Plan Review Details - Permit 04020945
Plan Review Stops For Permit 04020945
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-04-02 Cont ID  
Sent By jwitmer Date 2004-04-02 Time 12:48 Rev Time 1.00
Received By jwitmer Date 2004-04-02 Time 12:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-08 Cont ID  
Sent By jwitmer Date 2004-03-08 Time 09:12 Rev Time 1.00
Received By jwitmer Date 2004-03-08 Time 09:12 Sent To  
Notes
2004-03-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04020945
 ADD: 625 N FLAGLER DR
 CONT: PASS INTERNATIONAL INC
 TEL: (561)706-7201
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL. EXISTING DOOR# 7 TO
 COMPLY WITH FIGURE# 25.
 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-04-05 Cont ID  
Sent By btrobaug Date 2004-04-05 Time 12:29 Rev Time 0.50
Received By btrobaug Date 2004-04-05 Time 11:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-03-01 Cont ID  
Sent By dpalmer Date 2004-03-01 Time 06:12 Rev Time 0.50
Received By dpalmer Date 2004-03-01 Time 06:01 Sent To  
Notes
2004-03-01 00:00:00**********UNSAT *************
  
 1)NOTE: PLEASE INCLUDE PRINTED NAME IN
 TITLE BLOCK. PLEASE INCLUDE LICENSE #.
 PRINTED NAME AND LICENSE HAS BEEND RED-
 -LINED ON PREVIOUS PLANS, HOWEVER NEEDS
 TO BE ADDED PERMANENTLY.
 61G1-16.004, FS 481.219
  
  
 2)NOTE: PLEASE SEE MISSING CIRCUIT
 ATTACHED TO EM LT E-3 RM 100.
 700.12E
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-02-20 Cont ID  
Sent By mcarsill Date 2004-02-20 Time 15:56 Rev Time 0.00
Received By mcarsill Date 2004-02-20 Time 15:56 Sent To  
Notes
2004-02-20 00:00:001) DOOR CLOSER REQUIRED ON DOOR FROM
 RECEPTION TO CORRIDOR.
  
 2) PROVIDE SEPARATE PLANS AND PERMITS
 FOR ANY FIRE SPRINKLER REMODEL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-19 Cont ID  
Sent By csiegber Date 2004-03-19 Time 16:45 Rev Time 0.00
Received By csiegber Date 2004-03-19 Time 16:45 Sent To  
Notes
2004-03-19 00:00:00TO COMM BD#22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-20 Cont ID  
Sent By csiegber Date 2004-02-20 Time 11:33 Rev Time 0.00
Received By csiegber Date 2004-02-20 Time 11:32 Sent To  
Notes
2004-02-20 00:00:00TO COMM BD #42

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-04-05 Cont ID  
Sent By pkrauss Date 2004-04-05 Time 12:41 Rev Time 0.25
Received By pkrauss Date 2004-04-05 Time 12:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-03-04 Cont ID  
Sent By pkrauss Date 2004-03-04 Time 15:03 Rev Time 0.40
Received By pkrauss Date 2004-03-04 Time 15:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-03-22 Cont ID  
Sent By kstevens Date 2004-03-22 Time 12:55 Rev Time 0.25
Received By kstevens Date 2004-03-22 Time 12:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-03-03 Cont ID  
Sent By kstevens Date 2004-03-03 Time 17:24 Rev Time 0.50
Received By kstevens Date 2004-03-03 Time 17:24 Sent To  
Notes
2004-03-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 1) SUBMIT MANUF. SPECIFICATION SHEETS
 FOR WASTE PUMP. MANUF. SHEETS SHALL SHOW
 LISTING FOR PUMP.
  
 2) NAME AND LICENSE NUMBER OF ARCHITECT
 SHALL BE LOCATED ON TITLE BLOCE PER
 FFA 61G1-16.004(6) & FS 481.219
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]