Plan Review Stops For Permit 04031079 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2004-03-29 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2004-03-23 |
Time |
16:30 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2004-03-29 |
Time |
10:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2004-03-19 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-03-19 |
Time |
12:53 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-03-19 |
Time |
12:53 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2004-03-23 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-03-19 |
Time |
12:53 |
Rev Time |
0.33 |
Received By |
pkrauss |
Date |
2004-03-23 |
Time |
16:12 |
Sent To |
E |
|
Notes |
2004-03-23 00:00:00 | PROVISO: | | 1.AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED PER 2001 FBC(M) | | 307.2.3. | | | | 2.TRANSFER AIR GRILLES INDICATED ON | | THE PLAN ARE NOT PER THE REVISED 2001 | | FBC(M) 601.4 EXCEPTION #2, 50 SQ INCHES | | OF GRILLE AREA TO 100 CFM OF SUPPLY AIR. | | 10" X 10" = 100 SQ IN.PLEASE INCREASE | | TRANSFER GRILLE SIZE TO COMPLY WITH | | CODE REQUIREMENT. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
|