Plan Review Details - Permit 04030145
Plan Review Stops For Permit 04030145
Review Stop G GAS REVIEW
Rev No 1 Status F Date 2005-03-05 Cont ID  
Sent By kstevens Date 2005-03-05 Time 08:54 Rev Time 0.45
Received By kstevens Date 2005-03-05 Time 08:54 Sent To Z
Notes
2005-03-05 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 A) THE FOLLOWING INFORMATION REQUIRED
 FOR THE GAS REVISION:
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED)
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 5) EXHAUST TERMINATION FOR GENERATOR.
 6) ALL DRAWINGS SHALL BEAR THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN. SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-18 Cont ID  
Sent By adarroug Date 2005-02-18 Time 16:43 Rev Time 0.00
Received By adarroug Date 2005-02-18 Time 16:43 Sent To P
Notes
2005-02-18 00:00:00TO KSTEVENS DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-04 Cont ID  
Sent By csiegber Date 2004-03-04 Time 11:13 Rev Time 0.00
Received By csiegber Date 2004-03-04 Time 11:13 Sent To P
Notes
2004-03-04 00:00:00TO GAS

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-03-12 Cont ID  
Sent By csiegber Date 2004-03-04 Time 11:13 Rev Time 0.50
Received By kstevens Date 2004-03-12 Time 13:50 Sent To  
Notes
2004-03-12 00:00:00 
  
  
  
  
 IF DRYER ROOM IS A CONFINED SPACE,
 OPENINGS REQUIRED PER SECTION 304.3.1 0R
 SECTION 304.3.2 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 Z

Review Stop Z ZONING
Rev No 1 Status P Date 2005-03-09 Cont ID  
Sent By mmclean Date 2005-03-07 Time 11:41 Rev Time 0.00
Received By mmclean Date 2005-03-07 Time 12:24 Sent To P
Notes
2005-03-07 00:00:00CALLED CONTR, LEFT MSG REGARDING
 CLARIFICATION FOR REVISION. NEED TO KNOW
 IF THE REVISION IS FOR A NEW GENERATOR
 PAD AND WHAT'S THE SIDE SETBACK OF
 GENERATOR FROM PROPERTY LINE..
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN