2004-04-13 00:00:00 | DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) THE PLAN REVIEW NUMBER ON THE IMPACT |
| FEE RECEIPT DOES NOT MATCH THE PLAN |
| REVIEW NUMBER ON THE PLANS. PLEASE |
| CORRECT. |
| |
| 3) THE TOTAL SQUARE FEET OF A/C AREA ON |
| THE PLANS IS INCORRECT ON SHEET 3. IT |
| SHOULD BE 3410 SQFT. |
| |
| 4) THE FL PRODUCT APPROVAL #S LISTED FOR |
| TWO OF THE FIXED GLASS WINDOWS IN THE |
| SCHEDULE ON SHEET 3 ARE INCORRECT. THEY |
| SHOULD BE FL 243. |
| |
| 5) PLEASE CLARIFY THE TP4X CONNECTORS |
| SPECIFIED ON SHEET 2 FOR THE 3-2X4 POSTS |
| IN THE WALL BELOW THE GIRDER TRUSS. I |
| COULD NOT LOCATE THEM IN THE CURRENT |
| USP OR SIMPSON CATALOGES AND DID NOT SEE |
| FL PROD.APP. FOR IT. |
| |
| 6) THE WINDOW IN BATH #3 WHICH IS WITHIN |
| 3 FEET HORIZONTALLY OF THE TUB IS |
| REQUIRED TO BE TEMPERED BY FBC 2405.2. |
| |
| 7) SPECIFY THE ATTIC LIVE LOAD ON THE |
| PLANS. SEE FBC TABLE 1604.1. |
| |
| 8) FOR CLARITY, PLEASE INDICATE WHICH |
| CONNECTORS ARE FOR THE FLOOR TRUSSES ON |
| THE TRUSS TIE DOWN LAYOUT ON SHEET 9. |
| |
| 9) SUBMIT STATE PRODUCT APPROVAL FOR THE |
| SINGLE OUTSWING EXTERIOR DOOR AT BATH #2 |
| |
| 10) SUBMIT STATE PRODUCT APPROVAL WITH |
| APPROVED STATUS FOR THE COLLIER GARAGE |
| DOOR. |
| |
| 11) SUBMIT STATE OR LOCAL PRODUCT |
| APPROVAL FOR THE 8'X7' GARAGE DOOR. THE |
| DRAWINGS SUBMITTED FOR THE COLLIER |
| GARAGE DOOR IS LIMITED TO A MINIMUM SIZE |
| OF 10'X6'. |
| |
| 12) THE TRUSS ANCHOR SCHEDULE ON SHEET 9 |
| LISTS A NUE-VUE NVSTA 48 CONNECTOR. THE |
| STATE PRODUCT APPROVAL SUBMITTED LISTS A |
| NVRT 48 OR NVSTA 22. PLEASE CLARIFY. |
| |
| 13) THE TRUSS CONNECTOR SCHEDULE LISTS A |
| SIMPSON HUC 412 CONNECTOR WITH 1505# OF |
| UPLIFT. THE STATE PRODUCT APPROVAL |
| SUBMITTED IS FOR A HU 412 WITH 905# OF |
| UPLIFT. PLEASE CLARIFY. |
| |
| 14) THE SUBMITTAL FOR THE BUTT GLASS |
| WIDOW IS INCOMPLETE AND HAS ERRORS. THE |
| THIRD PARTY QUAILTY ASSURANCE IS |
| REQUIRED. THE DIMENSIONS OF THE PANELS |
| NEEDS TO MATCH THE ARCHITECTURAL PLANS. |
| THE LOT # ON SHEET 1 OF 2 IS INCORRECT. |
| SPECIFY THE DESIGN PRESSURES. SUBMIT |
| THE CALCULATIONS. SUBMIT THE SPECS. FOR |
| THE GE 1200 SILICONE. |
| |