Plan Review Details - Permit 04030630
Plan Review Stops For Permit 04030630
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-03-30 Cont ID  
Sent By kstevens Date 2004-03-29 Time 18:16 Rev Time 0.50
Received By lsmith Date 2004-03-30 Time 13:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-04-03 Cont ID  
Sent By btrobaug Date 2004-04-03 Time 07:27 Rev Time 0.33
Received By btrobaug Date 2004-04-03 Time 07:18 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-03-27 Cont ID  
Sent By csiegber Date 2004-04-02 Time 15:50 Rev Time 0.33
Received By btrobaug Date 2004-03-27 Time 12:31 Sent To P
Notes
2004-03-27 00:00:00 
 THE POOL SPECIFICATIONS INDICATE NO POOL
 HEATER, BUT THE CONTRACT SUBMITTED WITH
 THE APPLICATION INDICATES THERE IS TO
 BE A HEATER. SUBMIT LOAD CALCULATIONS
 FOR THE ELECTRICAL SERVICE, INDICATE
 SIZE OF EXISTING SERVICE, AND SHOW ALL
 LOADS TO BE ADDED WITH THE SCOPE OF
 THIS WORK.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-07-02 Cont ID  
Sent By csiegber Date 2004-07-02 Time 11:25 Rev Time 0.00
Received By csiegber Date 2004-07-02 Time 11:25 Sent To P
Notes
2004-07-02 00:00:00TO KS BOX/REV/HEAT PUMP SPEC SHEET

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-05-12 Cont ID  
Sent By csiegber Date 2004-05-12 Time 09:30 Rev Time 0.00
Received By csiegber Date 2004-05-12 Time 09:30 Sent To P
Notes
2004-05-12 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-02 Cont ID  
Sent By csiegber Date 2004-04-02 Time 15:50 Rev Time 0.00
Received By csiegber Date 2004-04-02 Time 15:50 Sent To E
Notes
2004-04-02 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-23 Cont ID  
Sent By csiegber Date 2004-03-23 Time 11:29 Rev Time 0.00
Received By csiegber Date 2004-03-23 Time 11:29 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-07-24 Cont ID  
Sent By kstevens Date 2004-07-24 Time 13:53 Rev Time 0.50
Received By kstevens Date 2004-07-24 Time 13:53 Sent To  
Notes
2004-07-24 00:00:00REVISION OK - ADDED HEAT PUMP

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-05-27 Cont ID  
Sent By csiegber Date 2004-07-02 Time 11:25 Rev Time 0.50
Received By kstevens Date 2004-05-26 Time 17:31 Sent To Z
Notes
2004-05-27 00:00:00REVISION OK - MOVED LOCATION OF POOL
 EQUIPMENT - DELETED POOL HEATER
2004-05-26 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1) ORIGINAL PLANS SHOW A HEAT PUMP FOR
 THE POOL HEATER. REVISION SHOWS NO HEAT
 PUMP IN SPECIFICATIONS NOR ON THE EQUIP-
 MENT LAYOUT. SHOW HEAT PUMP ON BOTH AS
 SHOWN ON STAMPED SET OF PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-04-09 Cont ID  
Sent By csiegber Date 2004-05-12 Time 09:30 Rev Time 0.33
Received By kstevens Date 2004-04-09 Time 17:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-03-29 Cont ID  
Sent By btrobaug Date 2004-04-03 Time 07:27 Rev Time 0.50
Received By kstevens Date 2004-03-29 Time 18:16 Sent To B
Notes
2004-03-29 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1) PROPOSAL AND MANUF. SPECIFICATION
 SHEETS SHOW HEAT PUMP TO BE INSTALLED.
 EQUIPMENT LAYOUT SHEET AND POOL SPECIF-
 ICATIONS SHEET INDICATE NOT POOL HEATER
 OR HEAT PUMP TO BE INSTALLED. PLEASE
 CLAIRFY.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2004-03-23 Cont ID  
Sent By kstevens Date 2004-05-27 Time 12:41 Rev Time 0.00
Received By mmclean Date 2004-03-23 Time 11:04 Sent To I
Notes
2004-03-23 00:00:00APPROVED BY DAVID KANNING PLANNER 659-80
 31

Review Stop Z ZONING
Rev No 1 Status F Date 2004-03-18 Cont ID  
Sent By mmclean Date 2004-03-18 Time 16:04 Rev Time 0.00
Received By mmclean Date 2004-03-18 Time 16:04 Sent To  
Notes
2004-03-18 00:00:00DENIED, NEED TO BE 10FT ON THE SIDE FROM
 WATERS EDGE TO PROPERTY LINE.CALLED
 CONTR FILE P MM