Plan Review Details - Permit 04030626
Plan Review Stops For Permit 04030626
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-04-29 Cont ID  
Sent By nmccray Date 2004-04-29 Time 15:27 Rev Time 0.00
Received By nmccray Date 2004-04-29 Time 15:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-03-16 Cont ID  
Sent By csiegber Date 2004-04-28 Time 15:07 Rev Time 0.00
Received By nmccray Date 2004-03-16 Time 10:31 Sent To  
Notes
2004-03-16 00:00:00***********DENIED***********************
 1) NEW FIRE ALARM SYSTEMS SHALL BE UL
 LISTED FOR CENTRAL STATION SERVICE.
  
 2) ALL NEW FIRE ALARM SYSTEMS THAT
 SUPERVISE FIRE SPRINKLER SYSTEMS SHALL
 BE UL CERTIFICATED AND HAVE DOCUMENT
 ATTESTING TO THIS CERTIFICATION PRIOR TO
 APPROVAL OF THESE PLANS.
  
 3) THE FIRE ALARM SYSTEM SHALL BE CLASS
 "A" OR FULLY ADDRESSABLE.
  
 4) ALL DUCT DETECTORS SHALL SEND AND PUT
 THE SYSTEM IN GENERAL FIRE ALARM MODE IN
 THE CITY OF WEST PALM BEACH NOT A
 SUPERVISORY SIGNAL.
  
 THESE COMMENTS AND NOTES ARE FOR PERMITS
 # 04030626 AND 04030625
  
 NATE M
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-28 Cont ID  
Sent By csiegber Date 2004-04-28 Time 15:07 Rev Time 0.00
Received By csiegber Date 2004-04-28 Time 15:07 Sent To FIRE
Notes
2004-04-28 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-11 Cont ID  
Sent By csiegber Date 2004-03-11 Time 15:49 Rev Time 0.00
Received By csiegber Date 2004-03-11 Time 15:49 Sent To FIRE
Notes
***NONE***