Plan Review Details - Permit 04020367
Plan Review Stops For Permit 04020367
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-06 Cont ID  
Sent By jwitmer Date 2004-03-06 Time 15:02 Rev Time 1.00
Received By jwitmer Date 2004-03-06 Time 15:02 Sent To PC
Notes
2004-03-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04020367
 ADD: 2151 45TH ST# 209
 CONT: MIKE MOORE CONST
 TEL: (561)262-6605
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE PROVIDE A COMPLETE FLOORPLAN
 TO SEE IF THE 2 EXISTS PROVIDED MEET
 THE 1/2 THE DIAGONAL FOR EXISTING. IS
 THE BUILDING FIRESPRINKLERED?
  
 2) PROVIDE ADD INFO FOR THE (2) EGRESS
 DOORS, ARE THEY FIRE RATED AND DO THEY
 HAVE CLOSERS?
  
 3) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY.
  
 4) THE BREAK ROOM SINK MUST MEET THE
 FL ACCESSIBILITY CODE 11-4.24 (1-7)
  
 5)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-02-19 Cont ID  
Sent By dpalmer Date 2004-02-19 Time 13:46 Rev Time 0.50
Received By dpalmer Date 2004-02-19 Time 13:46 Sent To  
Notes
2004-02-19 00:00:00************** UNSAT *************
  
 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 AS THEY WILL HAVE AN AFFECT ON ELEC-
 -TRICAL PLANS.
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH SUBMITTED
 PANEL SCHEDULE.
 PLEASE SEE 700.12 FOR CIRCUITING OF
 EM/EXT LTS.
  
 3)NOTE: PLEASE VERIFY OCP SHOWN FOR
 AHU @5KW. MIN OCP IS 125% PER 424.3B
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-02-13 Cont ID  
Sent By mcarsill Date 2004-02-13 Time 14:24 Rev Time 0.00
Received By mcarsill Date 2004-02-13 Time 14:24 Sent To  
Notes
2004-02-13 00:00:001) ELECTRICAL PLANS DO NOT DIPLAY
 ANY EXISTING OR NEW EXIT SIGNS.
  
 2) PLANS DO NOT INDICATE THAT THE
 EXISTING 3068 DOORS FROM THE EXISTING
 CORRDIOR ARE FIRE RATED AND ARE
 EQUIPPED WITH SELF-CLOSING DEVICES.
  
 3) ARE THERE ANY NEW OR EXISTING
 FIRE ALARM EQUIPMENT LOCATED WITHIN
 THE SPACE.
  
 4) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-06 Cont ID  
Sent By jwitmer Date 2004-03-06 Time 15:15 Rev Time 0.00
Received By jwitmer Date 2004-02-11 Time 15:13 Sent To PC
Notes
2004-02-11 00:00:00TO COMM BD#21

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-03-02 Cont ID  
Sent By pkrauss Date 2004-03-02 Time 13:49 Rev Time 0.33
Received By pkrauss Date 2004-03-02 Time 13:48 Sent To  
Notes
2004-03-02 00:00:00NO MECHANICAL PLANS SUBMITTED FOR REVIEW
 PLAN SHEET A-1 HVAC NOTES INDICATE THE
 SUB-CONTRACTOR TO APPLY OF PERMIT.
 PLEASE PROVIDE PLANS WITH OUTSIDE AIR
 CALCULATIONS WITH MECHANICAL PERMIT
 APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-02-20 Cont ID  
Sent By kstevens Date 2004-02-20 Time 13:06 Rev Time 0.50
Received By kstevens Date 2004-02-20 Time 13:06 Sent To  
Notes
2004-02-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT A-1 PLUMBING NOTES: #6 AIR CHAMB-
 ERS ARE NOT APPROVED. DELETE FROM REF-
 ERENCE. SECTION 604.9
 2) SHT A-1 FLOOR PLAN, BREAK ROOM SINK
 SHALL COMPLY WITH 11-4.24, 11-4.24.2,
 11-4.24.3, 11-4.24.4, 11-4.24.5, 11-4.24
 .6 AND 11-4.24.7. PLEASE SUBMIT A DETAIL
 3) A SANITARY AND A WATER RISER DIAGRAM
 ARE REQUIRED PER SECTION 104.3.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved