Plan Review Details - Permit 04030485
Plan Review Stops For Permit 04030485
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-04-23 Cont ID  
Sent By jwitmer Date 2004-04-23 Time 12:49 Rev Time 0.55
Received By jwitmer Date 2004-04-23 Time 12:49 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-04-09 Cont ID  
Sent By jwitmer Date 2004-04-09 Time 07:20 Rev Time 0.75
Received By jwitmer Date 2004-04-08 Time 16:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-04-21 Cont ID  
Sent By dpalmer Date 2004-04-21 Time 07:30 Rev Time 0.50
Received By dpalmer Date 2004-04-21 Time 07:30 Sent To  
Notes
2004-04-21 00:00:00******* NOTE *****
  
 HAND WROTE ENG NAME AND LICENSE # ON
 TITLE BLOCK AS REQ'D PER FAC 61G15-23.00
 2.
 REMOVED ALL OLD/VOIDED E-SHEETS.PLEASE
 REMOVE THESE SHEETS FOR FUTURE PROJECTS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-03-23 Cont ID  
Sent By csiegber Date 2004-03-17 Time 13:37 Rev Time 1.00
Received By btrobaug Date 2004-03-23 Time 12:34 Sent To  
Notes
2004-03-23 00:00:00 
 UNSAT
 ~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SEE THE TOTAL AMPS IN THE LOAD
 CALCULATION IS 380 AMPS (SHEET E-3),
 THE SERVICE CONDUCTOR SIZE ON SHEET E-2
 IS 400 MCM WHICH PER TABLE 310.16 @ 335
 AMPS, IS NOT RATED FOR THE LOAD SERVED.
  
 2} THE"#4/OG" CONDUCTOR LISTED ON THE
 RISER SHEET E-2, BEING RAN WITH THE
 FEEDER IS INCORRECT PER 250.122 IF IT
 IS SUPPOSED TO BE THE EQUIPMENT GROUND.
  
 3} THE TOTAL KW AS COMPUTED ACROSS FOR
 L2N,N2NA & N2N DOES NOT SEEM TO ADD
 CORRECTLY, PLEASE CHECK.SHEET E-3.
  
 4} CONTINUOUS LOADS SUCH AS LIGHTING
 MUST BE CALCULATED PER 210.19(A),
 210.20(A) AND 215.2(A). PLEASE ADDRESS
 THIS IN THE CALCULATIONS.
  
 5} PLEASE INDICATE THE LIGHTING BRANCH
 CIRCUIT NUMBERS AND THE CIRCUITING FOR
 THE LIGHTS ON SHEET E-1.
  
 6} PLEASE REFER TO NOTE #10 ON SHEET
 E-3. THE REVERENCE TO ARTICLE 380-8(B),
 IS A 1999 CODE REVERENCE. PLEASAE BE
 ADVISED THAT WEST PALM BEACH HAS
 ADOPTED THE 2002 NEC. SEE ARTICLE
 404.8(B).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-04-15 Cont ID  
Sent By mcarsill Date 2004-04-15 Time 14:02 Rev Time 0.00
Received By mcarsill Date 2004-04-15 Time 14:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-03-19 Cont ID  
Sent By mcarsill Date 2004-03-19 Time 14:44 Rev Time 0.00
Received By mcarsill Date 2004-03-19 Time 14:44 Sent To  
Notes
2004-03-19 00:00:001) THERE APPEARS TO BE NO EMERGENCY
 LIGHTING IN THE TESTING OR CONSUMER
 PROCESSORS OFFICE AREA.
  
 2) IT APPEARS THAT ONLY ONE FIRE ALARM
 DEVICE IS PRESENT NEAR THE EXISTING
 STAIR DOOR. COULD NOT LOCATE ANY FIRE
 ALARM EQUIPMENT IN THE LEGAL AREA 202.
  
 3) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
  
 4) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 5) PLEASE INDICATE TYPE OF CONSTRUCTION
 AND CLEARLY STATE IF FIRE SPRINKLERS
 ARE PRESENT OR ABSENT FROM THE SPACE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-15 Cont ID  
Sent By csiegber Date 2004-04-15 Time 09:42 Rev Time 0.00
Received By csiegber Date 2004-04-15 Time 09:42 Sent To  
Notes
2004-04-15 00:00:00TO COMM BD#45

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-17 Cont ID  
Sent By csiegber Date 2004-03-17 Time 13:37 Rev Time 0.00
Received By csiegber Date 2004-03-17 Time 13:37 Sent To  
Notes
2004-03-17 00:00:00TO COMM BD# 28

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-04-06 Cont ID  
Sent By pkrauss Date 2004-04-06 Time 09:14 Rev Time 0.40
Received By pkrauss Date 2004-04-06 Time 08:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-04-01 Cont ID  
Sent By kstevens Date 2004-04-01 Time 17:41 Rev Time 0.25
Received By kstevens Date 2004-04-01 Time 17:41 Sent To  
Notes
2004-04-01 00:00:00NO PLUMBING PLANS OR WORK SHOWN