Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-03-04 Cont ID  
Sent By pkrauss Date 2004-03-04 Time 14:14 Rev Time 0.40
Received By pkrauss Date 2004-03-04 Time 14:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-02-24 Cont ID  
Sent By csiegber Date 2004-02-19 Time 15:50 Rev Time 0.40
Received By pkrauss Date 2004-02-24 Time 09:49 Sent To  
Notes
2004-02-24 00:00:00DENIED:
 PLEASE INDICATE SCOPE OF WORK WITH THIS
 PERMIT APPLICATION.
 1.PLEASE PROIVDE OUTSIDE AIR
 CALCULATIONS FOR EACH TENANT SUBMITTED
 UNDER THIS PERMIT.
  
 2.PROVIDE SPECIFIC INFORMATION ON THE
 EQUIPMENT.EQUIPMENT SCHEDULE
 INDICATES 2 - 5 TON SYSTEMS, PLEASE
 CLARIFY.
  
 3.ENERGY CALCULATIONS NOT SUBMITTED,
 WAS THIS PROVIDED WITH ANOTHER PERMIT?
  
 4.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED FOR AHU-1. 2001
 FBC(M) 307.2.3.
  
 SPOKE WITH JEFF BERKUN, ENGINEER CAN DO
 THE ABOVE REQUIREMENTS WITH A SIGNED,
 SEALED AND DATED LETTER.TWO COPIES
 REQUIRED.PLANS ARE OTHERWISE CODE
 COMPLIANT.
  