2004-05-19 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 04021048 |
| ADD: 3031 OKEECHOBEE BLVD |
| CONT: POPPER & ASSOCIATES |
| TEL: (561)719-7133 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 2ND REVIEW |
| ACTION: DENIED |
| |
| 1) COMMENT# 1 FROM PREVIOUS REVIEW: |
| ADDITIONAL INFO ON THE WAYNE DAWSON |
| ROLL UP DOOR. |
| THE INFORMATION PROVIDED HAS DESCREPAN- |
| CIES, THE FIRST SUBITTAL IS FOR OVERHEAD |
| GARAGE DOOR(FIRE RATED) SERIES 640 OR |
| 641. THE SECOND IS A MIAMI-DADE NOA FOR |
| A EXTERIOR GARGE DOOR SERIES 610/620, |
| THE THIRD IS FOR WAYNE DALSON SERIES |
| AKBAR 89. NONE OF THESE SUBMITTALS ACT- |
| UALLY SPELL OUT WHAT RATING IS TO BE |
| USED. THE COVERSHEET INDICATES A SEPERAT |
| ION FROM THE SHOWROOMWITH THE PARTS |
| STORAGE. FOR S2 STORAGE A 2 HR WALL AND |
| 1 1/2 HR OPENING PROTECTIVES REQUIRED. |
| SUBMIT THE ACTUAL UNIT TO BE INSTALLED! |
| |
| THE SECOND ISSUE WITH THIS ISSUE IS THE |
| DETAIL-1, THE ROLL DOWN DOOR ASSUMED TO |
| BE 1 1/2 HR RATED IS TO SEAL AGAINST THE |
| NEW COUNTERTOP, WHICH IS (2) LAYERS OF |
| PLYWOOD SEE 709.6.2A,5/8" PLYWOOD IS ASS |
| IGNED A TIME OF 15 MIN. EVEN IF WE WENT |
| WITH 20 MIN FOR 3/4" TWO LAYERS STILL IS |
| GOOD FOR 40 MINUTES? |
| |
| 2) COMMENT "F" FROM PREVIOUS REVIEW DEAL |
| S WITH THE EXITING OF THE 2ND FLOOR. |
| THE ANSWER WAS , EXITING NOT AFFECTED BY |
| THE GOING THROUGH THE FLOOR. |
| THE XEROX SUBMITTAL ARE NOT FOR THE |
| 2ND FLOOR BUT THE FIRST FLOOR. THE AREA |
| WHERE THE FLOOR IS CUT AWAY MAY AFFECT |
| TRAVEL DISTANCES TO EXITING FOR THE |
| SECOND FLOOR THIS IS WHY THE REQUEST WAS |
| MADE AND STILL REMAINS A UNANSWERED QUES |
| TION? |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |