Plan Review Details - Permit 04020772
Plan Review Stops For Permit 04020772
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-03-25 Cont ID  
Sent By jleech Date 2004-03-08 Time 16:57 Rev Time 2.20
Received By alange Date 2004-03-25 Time 09:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-12-15 Cont ID  
Sent By btrobaug Date 2004-12-15 Time 16:18 Rev Time 0.75
Received By btrobaug Date 2004-12-15 Time 14:50 Sent To  
Notes
2004-12-15 00:00:00 
  
 THE RECEPTACLES REDLINED ON THE
 REVIEWED
 SET OF PLANS TO COMPLY WITH 210.52 DO
 NOT APPEAR TO HAVE BEEN INSTALLED. SEE
 HIGHLIGHTED AREAS ON THE PLANS BEING
 RETURNED.
  
 THE SMOKE DETECTOR THAT WAS RELOCATED TO
 THE FOYER FROM THE HALL OUTSIDE BEDROOM
 #2 DOES NOT MEET THE INTENT OF NFPA-72,
 8-1.4.1.6.2 "IMMEDIATE VICINITY"
 ESPECIALLY GIVEN THE FACT OF THE DOOR
 THAT COULD CLOSE THE HALL OFF FROM THE
 DETECTOR.
  
 THE PLANS MUST BE REVISED BY THE
 DESIGNER OF RECORD AND THAT PERSONS NAME
 PRINTED AND SIGNED ON THE
 PAGE(S).HANDDRAWN CHANGES WILL NOT BE
 ACCEPTED PER 104.2.1 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-02-24 Cont ID  
Sent By btrobaug Date 2004-02-24 Time 08:20 Rev Time 0.50
Received By btrobaug Date 2004-02-24 Time 07:42 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-20 Cont ID  
Sent By pkrauss Date 2004-08-20 Time 08:51 Rev Time 0.00
Received By pkrauss Date 2004-08-20 Time 08:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-25 Cont ID  
Sent By mmclean Date 2004-02-19 Time 11:14 Rev Time 0.00
Received By alange Date 2004-02-18 Time 09:02 Sent To  
Notes
2004-02-19 00:00:00TO SFD RACK/E
2004-02-18 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-08-20 Cont ID  
Sent By pkrauss Date 2004-08-20 Time 08:50 Rev Time 0.30
Received By pkrauss Date 2004-08-20 Time 08:40 Sent To  
Notes
2004-08-20 00:00:00RE-STAMP/PLANS DESTROYED BY RAIN

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-02-28 Cont ID  
Sent By btrobaug Date 2004-02-24 Time 08:20 Rev Time 0.25
Received By hmoser Date 2004-02-28 Time 11:03 Sent To P
Notes
2004-02-28 00:00:00PASS PRIVISO
 REFER TO SECTION 601.4 BALANCED RETURN
 AIR FOR MASTER.
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-03-08 Cont ID  
Sent By hmoser Date 2004-02-28 Time 11:03 Rev Time 0.25
Received By jleech Date 2004-03-08 Time 16:56 Sent To B
Notes
2004-03-08 00:00:00NO RISER DIAGRAM. NO PLUMBING PLAN
 REVIEW.

Review Stop Z ZONING
Rev No 1 Status P Date 2004-02-19 Cont ID  
Sent By mmclean Date 2004-02-19 Time 11:14 Rev Time 0.00
Received By mmclean Date 2004-02-19 Time 11:14 Sent To I
Notes
***NONE***