Plan Review Stops For Permit 04030485 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2004-04-23 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2004-04-23 |
Time |
12:49 |
Rev Time |
0.55 |
Received By |
jwitmer |
Date |
2004-04-23 |
Time |
12:49 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2004-04-09 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2004-04-09 |
Time |
07:20 |
Rev Time |
0.75 |
Received By |
jwitmer |
Date |
2004-04-08 |
Time |
16:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2004-04-21 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-04-21 |
Time |
07:30 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2004-04-21 |
Time |
07:30 |
Sent To |
|
|
Notes |
2004-04-21 00:00:00 | ******* NOTE ***** | | | | HAND WROTE ENG NAME AND LICENSE # ON | | TITLE BLOCK AS REQ'D PER FAC 61G15-23.00 | | 2. | | REMOVED ALL OLD/VOIDED E-SHEETS.PLEASE | | REMOVE THESE SHEETS FOR FUTURE PROJECTS. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2004-03-23 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-03-17 |
Time |
13:37 |
Rev Time |
1.00 |
Received By |
btrobaug |
Date |
2004-03-23 |
Time |
12:34 |
Sent To |
|
|
Notes |
2004-03-23 00:00:00 | | | UNSAT | | ~~~~~ | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PLEASE SEE THE TOTAL AMPS IN THE LOAD | | CALCULATION IS 380 AMPS (SHEET E-3), | | THE SERVICE CONDUCTOR SIZE ON SHEET E-2 | | IS 400 MCM WHICH PER TABLE 310.16 @ 335 | | AMPS, IS NOT RATED FOR THE LOAD SERVED. | | | | 2} THE"#4/OG" CONDUCTOR LISTED ON THE | | RISER SHEET E-2, BEING RAN WITH THE | | FEEDER IS INCORRECT PER 250.122 IF IT | | IS SUPPOSED TO BE THE EQUIPMENT GROUND. | | | | 3} THE TOTAL KW AS COMPUTED ACROSS FOR | | L2N,N2NA & N2N DOES NOT SEEM TO ADD | | CORRECTLY, PLEASE CHECK.SHEET E-3. | | | | 4} CONTINUOUS LOADS SUCH AS LIGHTING | | MUST BE CALCULATED PER 210.19(A), | | 210.20(A) AND 215.2(A). PLEASE ADDRESS | | THIS IN THE CALCULATIONS. | | | | 5} PLEASE INDICATE THE LIGHTING BRANCH | | CIRCUIT NUMBERS AND THE CIRCUITING FOR | | THE LIGHTS ON SHEET E-1. | | | | 6} PLEASE REFER TO NOTE #10 ON SHEET | | E-3. THE REVERENCE TO ARTICLE 380-8(B), | | IS A 1999 CODE REVERENCE. PLEASAE BE | | ADVISED THAT WEST PALM BEACH HAS | | ADOPTED THE 2002 NEC. SEE ARTICLE | | 404.8(B). | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2004-04-15 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2004-04-15 |
Time |
14:02 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2004-04-15 |
Time |
14:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2004-03-19 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2004-03-19 |
Time |
14:44 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2004-03-19 |
Time |
14:44 |
Sent To |
|
|
Notes |
2004-03-19 00:00:00 | 1) THERE APPEARS TO BE NO EMERGENCY | | LIGHTING IN THE TESTING OR CONSUMER | | PROCESSORS OFFICE AREA. | | | | 2) IT APPEARS THAT ONLY ONE FIRE ALARM | | DEVICE IS PRESENT NEAR THE EXISTING | | STAIR DOOR. COULD NOT LOCATE ANY FIRE | | ALARM EQUIPMENT IN THE LEGAL AREA 202. | | | | 3) PLEASE INDICATE INTERIOR FINISH | | CLASSIFICATION INFORMATION FOR WALLS | | AND CEILINGS. | | | | 4) DEMOLITION, RENOVATION, AND | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | 5) PLEASE INDICATE TYPE OF CONSTRUCTION | | AND CLEARLY STATE IF FIRE SPRINKLERS | | ARE PRESENT OR ABSENT FROM THE SPACE. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2004-04-15 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-04-15 |
Time |
09:42 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-04-15 |
Time |
09:42 |
Sent To |
|
|
Notes |
2004-04-15 00:00:00 | TO COMM BD#45 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2004-03-17 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-03-17 |
Time |
13:37 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-03-17 |
Time |
13:37 |
Sent To |
|
|
Notes |
2004-03-17 00:00:00 | TO COMM BD# 28 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2004-04-06 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2004-04-06 |
Time |
09:14 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2004-04-06 |
Time |
08:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2004-04-01 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2004-04-01 |
Time |
17:41 |
Rev Time |
0.25 |
Received By |
kstevens |
Date |
2004-04-01 |
Time |
17:41 |
Sent To |
|
|
Notes |
2004-04-01 00:00:00 | NO PLUMBING PLANS OR WORK SHOWN |
|
|