Plan Review Details - Permit 04030431
Plan Review Stops For Permit 04030431
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-04-09 Cont ID  
Sent By jwitmer Date 2004-04-09 Time 06:52 Rev Time 0.25
Received By jwitmer Date 2004-04-09 Time 06:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-04-06 Cont ID  
Sent By jwitmer Date 2004-04-06 Time 16:33 Rev Time 0.50
Received By jwitmer Date 2004-04-06 Time 16:33 Sent To  
Notes
2004-04-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04030431
 ADD: 303 EVERNIA ST
 CONT: RAYMOND NORDINE
 TEL: (561)252-4662
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1) PLANS MAY HAVE HEADER STRIP CUT OFF
 BUT PLANS HAVE WORDING THAT THE ARCHI-
 TECT IS D. NICHOLS INC.
  
 2)

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-03 Cont ID  
Sent By jwitmer Date 2004-04-03 Time 12:57 Rev Time 0.75
Received By jwitmer Date 2004-04-03 Time 12:36 Sent To PC
Notes
2004-04-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04030431
 ADD: 303 EVERNIA ST SUITE B/C
 CONT: RAYMOND NORDINE
 TEL: (561)252-4662
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 2)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2004-04-07 Cont ID  
Sent By btrobaug Date 2004-04-07 Time 17:57 Rev Time 0.25
Received By btrobaug Date 2004-04-07 Time 17:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-03-11 Cont ID  
Sent By dpalmer Date 2004-03-11 Time 18:08 Rev Time 0.33
Received By dpalmer Date 2004-03-11 Time 18:08 Sent To  
Notes
2004-03-11 00:00:00********** UNSAT ******************
  
 1)NOTE: PLEASE SEE SHEETS SHOWS NEW
 ELECTRICAL, YET APPLICATION IS FOR A
 NEW TENANT WALL ONLY?
 PLEASE SUBMIT AND SHOW WORK ONLY TO BE
 DONE.
  
 2)NOTE: PLEASE SEE FS 481.221, PLANS
 CONTAINING A TITLE BLOCK BY AN ARCH,
 MUST BE SIGNED, DATED AND SEALED BY THAT
 ARCH OF RECORD.
  
 IF NO ELECTRICAL WORK IS BEING DONE,
 PLEASE REMOVE.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-04-08 Cont ID  
Sent By mcarsill Date 2004-04-08 Time 15:34 Rev Time 0.00
Received By mcarsill Date 2004-04-08 Time 15:34 Sent To  
Notes
2004-04-08 00:00:001) DRYWALL PLANNED FOR USE TO CLOSE
 THE OPENING SHALL BE 5/8" TYPE X
 FIRE RATED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2004-04-06 Cont ID  
Sent By mcarsill Date 2004-04-06 Time 14:46 Rev Time 0.00
Received By mcarsill Date 2004-04-06 Time 14:46 Sent To  
Notes
2004-04-06 00:00:001) PLANS HAVE INFORMATION SCRATCHED
 OUT. THE DRAWINGS DO NOT ILLUSTRATE
 WHAT NEW WORK IS PLANNED. PLEASE
 CLARIFY. WHERE IS THE NEW WORK PLANNED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-03-09 Cont ID  
Sent By mcarsill Date 2004-03-09 Time 16:27 Rev Time 0.00
Received By mcarsill Date 2004-03-09 Time 16:27 Sent To  
Notes
2004-03-09 00:00:001) PLANS NOT SIGNED AND SEALED. PLANS
 RUN THROUGH COPY MACHINE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-08 Cont ID  
Sent By csiegber Date 2004-04-08 Time 14:09 Rev Time 0.00
Received By csiegber Date 2004-04-08 Time 14:09 Sent To  
Notes
2004-04-08 00:00:00TO COMM BD#7

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-05 Cont ID  
Sent By csiegber Date 2004-04-05 Time 11:11 Rev Time 0.00
Received By csiegber Date 2004-04-05 Time 11:11 Sent To  
Notes
2004-04-05 00:00:00TO COMM BD#7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-03 Cont ID  
Sent By csiegber Date 2004-03-09 Time 09:32 Rev Time 0.00
Received By jwitmer Date 2004-03-09 Time 09:32 Sent To PC
Notes
2004-03-09 00:00:00TO COMM BD#24

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-03-29 Cont ID  
Sent By msmith Date 2004-03-29 Time 08:54 Rev Time 0.00
Received By msmith Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-03-22 Cont ID  
Sent By kstevens Date 2004-03-22 Time 12:34 Rev Time 0.25
Received By kstevens Date 2004-03-22 Time 12:34 Sent To  
Notes
2004-03-22 00:00:00NO PLUMBING WORK OR PLANS SUBMITTED