Plan Review Details - Permit 04021048
Plan Review Stops For Permit 04021048
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-06-04 Cont ID  
Sent By jwitmer Date 2004-06-04 Time 16:08 Rev Time 0.56
Received By jwitmer Date 2004-06-04 Time 16:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-05-19 Cont ID  
Sent By jwitmer Date 2004-05-19 Time 11:05 Rev Time 1.22
Received By jwitmer Date 2004-05-19 Time 11:05 Sent To  
Notes
2004-05-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04021048
 ADD: 3031 OKEECHOBEE BLVD
 CONT: POPPER & ASSOCIATES
 TEL: (561)719-7133
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1) COMMENT# 1 FROM PREVIOUS REVIEW:
 ADDITIONAL INFO ON THE WAYNE DAWSON
 ROLL UP DOOR.
 THE INFORMATION PROVIDED HAS DESCREPAN-
 CIES, THE FIRST SUBITTAL IS FOR OVERHEAD
 GARAGE DOOR(FIRE RATED) SERIES 640 OR
 641. THE SECOND IS A MIAMI-DADE NOA FOR
 A EXTERIOR GARGE DOOR SERIES 610/620,
 THE THIRD IS FOR WAYNE DALSON SERIES
 AKBAR 89. NONE OF THESE SUBMITTALS ACT-
 UALLY SPELL OUT WHAT RATING IS TO BE
 USED. THE COVERSHEET INDICATES A SEPERAT
 ION FROM THE SHOWROOMWITH THE PARTS
 STORAGE. FOR S2 STORAGE A 2 HR WALL AND
 1 1/2 HR OPENING PROTECTIVES REQUIRED.
 SUBMIT THE ACTUAL UNIT TO BE INSTALLED!
  
 THE SECOND ISSUE WITH THIS ISSUE IS THE
 DETAIL-1, THE ROLL DOWN DOOR ASSUMED TO
 BE 1 1/2 HR RATED IS TO SEAL AGAINST THE
 NEW COUNTERTOP, WHICH IS (2) LAYERS OF
 PLYWOOD SEE 709.6.2A,5/8" PLYWOOD IS ASS
 IGNED A TIME OF 15 MIN. EVEN IF WE WENT
 WITH 20 MIN FOR 3/4" TWO LAYERS STILL IS
 GOOD FOR 40 MINUTES?
  
 2) COMMENT "F" FROM PREVIOUS REVIEW DEAL
 S WITH THE EXITING OF THE 2ND FLOOR.
 THE ANSWER WAS , EXITING NOT AFFECTED BY
 THE GOING THROUGH THE FLOOR.
 THE XEROX SUBMITTAL ARE NOT FOR THE
 2ND FLOOR BUT THE FIRST FLOOR. THE AREA
 WHERE THE FLOOR IS CUT AWAY MAY AFFECT
 TRAVEL DISTANCES TO EXITING FOR THE
 SECOND FLOOR THIS IS WHY THE REQUEST WAS
 MADE AND STILL REMAINS A UNANSWERED QUES
 TION?
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-06 Cont ID  
Sent By jwitmer Date 2004-03-06 Time 14:34 Rev Time 0.00
Received By jwitmer Date 2004-03-06 Time 14:34 Sent To  
Notes
2004-03-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04021048
 ADD: 3031 OKEECHOBEE BLVD
 CONT: POPPER & ASSOCIATES, INC
 TEL: (561)719-7133
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 A) PROVIDE INFORMATION ON THE WAYNE-
 DAWSON 3 HR ROLL UP DOOR. SPECS &
 INSTALLATION SCHEDULE.
 B) PROVIDE INFO FOR THE CAROUSELS BOTH
 THE 946 & 2060.
 C) IS THIS AREA FIRE SPRINKLERED? WHAT
 HEADS ARE TO BE REMOVED, OR MOVED?
 WHAT CLEARENCES WILL THERE BE FROM
 THE FIRE SPRINKLERS TO THE CAROUSEL?
 D) THE GUARDRAIL DOES NOT GIVE ANY IN-
 FORMATION AS TO COMPLYING WITH SEC-
 TION 1608 SHOW CALCS FOR 1608.2.2.1
 AND 1608.2.2.4.
 E) NOTE ON THE PLAN THE RATING OF THE
 STORAGE OCCUPANCY ?
 F) SHOW EGRESS FROM THE 2ND STORY.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2004-03-08 Cont ID  
Sent By dpalmer Date 2004-03-08 Time 06:05 Rev Time 0.25
Received By dpalmer Date 2004-03-08 Time 06:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2004-03-01 Cont ID  
Sent By dpalmer Date 2004-03-01 Time 12:23 Rev Time 0.25
Received By dpalmer Date 2004-03-01 Time 11:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-05-26 Cont ID  
Sent By nmccray Date 2004-05-26 Time 15:16 Rev Time 0.00
Received By nmccray Date 2004-05-26 Time 15:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2004-05-21 Cont ID  
Sent By mcarsill Date 2004-05-21 Time 11:27 Rev Time 0.00
Received By mcarsill Date 2004-05-21 Time 11:27 Sent To  
Notes
2004-05-21 00:00:001) THE INFORMATION PROVIDED DOES NOT
 SEEM TO CORRESPOND WITH EACH OTHER.
 ALSO PLEASE PROVIDE MORE CLARITY ON
 EXITING. THANK YOU.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-03-12 Cont ID  
Sent By mcarsill Date 2004-03-12 Time 18:15 Rev Time 0.00
Received By mcarsill Date 2004-03-12 Time 18:15 Sent To  
Notes
2004-03-12 00:00:001) PLEASE SEE BUILDING PLAN
 REVIEWER COMMENTS. PLEASE RESPOND TO
 THESE COMMENTS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-05-26 Cont ID  
Sent By alange Date 2004-05-26 Time 10:47 Rev Time 0.00
Received By alange Date 2004-05-26 Time 10:47 Sent To  
Notes
2004-05-26 00:00:00TO COMM BD. #64

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-05-18 Cont ID  
Sent By csiegber Date 2004-05-18 Time 11:44 Rev Time 0.00
Received By csiegber Date 2004-05-18 Time 11:44 Sent To  
Notes
2004-05-18 00:00:00TO COMM BD#58

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-23 Cont ID  
Sent By lmartine Date 2004-03-23 Time 08:25 Rev Time 0.00
Received By lmartine Date 2004-02-25 Time 14:14 Sent To  
Notes
2004-02-25 00:00:00TO COMM BD#47