Plan Review Details - Permit 04021028
Plan Review Stops For Permit 04021028
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-03-09 Cont ID  
Sent By btrobaug Date 2004-03-09 Time 16:53 Rev Time 0.50
Received By btrobaug Date 2004-03-09 Time 16:53 Sent To  
Notes
2004-03-09 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 SUBMIT PANEL SCHEDULES INDICATING
 COMPLIANCE WITH 210.11(C)(3),210.12 AND
 ALL OTHER APPLICABLE SECTIONS OF THE
 2002 NEC.NOTE SMOKE DETECTORS MUST BE
 INSTALLED PER 1999 NFPA-72, AND ALSO
 MUST BE ARC FAULT PROTECTED PER 210.12.
 SUBMIT THE ABOVE INFORMATION FOR
 REVIEW PRIOR TO ROUGH INSPECTION. ALSO
 SHOW CHANGES ON PLANS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2004-03-09 Cont ID  
Sent By csiegber Date 2004-02-25 Time 12:12 Rev Time 0.25
Received By btrobaug Date 2004-03-03 Time 09:21 Sent To  
Notes
2004-03-03 00:00:00 
 PLEASE SUBMIT PLANS. PLANS SUBMITTED
 UNDER THE PRIMARY PERMIT WHERE
 WITHDRAWN.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-25 Cont ID  
Sent By csiegber Date 2004-02-25 Time 12:12 Rev Time 0.00
Received By csiegber Date 2004-02-25 Time 12:12 Sent To E
Notes
***NONE***