 Time 12:49 Sent To E
Notes
2004-06-02 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-05-27 Cont ID  
Sent By csiegber Date 2004-05-27 Time 11:00 Rev Time 0.00
Received By csiegber Date 2004-05-27 Time 11:00 Sent To B
Notes
2004-05-27 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-04-27 Cont ID  
Sent By shill Date 2004-04-27 Time 11:12 Rev Time 0.00
Received By shill Date 2004-04-27 Time 11:12 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-22 Cont ID  
Sent By alange Date 2004-04-22 Time 12:37 Rev Time 0.00
Received By alange Date 2004-04-22 Time 12:37 Sent To B
Notes
2004-04-22 00:00:00TO SH DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-25 Cont ID  
Sent By shill Date 2004-03-25 Time 11:28 Rev Time 0.00
Received By shill Date 2004-03-25 Time 11:28 Sent To E
Notes
2004-03-25 00:00:00ROUTED TO WT DESK FOR ELEC REVIEW WITH
 03111252 (SAME PLAN)

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-19 Cont ID  
Sent By csiegber Date 2004-03-19 Time 14:36 Rev Time 0.00
Received By csiegber Date 2004-03-19 Time 14:36 Sent To B
Notes
2004-03-19 00:00:00TO SH DESK/MASTER

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-06-29 Cont ID  
Sent By shill Date 2004-05-04 Time 10:08 Rev Time 0.35
Received By pkrauss Date 2004-06-29 Time 11:26 Sent To B
Notes
2004-05-04 00:00:00APPROVED 3-16-04

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-03-26 Cont ID  
Sent By kstevens Date 2004-03-26 Time 14:29 Rev Time 0.33
Received By kstevens Date 2004-03-26 Time 14:29 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2004-06-02 Cont ID  
Sent By shill Date 2004-06-02 Time 12:50 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
2004-06-02 00:00:00MASTER - DO NOT ISSUE