Plan Review Details - Permit 04030171
Plan Review Stops For Permit 04030171
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-04-12 Cont ID  
Sent By lsmith Date 2004-04-12 Time 10:54 Rev Time 0.50
Received By lsmith Date 2004-04-12 Time 10:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-15 Cont ID  
Sent By btrobaug Date 2004-04-08 Time 17:46 Rev Time 0.50
Received By lsmith Date 2004-03-15 Time 10:10 Sent To  
Notes
2004-03-15 00:00:00BUILDING PLAN REVIEW FAILED:
  
 1. PLANS MUST SHOW METHOD OF PROTECTING
 POOL FROM OPENINGS OF HOUSE LEADING TO
 POOL AREA.
  
 ANY QUESTIONS PLEASE CALL: LEA SMITH
 805-6713

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-04-08 Cont ID  
Sent By btrobaug Date 2004-04-08 Time 17:46 Rev Time 0.33
Received By btrobaug Date 2004-04-08 Time 17:43 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-03-09 Cont ID  
Sent By kstevens Date 2004-04-07 Time 17:47 Rev Time 0.33
Received By btrobaug Date 2004-03-09 Time 07:27 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-03-30 Cont ID  
Sent By alange Date 2004-03-30 Time 13:32 Rev Time 0.00
Received By alange Date 2004-03-30 Time 13:32 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-08 Cont ID  
Sent By csiegber Date 2004-03-08 Time 16:41 Rev Time 0.00
Received By csiegber Date 2004-03-08 Time 16:41 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-04 Cont ID  
Sent By mmclean Date 2004-03-08 Time 10:26 Rev Time 0.00
Received By csiegber Date 2004-03-04 Time 11:14 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-04-07 Cont ID  
Sent By kstevens Date 2004-04-07 Time 17:46 Rev Time 0.50
Received By kstevens Date 2004-04-07 Time 17:46 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-03-13 Cont ID  
Sent By alange Date 2004-03-30 Time 13:32 Rev Time 0.50
Received By kstevens Date 2004-03-13 Time 12:41 Sent To B
Notes
2004-03-13 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 1) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
  
 2)ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2)- FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-03-08 Cont ID  
Sent By csiegber Date 2004-03-04 Time 11:15 Rev Time 0.00
Received By mmclean Date 2004-03-08 Time 10:26 Sent To I
Notes
***NONE***