Plan Review Details - Permit 04030277
Plan Review Stops For Permit 04030277
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-05 Cont ID  
Sent By csiegber Date 2004-03-05 Time 11:56 Rev Time 0.00
Received By csiegber Date 2004-03-05 Time 11:56 Sent To P
Notes
2004-03-05 00:00:00TO GAS

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-03-17 Cont ID  
Sent By csiegber Date 2004-03-05 Time 11:56 Rev Time 0.50
Received By kstevens Date 2004-03-17 Time 11:11 Sent To  
Notes
2004-03-17 00:00:00 
  
  
  
  
  
 PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING.
  
 IF WATER HEATER RM IS A CONFINED SPACE,
 OPENINGS REQUIRED PER SECTION 304.3.1 0R
 SECTION 304.3.2 SHALL BE INSTALLED.
 MINIMUM 3,750 CUBIC FEET REQUIRED.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 Z