|
 |
 |
 |
 |
 |
Plan Review Details - Permit 04020367
Plan Review Stops For Permit 04020367 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2004-03-06 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2004-03-06 |
Time |
15:02 |
Rev Time |
1.00 |
Received By |
jwitmer |
Date |
2004-03-06 |
Time |
15:02 |
Sent To |
PC |
|
Notes |
2004-03-06 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 04020367 | | ADD: 2151 45TH ST# 209 | | CONT: MIKE MOORE CONST | | TEL: (561)262-6605 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | 1ST REVIEW | | ACTION: DENIED | | | | 1) PLEASE PROVIDE A COMPLETE FLOORPLAN | | TO SEE IF THE 2 EXISTS PROVIDED MEET | | THE 1/2 THE DIAGONAL FOR EXISTING. IS | | THE BUILDING FIRESPRINKLERED? | | | | 2) PROVIDE ADD INFO FOR THE (2) EGRESS | | DOORS, ARE THEY FIRE RATED AND DO THEY | | HAVE CLOSERS? | | | | 3) TABLE 803.3 MINIMUM INTERIOR FINISH | | CLASSIFICATION; PROVIDE INFORMATION | | BASED ON INTERIOR FINISH REQUIREMENTS | | BASED ON OCCUPANCY. | | | | 4) THE BREAK ROOM SINK MUST MEET THE | | FL ACCESSIBILITY CODE 11-4.24 (1-7) | | | | 5)704.2.1.4 CORRIDOR PARTITIONS, SMOKE | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | ITIONS, EXIT ENCLOSURES, AND FIRE | | RATED WALLS REQUIRED TO HAVE PROTECTED | | OPENINGS SHALL BE EFFECTIVELY AND | | PERMANETLY IDENTIFIED WITH SIGNS OR | | STENCILING IN A MANNER ACCEPTABLE TO THE | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | CEILING CEILING AND IN CONCEALED SPACES. | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | PROTECT ALL OPENINGS". | | | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2004-02-19 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-02-19 |
Time |
13:46 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2004-02-19 |
Time |
13:46 |
Sent To |
|
|
Notes |
2004-02-19 00:00:00 | ************** UNSAT ************* | | | | 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS | | AS THEY WILL HAVE AN AFFECT ON ELEC- | | -TRICAL PLANS. | | | | 2)NOTE: PLEASE SHOW ALL CIRCUITING ON | | PLANS AND CORRELATE WITH SUBMITTED | | PANEL SCHEDULE. | | PLEASE SEE 700.12 FOR CIRCUITING OF | | EM/EXT LTS. | | | | 3)NOTE: PLEASE VERIFY OCP SHOWN FOR | | AHU @5KW. MIN OCP IS 125% PER 424.3B | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2004-02-13 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2004-02-13 |
Time |
14:24 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2004-02-13 |
Time |
14:24 |
Sent To |
|
|
Notes |
2004-02-13 00:00:00 | 1) ELECTRICAL PLANS DO NOT DIPLAY | | ANY EXISTING OR NEW EXIT SIGNS. | | | | 2) PLANS DO NOT INDICATE THAT THE | | EXISTING 3068 DOORS FROM THE EXISTING | | CORRDIOR ARE FIRE RATED AND ARE | | EQUIPPED WITH SELF-CLOSING DEVICES. | | | | 3) ARE THERE ANY NEW OR EXISTING | | FIRE ALARM EQUIPMENT LOCATED WITHIN | | THE SPACE. | | | | 4) PLEASE INDICATE INTERIOR FINISH | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2004-03-06 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2004-03-06 |
Time |
15:15 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2004-02-11 |
Time |
15:13 |
Sent To |
PC |
|
Notes |
2004-02-11 00:00:00 | TO COMM BD#21 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2004-03-02 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2004-03-02 |
Time |
13:49 |
Rev Time |
0.33 |
Received By |
pkrauss |
Date |
2004-03-02 |
Time |
13:48 |
Sent To |
|
|
Notes |
2004-03-02 00:00:00 | NO MECHANICAL PLANS SUBMITTED FOR REVIEW | | PLAN SHEET A-1 HVAC NOTES INDICATE THE | | SUB-CONTRACTOR TO APPLY OF PERMIT. | | PLEASE PROVIDE PLANS WITH OUTSIDE AIR | | CALCULATIONS WITH MECHANICAL PERMIT | | APPLICATION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2004-02-20 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2004-02-20 |
Time |
13:06 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2004-02-20 |
Time |
13:06 |
Sent To |
|
|
Notes |
2004-02-20 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | FBC-2001 CHAPTER 11 | | | | 1) SHT A-1 PLUMBING NOTES: #6 AIR CHAMB- | | ERS ARE NOT APPROVED. DELETE FROM REF- | | ERENCE. SECTION 604.9 | | 2) SHT A-1 FLOOR PLAN, BREAK ROOM SINK | | SHALL COMPLY WITH 11-4.24, 11-4.24.2, | | 11-4.24.3, 11-4.24.4, 11-4.24.5, 11-4.24 | | .6 AND 11-4.24.7. PLEASE SUBMIT A DETAIL | | 3) A SANITARY AND A WATER RISER DIAGRAM | | ARE REQUIRED PER SECTION 104.3.1.1. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |