Plan Review Details - Permit 04020465
Plan Review Stops For Permit 04020465
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-04-05 Cont ID  
Sent By btrobaug Date 2004-04-05 Time 10:19 Rev Time 0.00
Received By btrobaug Date 2004-04-05 Time 10:19 Sent To  
Notes
2004-04-05 00:00:00 
 OK PER JIM W./WRT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-06 Cont ID  
Sent By jwitmer Date 2004-03-06 Time 15:28 Rev Time 0.50
Received By jwitmer Date 2004-03-06 Time 15:28 Sent To  
Notes
2004-03-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04020465
 ADD: 5601 GRENWOOD AVE
 CONT:TBD, STEWART ENTERPRISE
 TEL: (504) 729-1908
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 PLAN REVIEW
 1ST REVIEW
 ACTION: DENIED
  
 1) THE PLANS ARE CODE COMPLIANT,
 ALTHOUGH CODE COMPLIANT THE PLANS SUBMIT
 TED FOR PLAN REVIEW IF SUBMITTED FOR
 PERMIT WOULD FAIL BECAUSE OF THE MISSING
 LICENSING INFO BY THE ARCHETECT AND
 FIRM SEE FAC 61G15-23.002/ FL SS 481.219
 PROVIDE ALL LICENSE INFORMATION ON THE
 TITLE BLOCKS FOR THE ARCH/ ARCH FIRM,
 MISSING CERTIFICATION OF AUTHORIZATION
 NUMBER.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-04-05 Cont ID  
Sent By btrobaug Date 2004-04-05 Time 09:53 Rev Time 0.75
Received By btrobaug Date 2004-04-05 Time 08:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-02-19 Cont ID  
Sent By dpalmer Date 2004-02-19 Time 15:46 Rev Time 0.33
Received By dpalmer Date 2004-02-19 Time 15:43 Sent To  
Notes
2004-02-19 00:00:00**********UNSAT **************
  
 1)NOTE: PLANS ARE ONLY IN FOR PLAN
 REVIEW AND NOT FOR PERMIT.
  
 2)NOTE: PLEASE PROVIDE ALL LICENSE
 INFORMATION ON TITLE BLOCKS FOR ARCH/
 ARCH FIRM AS REQUIRED UNDER FAC 61G1-16.
 004. PLEASE SEEE FS 481.219 FOR REQ'D
 CERTIFICATE OF AUTHORIZATION # . THIS
 IS REQUIRED FOR ALL SHEETS AND TRADES
 WEATHER OR NOT COMMENT IS MADE BY
 OTHER REVIEWERS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-02-13 Cont ID  
Sent By mcarsill Date 2004-02-13 Time 14:22 Rev Time 0.00
Received By mcarsill Date 2004-02-13 Time 14:22 Sent To  
Notes
2004-02-13 00:00:001) DEMOLITION, RENOVATION, AND
 CONSTRUCTION SHALL COMPLY WITH
 NFPA 241.
  
 2) DEBRIS SHALL BE REMOVED FROM THE
 BUILDING DAILY.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 834-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-16 Cont ID  
Sent By csiegber Date 2004-03-16 Time 14:51 Rev Time 0.00
Received By csiegber Date 2004-03-16 Time 14:51 Sent To  
Notes
2004-03-16 00:00:00TO COMM BD#15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-05 Cont ID  
Sent By btrobaug Date 2004-04-05 Time 10:19 Rev Time 0.00
Received By btrobaug Date 2004-02-11 Time 15:39 Sent To  
Notes
2004-02-11 00:00:00TO COMM BD#24

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-02-24 Cont ID  
Sent By pkrauss Date 2004-02-24 Time 14:24 Rev Time 0.35
Received By pkrauss Date 2004-02-24 Time 14:24 Sent To  
Notes
2004-02-24 00:00:00NO MECHANICAL PLANS SUBMITTED FOR REVIEW
 MECHANICAL NOTES ON PLAN SHEET A-1.
 PLEASE PROVIDE PLANS WITH MECHANICAL
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.